Skip to content

Chapter 4 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

Section 130.5 — ELECTRICAL POWER DISTRIBUTION SYSTEMS

2025 California Energy Code (Title 24, Part 6) · 2025 edition · updated 2026-07-25 · California

Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.5(a) through 130.5(e).

(a) Service electrical metering. Each electrical service or feeder shall have a permanently installed metering system which measures electrical energy use in accordance with Table 130.5-A.

Exception 1 to Section 130.5(a): Service or feeder for which the utility company provides a metering system that indicates instantaneous kW demand and kWh for a utility-defined period.

Exception 2 to Section 130.5(a): Electrical power distribution systems subject to California Electrical Code Article 517.

TABLE 130.5-A—MINIMUM REQUIREMENTS FOR METERING OF ELECTRICAL LOAD

METERING FUNCTIONALITY ELECTRICAL
SERVICES RATED
50 kVA OR LESS
ELECTRICAL SERVICES
RATED MORE THAN 50 kVA
AND LESS THAN OR EQUAL
TO 250 kVA
ELECTRICAL SERVICES
RATED MORE THAN 250 kVA
AND LESS THAN OR EQUAL
TO 1000 kVA
ELECTRICAL
SERVICES RATED
MORE THAN 1000
kVA
Instantaneous (at the time) kW
demand
Required Required Required Required
Historical peak demand (kW) Not required Not required Required Required
Tracking kWh for a user-definable
period
Required Required Required Required
kWh per rate period Not required Not required Not required Required

(b) Separation of electrical circuits for electrical energy monitoring. Electrical power distribution systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to Table 130.5-B.

Exception 1 to Section 130.5(b): For each separate load type, up to 10 percent of the connected load may be of any type.

Exception 2 to Section 130.5(b): Electrical power distribution systems subject to California Electrical Code Article 517.

TABLE 130.5-B—MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD

ELECTRICAL LOAD TYPE ELECTRICAL
SERVICES
RATED 50
kVA OR LESS
ELECTRICAL SERVICES
RATED MORE THAN 50 kVA
AND LESS THAN OR EQUAL
TO 250 kVA
ELECTRICAL SERVICES
RATED MORE THAN 250 kVA
AND LESS THAN OR EQUAL
TO 1000 kVA
ELECTRICAL SERVICES
RATED MORE THAN
1000 kVA
Lighting including exit and egress lighting
and exterior lighting
Not required All lighting in aggregate All lighting disaggregated
by floor, type or area
All lighting
disaggregated by floor,
type or area
HVAC systems and components including
chillers, fans, heaters, furnaces, package
units, cooling towers and circulation
pumps associated with HVAC
Not required All HVAC in aggregate All HVAC in aggregate
and each HVAC load rated
at least 50 kVA
All HVAC in aggregate
and each HVAC load
rated at least 50 kVA
Domestic and service water system
pumps and related systems and
components
Not required All loads in aggregate All loads in aggregate All loads in aggregate
Plug load including appliances rated less
than 25 kVA
Not required All plug load in aggregate
Groups of plug loads
exceeding 25 kVA connected
load in an area less than
5000 sf
All plug load separated by
floor, type or area
Groups of plug loads exceeding
25 kVA connected load in an
area less than 5000 sf
All plug load separated
by floor, type or area
All groups of plug loads
exceeding 25 kVA
connected load in an
area less than 5000 sf

102 2025 CALIFORNIA ENERGY CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

TABLE 130.5-B—MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD—continued

ELECTRICAL LOAD TYPE ELECTRICAL
SERVICES
RATED 50
kVA OR LESS
ELECTRICAL SERVICES
RATED MORE THAN 50 kVA
AND LESS THAN OR EQUAL
TO 250 kVA
ELECTRICAL SERVICES
RATED MORE THAN 250 kVA
AND LESS THAN OR EQUAL
TO 1000 kVA
ELECTRICAL SERVICES
RATED MORE THAN
1000 kVA
Elevators, escalators, moving walks and
transit systems
Not required All loads in aggregate All loads in aggregate All loads in aggregate
Other individual non-HVAC loads or
appliances rated 25 kVA or greater
Not required All loads in aggregate All loads in aggregate All loads in aggregate
Industrial and commercial load centers
25 kVA or greater, including theatrical
lighting installations and commercial
kitchens
Not required All loads in aggregate All loads in aggregate All loads in aggregate
Renewable power source (net or total) Each group Each group Each group Each group
Loads associated with renewable power
source
Not required All loads in aggregate All loads in aggregate All loads in aggregate
Charging stations for electric vehicles All loads in
aggregate
All loads in aggregate All loads in aggregate All loads in aggregate

(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.

Exception to Section 130.5(c): Voltage drop permitted by California Electrical Code Sections 647.4, 695.6 and 695.7.

(d) Circuit controls for 120-volt receptacles and controlled receptacles. In all buildings, both controlled and uncontrolled 120 volt receptacles shall be provided in office areas, lobbies, conference rooms, kitchen areas in office spaces and copy rooms. Additionally, hotel/motel guest rooms shall comply with Section 130.5(d)4.

Plug-in strips and other plug-in devices shall not be used to comply with the requirements of Section 130.5(d).

Controlled receptacles shall meet the following requirements, as applicable:

  1. Install a control capable of automatically shutting OFF the controlled receptacles when the space is typically unoccupied, either at the receptacle or circuit level. When an automatic time switch control is installed it shall incorporate an override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override is initiated and an automatic holiday “shut-OFF” feature that turns OFF all loads for at least 24 hours and then resumes the normally scheduled operation. Countdown timer switches shall not be used to comply with the automatic time switch control requirements; and
  2. Install at least one controlled receptacle within 6 feet from each uncontrolled receptacle or install a multiple-receptacle outlet with at least one controlled and one uncontrolled receptacle. Where receptacles are installed in modular furniture in open office areas, at least one controlled receptacle shall be installed at each workstation; and
  3. Provide a permanent marking for controlled receptacles or circuits to differentiate them from uncontrolled receptacles or circuits; and
  4. For hotel and motel guest rooms, install controlled receptacles for at least one-half of the 120-volt receptacles in each guestroom. Electric circuits serving controlled receptacles in guestrooms shall have captive card key controls, occupant sensing controls, or automatic controls so the power is switched OFF no longer than 20 minutes after the guestroom has been vacated.

Exception 1 to Section 130.5(d): Receptacles that are only for the following purposes: i. Receptacles specifically for refrigerators and water dispensers in kitchen area. ii. Receptacles located a minimum of six feet above the floor that are specifically for clocks. iii. Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in copy

rooms.

iv. Receptacles on circuits rated more than 20 amperes. v. Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.

Exception 2 to Section 130.5(d): Receptacles in healthcare facilities.

(e) Demand responsive controls and equipment. See Section 110.12 for requirements for demand responsive controls and equipment, including demand responsive controls for controlled receptacles.

Note: Definitions of terms and phrases in Section 130.5 are determined as specified in Section 100.1(b). Terms and phrases not found in Section 100.1(b) shall be defined as specified in Title 24, Part 3, Article 100 of the California Electrical Code.

Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

104 2025 CALIFORNIA ENERGY CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Energy Code (Title 24, Part 6)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.