Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
BB104 Fire Area — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § BB104 · Effective January 1, 2026 · Official source: Building Standards Commission
BB104.1 General.¶
The fire area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projec- tions of the roof of a building, except as modified in Section 4.
BB104.2 Area separation.¶
Portions of buildings which are separated by one or more 4-hour area separation walls constructed in accor- dance with the building code, without openings and provided with a 30-inch (762 mm) parapet, are allowed to be considered as separate fire areas.
BB104.3 Type I and Type IB construction.¶
The fire area of buildings constructed of Type I and Type IB construction shall be the area of the three largest successive floors.
Continue researching
Related topics
State and federal sources. Edit the document title or filters, then run your search.
Get a plain-English answer with a citation back to this text.