Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
Section 1116 — EXISTING GROUP L AND GROUP H-8 OCCUPANCIES [SFM]
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1116.1 Repairs general. ¶
Additions, alterations or repairs may be made to any building or structure without requiring the existing build- ing or structure to comply with all the requirements of this code section, provided the addition, alteration or repair conforms to the requirements of this section.
1116.2 Unsafe condition. ¶
Additions, repairs or alterations shall not be made to an existing building or structure that will cause the exist- ing building or structure to be in violation of any of the provisions of this code, nor shall such additions or alterations cause the existing building or structure to become unsafe, or to be in violation of any of the provisions of this code. An unsafe condition shall be deemed to have been created if an addition or alteration will cause the existing building or structure to become structurally unsafe or overloaded; will not provide adequate egress in compliance with the provisions of this code or will obstruct existing exits; will create a fire hazard; will reduce required fire resistance or will otherwise create conditions dangerous to human life.
1116.3 Changes in use or occupancy. ¶
Any buildings that have alternations or additions, which involves a change in use or occupancy, shall not exceed the height, number of stories and area permitted for new buildings.
1116.4 Buildings not in compliance with code. ¶
Additions or alterations shall not be made to an existing building or structure when such existing building or structure is not in full compliance with the provisions of this code except when such addition or alteration will result in the existing building or structure being no more hazardous, based on life safety, fire safety and sanitation, than before such additions or alterations are undertaken.
1116.5 Maintenance of structural and fire resistive integrity. ¶
Alterations or repairs to an existing building or structure that are nonstructural and do not adversely affect any structural member of any part of the building or structure having required fire resistance may be made with the same materials of which the building or structure is constructed. The installation or replacement of glass shall be as required for new installations.
11-28 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
1116.6 Continuation of existing use. ¶
Buildings in existence at the time of the adoption of this code may have their existing use or occu- pancy continued if such use or occupancy was legal at the time of the adoption of this code, provided such continued use is not dangerous to life.
1116.7 Maximum allowable quantities. ¶
Existing Group H-8 laboratory suites approved prior to January 1, 2008 shall not exceed the maximum allowable quantities listed in Tables 1116.7(1) and 1116.7(2).
TABLE 1116.7(1)–EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS
PRESENTING A PHYSICAL HAZARD BASIC QUANTITIES PER LABORATORY SUITE1
When two units are given, values within parentheses are in cubic feet (cu. ft) or pounds (lb)
| CONDITION | CONDITION | STORAGE | STORAGE | STORAGE | USE CLOSED SYSTEMS | USE CLOSED SYSTEMS | USE CLOSED SYSTEMS | USE OPEN SYSTEMS | USE OPEN SYSTEMS | USE OPEN SYSTEMS |
|---|---|---|---|---|---|---|---|---|---|---|
| MATERIAL | CLASS | Solid Pounds (cu. ft) |
Liquid Gallons (lb) |
Gas (cu. ft) |
Solid Pounds (cu. ft) |
Liquid Gallons (lb) |
Gas (cu. ft) |
Solid Pounds (cu. ft) |
Liquid Gallons (lb) |
Gas (cu. ft) |
| 1.1 Combustible liquid | II | — | 1202 | — | — | 120 | — | — | 30 | — |
| 1.1 Combustible liquid | III-A | — | 3302 | — | — | 330 | — | — | 80 | — |
| 1.1 Combustible liquid | III-B | — | 13,2002 | — | — | 13,200 | — | — | 3,300 | — |
| 1.2 Combustible dust lbs./1000 cu. ft. | 1 | — | — | 1 | — | — | 1 | — | — | |
| 1.3 Combustible fiber _ (loose) (baled)_ |
(100) (1,000) |
— — |
— — |
(100) (1,000) |
— — |
— — |
(20) (200) |
— — |
— — |
|
| 1.4 Cryogenic, flammable or oxidizing | — | 45 | — | — | 45 | — | — | 10 | — | |
| 2.1 Explosives | 12 | (1)2 | — | 1/4 | (1/4) | — | 1/4 | (1/4) | — | |
| 3.1 Flammable solid | 1252 | — | — | 25 | — | — | 25 | — | — | |
| 3.2 Flammable gas _ (gaseous) (liquefied)_ |
— — |
— 152 |
7502 — |
— — |
— 152 |
7502 — |
— — |
— — |
— — |
|
| 3.3 Flammable liquid combination I-A, I-B, I-C |
I-A | — | 302 | — | — | 30 | — | — | 10 | — |
| 3.3 Flammable liquid combination I-A, I-B, I-C |
I-B | — | 602 | — | — | 60 | — | — | 15 | — |
| 3.3 Flammable liquid combination I-A, I-B, I-C |
I-C | — | 902 | — | — | 90 | — | — | 20 | — |
| 3.3 Flammable liquid combination I-A, I-B, I-C |
— | 1202 | — | — | 120 | — | — | 30 | — | |
| 4.1 Organic peroxide, unclassified detonatable |
12 | (1)2 | — | 1/4 | (1/4) | — | 1/4 | (1/4) | — | |
| 4.2 Organic peroxide | I | 52 | (5)2 | — | (1) | (1) | — | 1 | 1 | — |
| 4.2 Organic peroxide | II | 502 | (50)2 | — | 50 | (50) | — | 10 | (10) | — |
| 4.2 Organic peroxide | III | 1252 | (125)2 | — | 125 | (125) | — | 25 | (25) | — |
| 4.2 Organic peroxide | IV | 500 | (500) | — | 500 | (500) | — | 100 | (100) | — |
| 4.2 Organic peroxide | V | N.L. | N.L. | — | N.L. | N.L. | — | N.L. | N.L. | — |
| 4.3 Oxidizer | 4 | 12 | (1)2 | — | 1/4 2 |
(1/4) | — | 1/4 | (1/4) | — |
| 4.3 Oxidizer | 3 | 102 | (10)2 | — | 2 | (2) | — | 2 | (2) | — |
| 4.3 Oxidizer | 2 | 2502 | (250)2 | — | 50 | (250) | — | 50 | (50) | — |
| 4.3 Oxidizer | 1 | 1,0002 | (1,000)2 | — | 1,000 | (1,000) | — | 200 | (200) | — |
| 4.4 Oxidizer, Gas _ (gaseous) (liquefied)_ |
— — |
— 152 |
1,5002 — |
— — |
— 152 |
1,5002 — |
— — |
— — |
— — |
|
| 5.1 Pyrophoric | 42 | (4)2 | 502 | 1 | (1) | 102 | 0 | 0 | 0 | |
| 6.1 Unstable (reactive) | 4 | 12 | (1)2 | 102 | 1/4 | (1/4) | 22 | 1/4 | (1/4) | 0 |
| 6.1 Unstable (reactive) | 3 | 52 | (5)2 | 502 | 1 | (1) | 102 | 1 | (1) | 0 |
| 6.1 Unstable (reactive) | 2 | 502 | (50)2 | 2502 | 50 | (50) | 2502 | 10 | (10) | 0 |
| 6.1 Unstable (reactive) | 1 | 1252 | 1252 | 7502 | 125 | (125) | 7502 | 25 | (25) | 0 |
| 7.1 Water (reactive) | 3 | 52 | (5)2 | — | 5 | (5) | — | 1 | (1) | — |
| 7.1 Water (reactive) | 2 | 502 | (50)2 | — | 50 | (50) | — | 10 | (10) | — |
| 7.1 Water (reactive) | 1 | 1252 | (125)2 | — | 125 | (125)2 | — | 25 | (25) | — |
1. A laboratory suite is a space up to 10,000 square feet (929 m2) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt amounts of
hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in this table shall apply.
Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh through 10th floor and below the third
basement floor level quantity shall be reduced to 50 percent of this table.
2. Quantities may be increased 100 percent when stored in approved exhausted gas cabinets, exhausted enclosures or fume hoods.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
TABLE 1116.7(2)–EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS
PRESENTING A HEALTH HAZARD MAXIMUM QUANTITIES PER LABORATORY SUITE1
When two units are given, values within parentheses are in pounds (lbs.)
| MATERIAL | STORAGE | STORAGE | STORAGE | USE CLOSED SYSTEMS | USE CLOSED SYSTEMS | USE CLOSED SYSTEMS | USE OPEN SYSTEMS | USE OPEN SYSTEMS |
|---|---|---|---|---|---|---|---|---|
| MATERIAL | Solid lb | Liquid Gallons (lb) |
Gas (cu. ft) |
Solid lb | Liquid Gallons (lb) |
Gas (cu. ft) |
Solid lb | Liquid Gallons (lb) |
| 1. Corrosives | 5,000 | 500 | 6502 | 5,000 | 500 | 650 | 1,000 | 100 |
| _2a. Highly toxics2 _ | 40 | 10 | 65 | 5 | 1 | 65 | 2 | 1/4 |
| 2b. Toxics | 500 | 50 | 6502 | 500 | 50 | 650 | 5 | 1/2 |
| 3. Irritants | 5,000 | 500 | 650 | 5,000 | 500 | 650 | 1,000 | 100 |
| 4. Sensitizers | 5,000 | 500 | 650 | 5,000 | 500 | 650 | 1,000 | 100 |
| 5. Other health hazards | 5,000 | 500 | 650 | 5,000 | 500 | 650 | 1,000 | 100 |
1. A laboratory suite is a space up to 10,000 square feet (929 m2) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt amounts of
hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in this table shall apply.
Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh through 10th floor and below the third
basement floor level quantity shall be reduced to 50 percent of this table.
2. Permitted only when stored or used in approved exhausted gas cabinets, exhausted enclosures or fume hoods. Quantities of high toxics in use in open systems need not be
reduced above the third floor or below the first basement floor level. Individual container size shall be limited to 2 pounds (0.91 kg) for solids and1/4 gallon (0.95 L) for liquids.
11-30 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE
CHAPTER 12 – ENERGY SYSTEMS
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | BSC | BSC- CG |
T-24 | T-19* | 1 | 2 | 1/AC | AC | SS | 1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt Entire Chapter | |||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | ||||||||||||||||||||||
| Adopt only those sections that are listed below |
|||||||||||||||||||||||
| [California Code of Regulations, Title 19, Division 1] |
|||||||||||||||||||||||
| Chapter / Section | |||||||||||||||||||||||
| 1203.1.2 | X | ||||||||||||||||||||||
| 1203.1.3.1 | X | ||||||||||||||||||||||
| 1203.1.5.1 | X | ||||||||||||||||||||||
| 1203.2.11 | X | ||||||||||||||||||||||
| 1205.2.4 | X | ||||||||||||||||||||||
| 1205.3.4 | X | ||||||||||||||||||||||
| 1207.11.3 | X | ||||||||||||||||||||||
| 1207.11.4 | X | ||||||||||||||||||||||
| Table 1207.11.4 | X |
- The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-2 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
-
▸ Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
Overview- Section 1101 — GENERAL
- Section 1102 — DEFINITIONS
- Section 1103 — FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
- Section 1104 — MEANS OF EGRESS FOR EXISTING BUILDINGS
- Section 1105 — CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2
- Section 1106 — REQUIREMENTS FOR OUTDOOR OPERATIONS
- Section 1107 — ENERGY STORAGE SYSTEMS
- Section 1108 — GROUP A PUBLIC ADDRESS SYSTEM
- Section 1113 — EXISTING GROUP R-1 AND GROUP R-2 OCCUPANCIES [S…
- Section 1114 — EXISTING HIGH-RISE BUILDINGS [SFM]
- Section 1115 — EXISTING GROUP I OCCUPANCIES [SFM]
- Section 1116 — EXISTING GROUP L AND GROUP H-8 OCCUPANCIES [SFM]
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…