Chapter 15 — CONSTRUCTION SAFEGUARDS
Section 1509 — STANDPIPES
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[F] 1509.1 Where required. In buildings required to have standpipes by Section 905.3.1 of the California Building Code, not less than one standpipe shall be provided for use during construction. Such standpipes shall be installed prior to construction exceeding 40 feet (12 192 mm) in height above the lowest level of fire department vehicle access. Such standpipes shall be provided with fire department hose connections at locations adjacent to stairways, complying with Section 1508.1. As construction progresses, such standpipes shall be extended to within one floor of the highest point of construction having secured decking or flooring.
[F] 1509.2 Buildings being demolished. Where a building or portion of a building is being demolished and a standpipe is existing within such a building, such standpipe shall be maintained in an operable condition so as to be available for use by the fire department. Such standpipe shall be demolished with the building but shall not be demolished more than one floor below the floor being demolished.
[F] 1509.3 Detailed requirements. Standpipes shall be installed in accordance with the provisions of Chapter 9 of the California Building Code .
Exception: Standpipes shall be either temporary or permanent in nature, and with or without a water supply, provided that such standpipes conform to the requirements of Section 905 of the California Building Code as to capacity, outlets and materials.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
-
▸ Chapter 15 — CONSTRUCTION SAFEGUARDS
Overview- Section 1501 — GENERAL
- Section 1502 — OWNER’S RESPONSIBILITY FOR FIRE PROTECTION
- Section 1503 — SANITARY
- Section 1504 — PROTECTION OF PEDESTRIANS
- Section 1505 — PROTECTION OF ADJOINING PROPERTY
- Section 1506 — TEMPORARY USE OF STREETS, ALLEYS AND PUBLIC PRO…
- Section 1507 — FIRE EXTINGUISHERS
- Section 1508 — MEANS OF EGRESS
- Section 1509 — STANDPIPES
- Section 1510 — AUTOMATIC SPRINKLER SYSTEM
- Section 1511 — ACCESSIBILITY
- Section 1512 — WATER SUPPLY FOR FIRE PROTECTION
- Chapter 16 — REFERENCED STANDARDS
- Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
- Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…