Skip to content

Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS

Section 5003 — GENERAL REQUIREMENTS

2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

5003.1 Scope.

The storage, use and handling of all hazardous materials shall be in accordance with this section.

5003.1.1 Maximum allowable quantity per control area. The maximum allowable quantity per control area shall be as specified in Tables 5003.1.1(1) through 5003.1.1(4).

Exception: Medical gases utilized for patient care within patient areas of a Group I-2 occupancy when the applicable require- ments of NFPA 99 Chapter 5 and Chapter 11 have been met.

For retail and wholesale storage and display in Group M occupancies and Group S storage, see Section 5003.11.

TABLE 5003.1.1(1)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, c, i, l, m, o

MATERIAL CLASS GROUP WHEN
THE MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
STORAGEb STORAGEb STORAGEb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb USE-OPEN SYSTEMSb
MATERIAL CLASS GROUP WHEN
THE MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
(cubic feet
at NTP)
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
(cubic
feet at
NTP)
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)
Combustible
dust
NA H-2 See Note p NA NA See Note p NA NA See Note
p
NA
Combustible
fibersp
Loose H-3 (100) NA NA (100) NA NA (20) NA
Combustible
fibersp
Baled Baled (1,000) (1,000) (1,000) (1,000) (1,000) (1,000) (200) (200)
Combustible
liquid
II H-2 or H-3 NA 120d, e NA NA 120d NA NA 30d
Combustible
liquid
IIIA H-2 or H-3 H-2 or H-3 330d, e 330d, e 330d, e 330d 330d 330d 80d
Combustible
liquid
IIIB NA NA 13,200e, f 13,200e, f 13,200e, f 13,200f 13,200f 13,200f 3,300f
Cryogenic
Flammable
NA H-2 NA 45d NA NA 45d NA NA 10d
Cryogenic
Inert
NA NA NA NA NL NA NA NL NA NA
Cryogenic
Oxidizing
NA H-3 NA 45d NA NA 45d NA NA 10d
Explosives Division
1.1
H-1 1e, g (1)e, g NA 0.25g (0.25)g NA 0.25g (0.25)g
Explosives Division
1.2
H-1 1e, g (1)e, g (1)e, g 0.25g (0.25)g (0.25)g 0.25g (0.25)g
Explosives Division
1.3
H-1 or H-2 5e, g (5)e, g (5)e, g 1g (1)g (1)g 1g (1)g
Explosives Division
1.4
H-3 50e, g (50)e, g (50)e, g 50g (50)g (50)g NA NA
Explosives Division
1.4G
H-3 125e, k NA NA NA NA NA NA NA
Explosives Division
1.5
H-1 1e, g (1)e, g (1)e, g 0.25g (0.25)g (0.25)g 0.25g (0.25)g
Explosives Division
1.6
H-1 1e, g NA NA NA NA NA NA NA
Flammable
gas
Gaseous H-2 NA NA NA NA NA NA
Flammable
gas
1A and 1B
(High BV)q
1A and 1B
(High BV)q
1A and 1B
(High BV)q
1A and 1B
(High BV)q
1,000d, e 1,000d, e 1,000d, e 1,000d, e 1,000d, e 1,000d, e
Flammable
gas
1B
(Low BV)q
1B
(Low BV)q
1B
(Low BV)q
1B
(Low BV)q
162,500d, e 162,500d, e 162,500d, e 162,500d, e 162,500d, e 162,500d, e
Flammable
gas
Liquefied Liquefied Liquefied NA NA NA NA NA
Flammable
gas
1A and 1B
(High BV)q
1A and 1B
(High BV)q
1A and 1B
(High BV)q
(150)d, e (150)d, e (150)d, e (150)d, e (150)d, e (150)d, e (150)d, e
Flammable
gas
1B
(Low BV)q
1B
(Low BV)q
1B
(Low BV)q
(10,000)d, e (10,000)d, e (10,000)d, e (10,000)d, e (10,000)d, e (10,000)d, e (10,000)d, e

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.1.1(1)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, c, i, l, m, o—continued

MATERIAL CLASS GROUP WHEN
THE MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
STORAGEb STORAGEb STORAGEb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb USE-OPEN SYSTEMSb
MATERIAL CLASS GROUP WHEN
THE MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
(cubic feet
at NTP)
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
(cubic
feet at
NTP)
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)
Flammable
liquidn
IA
IB and IC
H-2
or
H-3
NA 30d, e NA NA 30d NA NA 10d
Flammable
liquidn
IA
IB and IC
H-2
or
H-3
NA 120d, e 120d, e 120d, e 120d 120d 120d 30d
Flammable
liquid,
combination
(IA, IB, IC)n
NA H-2
or
H-3
NA 120d, e, h NA NA 120d, h NA NA 30d, h
Flammable
solid
NA H-3 125d, e NA NA 125d NA NA 25d NA
Inert gas Gaseous NA NA NA NL NA NA NL NA NA
Inert gas Liquefied NA NA NA NL NA NA NL NA NA
Organic
peroxide
UD H-1 1e, g (1)e, g NA 0.25g (0.25)g NA 0.25g (0.25)g
Organic
peroxide
I H-2 5d, e (5)d, e (5)d, e 1d (1)d (1)d 1d (1)d
Organic
peroxide
II H-3 50d, e (50)d, e (50)d, e 50d (50)d (50)d 10d (10)d
Organic
peroxide
III H-3 125d, e (125)d, e (125)d, e 125d (125)d (125)d 25d (25)d
Organic
peroxide
IV NA NL NL NL NL NL NL NL NL
Organic
peroxide
V NA NL NL NL NL NL NL NL NL
Oxidizer 4 H-1 1g (1)e, g NA 0.25g (0.25)g NA 0.25g (0.25)g
Oxidizer 3j H-2 or H-3 10d, e (10)d, e (10)d, e 2d (2)d (2)d 2d (2)d
Oxidizer 2 H-3 250d, e (250)d, e (250)d, e 250d (250)d (250)d 50d (50)d
Oxidizer 1 NA 4,000e, f (4,000)e, f (4,000)e, f 4,000f (4,000)f (4,000)f 1,000f (1,000)f
Oxidizing gas Gaseous H-3 NA NA 1,500d,e NA NA 1,500d, e NA NA
Oxidizing gas Liquefied Liquefied Liquefied (150)d, e NA NA (150)d, e NA NA NA
Pyrophoric NA H-2 4e, g (4)e, g 50e, g 1g (1)g 10e, g 0 0
Unstable
(reactive)
4 H-1 1e, g (1)e, g 10e, g 0.25g (0.25)g 2e, g 0.25g (0.25)g
Unstable
(reactive)
3 H-1 or H-2 5d, e (5)d, e 50d, e 1d (1)d 10d, e 1d (1)d
Unstable
(reactive)
2 H-3 50d, e (50)d, e 750d, e 50d (50)d 750d, e 10d (10)d
Unstable
(reactive)
1 NA NL NL NL NL NL NL NL NL
Water
reactive
3 H-2 5d, e (5)d, e NA 5d (5)d NA 1d (1)d
Water
reactive
2 H-3 50d, e (50)d, e (50)d, e 50d (50)d (50)d 10d (10)d
Water
reactive
1 NA NL NL NL NL NL NL NL NL

For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
NA = Not Applicable, NL = Not Limited, UD = Unclassified Detonable.
a. For use of control areas, see Section 5003.8.3.
b. The aggregate quantity in use and storage shall not exceed the maximum allowance quantity for storage, including applicable increases.
c. For hazardous materials in Group B higher education laboratory occupancies, see Section 428 of the_California Building Code_ and Chapter 38.
d._ [SFM]__ In other than Group L occupancies, maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in_
accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. For Group L occupancies, refer to California Building
Code Table 453.7.2.1 for approved cabinets.
e. Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets, day boxes, gas cabinets, gas rooms, exhausted enclosures or in
listed safety cans in accordance with Section 5003.9.10. Where Note d applies, the increase for both notes shall be applied accumulatively.
f. Quantities shall not be limited in a building equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system.
h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids.
i. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
j. A maximum quantity of 220 pounds of solid or 22 gallons of liquid Class 3 oxidizers is allowed where such materials are necessary for maintenance purposes, operation or
sanitation of equipment where the storage containers and the manner of storage are approved.
k. Net weight of pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of
the fireworks including packaging shall be used.
l. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
m.For oxidizers, unstable (reactive) materials and water-reactive materials stored or displayed in Group M occupancies or stored in Group S occupancies, see Section 5003.11.
n. For flammable and combustible liquid storage in Group M occupancy wholesale and retail sales uses, see Section 5704.3.6.
o. Quantities in this table shall be modified in accordance with Table 5003.1.1(5).
p. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accor-
dance with Section 104.2.2.
q. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.

50-8 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.1.1(2)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A HEALTH HAZARDa, c, h, i, j

MATERIAL STORAGEb STORAGEb STORAGEb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb USE-OPEN SYSTEMSb
MATERIAL Solid
poundsd, e, f
Liquid
gallons
(pounds)d, e, f
Gas cubic
feet at NTP
(pounds)d
Solid
poundsd
Liquid
gallons
(pounds)d
Gas cubic
feet at NTP
(pounds)d
Solid
poundsd
Liquid
gallons
(pounds)d
Corrosives 5,000 500 Gaseous 810e
Liquefied (150)
5,000 500 Gaseous 810e
Liquefied (150)
1,000 100
Highly toxics 10 (10) Gaseous 20g
Liquefied (4)g
10 (10) Gaseous 20g
Liquefied (4)g
3 (3)
Toxics 500 (500) Gaseous 810e
Liquefied (150)e
500 (500) Gaseous 810e
Liquefied (150)e
125 (125)

For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see Section 5003.8.3.
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
c. In retail and wholesale sales occupancies, the quantities of medicines, foodstuff or consumer products and cosmetics, containing not more than 50 percent by volume of
water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers
not exceeding 1.3 gallons.
d._ [SFM]_In other than Group L occupancies, maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. For Group L occupancies, refer to California Building
Code Table 453.7.2.1 for approved cabinets.
e. Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets, gas cabinets or exhausted enclosures. Where Note d applies, the
increase for both notes shall be applied accumulatively.
f. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 5003.11, see Table 5003.11.1.
g. Allowed only where stored in approved exhausted gas cabinets or exhausted enclosures.
h. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
j. Quantities in this table shall be modified in accordance with Table 5003.1.1(5).

TABLE 5003.1.1(3)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD IN AN OUTDOOR CONTROL AREAa, b, c, d

MATERIAL CLASS STORAGEb STORAGEb STORAGEb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb USE-OPEN SYSTEMSb
MATERIAL CLASS Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Gas cubic
feet at
NTP
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Gas cubic
feet at
NTP
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Flammable
gas
Gaseous Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Flammable
gas
1A and 1B
(High BV)e
1A and 1B
(High BV)e
1A and 1B
(High BV)e
3,000 3,000 3,000 1,500 1,500 1,500
Flammable
gas
1B (Low
BV)e
1B (Low
BV)e
1B (Low
BV)e
195,000 195,000 195,000 97,500 97,500 97,500
Flammable
gas
Liquefied Liquefied Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Flammable
gas
1A and 1B
(High BV)e
1A and 1B
(High BV)e
(300) (300) (300) (150) (150) (150) (150)
Flammable
gas
1B (Low
BV)e
1B (Low
BV)e
(20,000) (20,000) (20,000) (10,000) (10,000) (10,000) (10,000)
Flammable
solid
Not
Applicable
500 Not
Applicable
Not
Applicable
250 Not
Applicable
Not
Applicable
50 Not
Applicable
Inert Gas
Cryogenic
inert
Gaseous
Liquefied
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not Limited
Not Limited
Not Limited
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not Limited
Not Limited
Not Limited
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Organic
peroxide
Unclassified
Detonable
1 (1) Not
Applicable
0.25 (0.25) Not
Applicable
0.25 (0.25)
Organic
peroxide
I
II
III
IV
V
20
200
500
Not Limited
Not Limited
(20)
(200)
(500)
Not Limited
Not Limited
Not
Applicable
10
100
250
Not Limited
Not Limited
(10)
(100)
(250)
Not Limited
Not Limited
Not
Applicable
2
20
50
Not
Limited
Not
Limited
(2)
(20)
(50)
Not
Limited
Not
Limited

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.1.1(3)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD IN AN OUTDOOR CONTROL AREAa, b, c, d—continued

MATERIAL CLASS STORAGEb STORAGEb STORAGEb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb USE-OPEN SYSTEMSb
MATERIAL CLASS Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Gas cubic
feet at
NTP
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Gas cubic
feet at
NTP
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)d
Oxidizer 4
3
2
1
2
40
1,000
Not Limited
(2)
(40)
(1,000)
Not Limited
Not
Applicable
1
20
500
Not Limited
(1)
(20)
(500)
Not Limited
Not
Applicable
0.25
4
100
Not
Limited
(0.25)
(4)
(100)
Not
Limited
Oxidizing
gas
Gaseous
Liquefied
Not
Applicable
Not
Applicable
(600)
6,000
Not
Applicable
Not
Applicable
Not
Applicable
(300)
1,500
Not
Applicable
Not
Applicable
Not
Applicable
Pyrophoric
materials
Not
Applicable
8 (8) 100 4 (4) 10 0 0
Unstable
(reactive)
4
3
2
1
2
20
200
Not Limited
(2)
(20)
(200)
Not Limited
20
200
1,000
Not Limited
1
10
100
Not Limited
(1)
(10)
(100)
Not Limited
2
10
250
Not Limited
0.25
1
10
Not
Limited
(0.25)
(1)
(10)
Not
Limited
Water
reactive
3
2
1
20
200
Not Limited
(20)
(200)
Not Limited
Not
Applicable
10
100
Not Limited
(10)
(100)
Not Limited
Not
Applicable
1
10
Not
Limited
(1)
(10)
Not
Limited

TABLE 5003.1.1(3)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD IN AN OUTDOOR CONTROL AREAa, b, c, d—continued

For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.

e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.|For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.|For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.|For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.|For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Quantities in parentheses indicate quantity units in parentheses at the head of each column.
e. “High BV” Category 1B flammable gas has a burning velocity greater than 3.9 in/s (10 cm/s). “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s or less.|

TABLE 5003.1.1(4)—MAXIMUM ALLOWABLE QUANTITY PER
CONTROL AREA OF HAZARDOUS MATERIALS POSING A HEALTH HAZARD IN AN OUTDOOR CONTROL AREAa, b, c, f

MATERIAL STORAGE STORAGE STORAGE USE-CLOSED SYSTEMS USE-CLOSED SYSTEMS USE-CLOSED SYSTEMS USE-OPEN SYSTEMS USE-OPEN SYSTEMS
MATERIAL Solid
pounds
Liquid
gallons
(pounds)
Gas cubic
feet at NTP
(pounds)
Solid
pounds
Liquid
gallons
(pounds)
Gas cubic
feet at NTP
(pounds)
Solid
pounds
Liquid
gallons
(pounds)
Corrosives 20,000 2,000 Gaseous
1,620
Liquefied
(300)
10,000 1,000 Gaseous 810
Liquefied
(150)
1,000 100
Highly toxics 20 (20) Gaseous 40d
Liquefied
(8)d
10 (10) Gaseous 20d
Liquefied
(4)d
3 (3)
Toxics 1,000 (l,000)e Gaseous
1,620
Liquefied
(300)
500 50e Gaseous 810
Liquefied
(150)
125 (125)e

For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 pound per square inch absolute = 6.895 kPa,°C = (°F – 32)/1.8.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the maximum allowable quantity for storage, including applicable increases.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the
same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area where such storage is in accordance with
Section 5003.11.
d. Allowed only where used in approved exhausted gas cabinets, exhausted enclosures or under fume hoods.
e. The maximum allowable quantity per control area for toxic liquids with vapor pressures in excess of 1 psia at 77°F shall be the maximum allowable quantity per control area
listed for highly toxic liquids.
f. Quantities in parentheses indicate quantity units in parentheses at the head of each column.

50-10 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.1.1(5)—HAZARDOUS MATERIALS EXEMPTIONSa

MATERIAL CLASSIFICATION OCCUPANCY OR
APPLICATION
EXEMPTION
Combustible fiber Baled cotton Densely packed baled cotton shall not be classified as combustible fiber, provided that
the bales comply with the packing requirements of ISO 8115.
Corrosive Building materials The quantity of commonly used building materials that are classified as corrosive
materials is not limited.
Corrosive Personal and
household products
The quantity of personal and household products that are classified as corrosive materials
is not limited in retail displays, provided that the products are in original packaging.
Corrosive Retail and wholesale
sales occupancies
The quantity of medicines, foodstuffs or consumer products, and cosmetics containing
not more than 50 percent by volume of water-miscible liquids, with the remainder of
the solutions not being flammable, is not limited.
To qualify for this allowance, such materials shall be packaged in individual containers
not exceeding 1.3 gallons.
Explosives Groups B, F, M and S Storage of special industrial explosive devices is not limited.
Explosives Groups M and R-3 Storage of black powder, smokeless propellant, and small arms primers is not limited.
Flammable and combustible
liquids and gases
Aerosols Buildings and structures occupied for the storage of aerosol products, aerosol cooking
spray products, or plastic aerosol 3 products shall be classified as Group S-1.
Flammable and combustible
liquids and gases
Alcoholic beverages The quantity of alcoholic beverages in liquor stores and distributors without bulk
storage is not limited.
Flammable and combustible
liquids and gases
Alcoholic beverages The quantity of alcoholic beverages in distilling or brewing of beverages is not limited.
Flammable and combustible
liquids and gases
Alcoholic beverages The storage quantity of beer, distilled spirits and wines in barrels and casks is not limited.
Flammable and combustible
liquids and gases
Alcoholic beverages The quantity of alcoholic beverages in retail and wholesale sales occupancies is not
limited. To qualify for this allowance, beverages shall be packaged in individual
containers not exceeding 1.3 gallons.
Flammable and combustible
liquids and gases
Cleaning establish-
ments with
combustible liquid
solvents
The quantity of combustible liquid solvents used in closed systems and having a flash
point at or above 140°F is not limited. To qualify for this allowance, equipment shall be
listed by an approved testing agency and the occupancy shall be separated from all
other areas of the building by 1-hour fire barriers or 1-hour horizontal assemblies, or
both, constructed in accordance with the_California Building Code_.
Flammable and combustible
liquids and gases
Cleaning establish-
ments with
combustible liquid
solvents
The quantity of combustible liquid solvents having a flash point at or above 200°F is
not limited.
Flammable and combustible
liquids and gases
Closed piping
systems
The quantity of flammable and combustible liquids and gases utilized for the
operation of machinery or equipment is not limited.
Flammable and combustible
liquids and gases
Flammable finishing
operations using
flammable and
combustible liquids
Buildings and structures occupied for the application of flammable finishes shall
comply with Section 416.
Flammable and combustible
liquids and gases
Fuel The quantity of liquid or gaseous fuel in fuel tanks on vehicles or motorized equipment
is not limited.
Flammable and combustible
liquids and gases
Fuel The quantity of gaseous fuels in piping systems and fixed appliances regulated by the
International Fuel Gas Code is not limited.
Flammable and combustible
liquids and gases
Fuel The quantity of liquid fuels in piping systems and fixed appliances regulated by the
California Mechanical Code is not limited.
Flammable and combustible
liquids and gases
Fuel oil The quantity of fuel oil storage complying with Section 605.4.2 is not limited.
Flammable and combustible
liquids and gases
Hand sanitizer The quantity of alcohol-based hand rubs (ABHR) classified as Class I or II liquids in
dispensers installed in accordance with Sections 5705.5 and 5705.5.1 is not limited.
The location of the ABHR shall be provided in the construction documents.
Flammable and combustible
liquids and gases
Retail and wholesale
sales occupancies
with flammable and
combustible liquids
The quantity of medicines, foodstuffs or consumer products, and cosmetics containing
not more than 50 percent by volume of water-miscible liquids, with the remainder of
the solutions not being flammable, is not limited.
To qualify for this allowance, such materials shall be packaged in individual containers
not exceeding 1.3 gallons.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.1.1(5)—HAZARDOUS MATERIALS EXEMPTIONSa—continued

MATERIAL CLASSIFICATION OCCUPANCY OR
APPLICATION
EXEMPTION
Highly toxic and toxic
materials
Retail and wholesale
sales occupancies
The quantity of medicines, foodstuffs or consumer products, and cosmetics containing
not more than 50 percent by volume of water-miscible liquids, with the remainder of
the solutions not being flammable, is not limited.
To qualify for this allowance, such materials shall be packaged in individual containers
not exceeding 1.3 gallons.
Any Agricultural materials The quantity of agricultural materials stored or utilized for agricultural purposes on the
premises is not limited.
Any Energy storage The quantity of hazardous materials in stationary storage battery systems is not
limited.
Any Energy storage The quantity of hazardous materials in stationary fuel cell power systems is not limited.
Any Energy storage The quantity of hazardous materials in capacitor energy storage systems is not limited.
Any Refrigeration systems The quantity of refrigerants in refrigeration systems is not limited.
For SI: 1 gallon = 3.785 L, °C = (°F – 32)/1.8.
a. Exempted materials and conditions listed in this table are required to comply with provisions of this code that are not based on exceeding maximum allowable quantities in
Section 5003.

5003.1.2 Conversion. Where quantities are indicated in pounds and where the weight per gallon of the liquid is not provided to the fire code official, a conversion factor of 10 pounds per gallon (1.2 kg/L) shall be used.

5003.1.3 Quantities not exceeding the maximum allowable quantity per control area. The storage, use and handling of hazardous materials in quantities not exceeding the maximum allowable quantity per control area indicated in Tables 5003.1.1(1) through 5003.1.1(4) shall be in accordance with Sections 5001 and 5003.

5003.1.4 Quantities exceeding the maximum allowable quantity per control area. The storage and use of hazardous materials in quantities exceeding the maximum allowable quantity per control area indicated in Tables 5003.1.1(1) through 5003.1.1(4) shall be in accordance with this chapter.

5003.2 Systems, equipment and processes.

Systems, equipment and processes utilized for storage, dispensing, use or handling of hazardous materials shall be in accordance with Sections 5003.2.1 through 5003.2.9.

5003.2.1 Design and construction of containers, cylinders and tanks. Containers, cylinders and tanks shall be designed and constructed in accordance with approved standards. Containers, cylinders, tanks and other means used for containment of hazardous materials shall be of an approved type. Pressure vessels not meeting DOTn requirements for transportation shall comply with the ASME Boiler and Pressure Vessel Code.

5003.2.2 Piping, tubing, valves and fittings. Piping, tubing, valves, and fittings conveying hazardous materials shall be designed and installed in accordance with ASME B31.1 or other approved standards, and shall be in accordance with Sections 5003.2.2.1 and 5003.2.2.2.

5003.2.2.1 Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following:

  1. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials that are compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress and exposure to which they are subject.
  2. Piping and tubing shall be identified in accordance with ASME A13.1 to indicate the material conveyed.
  3. Manual valves or automatic remotely activated fail-safe emergency shutoff valves shall be installed on supply piping and tubing and provided with ready access at the following locations: 3.1. The point of use. 3.2. The tank, cylinder or bulk source.
  4. Manual emergency shutoff valves and controls for remotely activated emergency shutoff valves shall be clearly visible, provided with ready access and identified in an approved manner.
  5. Backflow prevention or check valves shall be provided where the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials.

Exceptions:

  1. Piping for inlet connections designed to prevent backflow.
  2. Piping for pressure relief devices.

5003.2.2.2 Additional regulations for supply piping for health-hazard materials. Supply piping and tubing for gases and liquids having a health-hazard ranking of 3 or 4 in accordance with NFPA 704 shall be in accordance with ASME B31.3 and the following:

  1. Piping and tubing utilized for the transmission of highly toxic, toxic or highly volatile corrosive liquids and gases shall have welded, threaded or flanged connections throughout except for connections located within a ventilated enclo

50-12 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

sure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid. 2. Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H occupancies.

Exception: Piping and tubing within the space defined by the walls of corridors and the floor or roof above or in concealed spaces above other occupancies where installed in accordance with Section 415.11.7.4 of the California Building Code for Group H-5 occupancies.

5003.2.3 Equipment, machinery and alarms. Equipment, machinery and required detection and alarm systems associated with the use, storage or handling of hazardous materials shall be listed or approved.

5003.2.4 Installation of tanks. Installation of tanks shall be in accordance with Sections 5003.2.4.1 through 5003.2.4.2.1.

5003.2.4.1 Underground tanks. Underground tanks used for the storage of liquid hazardous materials shall be provided with secondary containment. In lieu of providing secondary containment for an underground tank, an above-ground tank in an underground vault complying with Section 5704.2.8 shall be permitted.

5003.2.4.2 Above-ground tanks. Above-ground stationary tanks used for the storage of hazardous materials shall be located and protected in accordance with the requirements for outdoor storage of the particular material involved.

Exception: Above-ground tanks that are installed in vaults complying with Section 5303.16 or 5704.2.8 shall not be required to comply with location and protection requirements for outdoor storage.

5003.2.4.2.1 Marking. Above-ground stationary tanks shall be marked as required by Section 5003.5.

5003.2.5 Empty containers and tanks. Empty containers and tanks previously used for the storage of hazardous materials shall be free from residual material and vapor as defined by DOTn, the Resource Conservation and Recovery Act (RCRA) or other regulating authority or maintained as specified for the storage of hazardous material.

5003.2.6 Maintenance. In addition to the requirements of Section 5003.2.3, equipment, machinery and required detection and alarm systems associated with hazardous materials shall be maintained in an operable condition. Defective containers, cylinders and tanks shall be removed from service, repaired or disposed of in an approved manner. Defective equipment or machinery shall be removed from service and repaired or replaced. Required detection and alarm systems shall be replaced or repaired where defective.

5003.2.6.1 Tanks out of service for 90 days. Stationary tanks not used for a period of 90 days shall be properly safeguarded or removed in an approved manner. Such tanks shall have the fill line, gauge opening and pump connection secured against tampering. Vent lines shall be properly maintained.

5003.2.6.1.1 Return to service. Tanks that are to be placed back in service shall be tested in an approved manner.

5003.2.6.2 Defective containers and tanks. Defective containers and tanks shall be removed from service, repaired in accordance with approved standards or disposed of in an approved manner.

5003.2.7 Liquid-level limit control. Atmospheric tanks having a capacity greater than 500 gallons (1893 L) and that contain hazardous material liquids shall be equipped with a liquid-level limit control or other approved means to prevent overfilling of the tank.

5003.2.8 Seismic protection. Machinery and equipment utilizing hazardous materials shall be braced and anchored in accordance with the seismic design requirements of the California Building Code for the seismic design category in which the machinery or equipment is classified.

5003.2.9 Testing. The equipment, devices and systems listed in Section 5003.2.9.1 shall be tested at the time of installation and at one of the intervals listed in Section 5003.2.9.2. Records of the tests conducted or maintenance performed shall be maintained in accordance with the provisions of Section 110.3.

Exceptions:

  1. Periodic testing shall not be required where approved written documentation is provided stating that testing will damage the equipment, device or system and the equipment, device or system is maintained as specified by the manufacturer.

  2. Periodic testing shall not be required for equipment, devices and systems that fail in a fail-safe manner.

  3. Periodic testing shall not be required for equipment, devices and systems that self-diagnose and report trouble. Records of the self-diagnosis and trouble reporting shall be made available to the fire code official.

  4. Periodic testing shall not be required if system activation occurs during the required test cycle for the components activated during the test cycle.

  5. Approved maintenance in accordance with Section 5003.2.6 that is performed not less than annually or in accordance with an approved schedule shall be allowed to meet the testing requirements set forth in Sections 5003.2.9.1 and 5003.2.9.2.

5003.2.9.1 Equipment, devices and systems requiring testing. The following equipment, systems and devices shall be tested in accordance with Sections 5003.2.9 and 5003.2.9.2.

  1. Gas detection systems, alarms and automatic emergency shutoff valves required by Section 6004.2.2.10 for highly toxic and toxic gases.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

  1. Limit control systems for liquid level, temperature and pressure required by Sections 5003.2.7, 5004.8 and 5005.1.4.
  2. Emergency alarm systems and supervision required by Sections 5004.9 and 5005.4.4.
  3. Monitoring and supervisory systems required by Sections 5004.10 and 5005.1.6.
  4. Manually activated shutdown controls required by Section 6403.1.1.1 for compressed gas systems conveying pyrophoric gases.

ntrol systems for liquid level, temperature and pressure required by Sections 5003.2.7, 5004.8 and 5005.1.4. 3. Emergency alarm systems and supervision required by Sections 5004.9 and 5005.4.4. 4. Monitoring and supervisory systems required by Sections 5004.10 and 5005.1.6. 5. Manually activated shutdown controls required by Section 6403.1.1.1 for compressed gas systems conveying pyrophoric gases.

5003.2.9.2 Testing frequency. The equipment, systems and devices listed in Section 5003.2.9.1 shall be tested at one of the following frequencies:

  1. Not less than annually.
  2. In accordance with the approved manufacturer’s requirements.
  3. In accordance with approved recognized industry standards.
  4. In accordance with an approved schedule.

5003.3 Release of hazardous materials.

Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere.

Exceptions:

  1. The release or emission of hazardous materials is allowed where in compliance with federal, state or local governmental agencies, regulations or permits.
  2. The release of pesticides is allowed where used in accordance with registered label directions.
  3. The release of fertilizer and soil amendments is allowed where used in accordance with manufacturer’s specifications.

5003.3.1 Unauthorized discharges. In the event hazardous materials are released in quantities reportable under state, federal or local regulations, the fire code official shall be notified and the following procedures required in accordance with Sections 5003.3.1.1 through 5003.3.1.4.

5003.3.1.1 Records. Records of the unauthorized discharge of hazardous materials by the permittee shall be maintained.

5003.3.1.2 Preparation. Provisions shall be made for controlling and mitigating unauthorized discharges.

5003.3.1.3 Control. Where an unauthorized discharge caused by primary container failure is discovered, the involved primary container shall be repaired or removed from service.

5003.3.1.4 Responsibility for cleanup. The person, firm or corporation responsible for an unauthorized discharge shall institute and complete all actions necessary to remedy the effects of such unauthorized discharge, whether sudden or gradual, without cost to the jurisdiction. Where deemed necessary by the fire code official, cleanup can be initiated by the fire department or by an authorized individual or firm. Costs associated with such cleanup shall be borne by the owner, operator or other person responsible for the unauthorized discharge.

5003.4 Safety Data Sheets.

Safety Data Sheets (SDS) shall be readily available on the premises for hazardous materials regulated by this chapter. Where a hazardous substance is developed in a laboratory, available information shall be documented.

Exception: Designated hazardous waste.

5003.5 Hazard identification signs.

Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official.

5003.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: “COMPRESSED GAS.”

5003.6 Signs.

Signs and markings required by Sections 5003.5 and 5003.5.1 shall not be obscured or removed, shall be in English as a primary language or in symbols allowed by this code, shall be durable, and the size, color and lettering shall be approved.

5003.7 Sources of ignition.

Sources of ignition shall comply with Sections 5003.7.1 through 5003.7.3.

5003.7.1 Smoking. Smoking shall be prohibited and “No Smoking” signs provided as follows:

  1. In rooms or areas where hazardous materials are stored or dispensed or used in open systems in amounts requiring a permit in accordance with Section 5001.5.
  2. Within 25 feet (7620 mm) of outdoor storage, dispensing or open use areas.
  3. Facilities or areas within facilities that have been designated as totally “no smoking” shall have “No Smoking” signs placed at all entrances to the facility or area. Designated areas within such facilities where smoking is permitted either permanently or temporarily, shall be identified with signs designating that smoking is permitted in these areas only.
  4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or used.

Signs required by this section shall be in English as a primary language or in symbols allowed by this code and shall comply with Section 310.

5003.7.2 Open flames. Open flames and high-temperature devices shall not be used in a manner that creates a hazardous condition and shall be listed for use with the hazardous materials stored or used.

5003.7.3 Industrial trucks. Powered industrial trucks used in areas designated as hazardous (classified) locations shall be in accordance with Section 309.2.

50-14 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

5003.7.4 Respiratory therapy. In Group I-2 and ambulatory care facilities, within areas with respiratory therapy services, sources of ignition shall be regulated in accordance with NFPA 99.

5003.8 Construction requirements.

Buildings, control areas, enclosures and cabinets for hazardous materials shall be in accordance with Sections 5003.8.1 through 5003.8.7.4.

5003.8.1 Buildings. Buildings, or portions thereof, in which hazardous materials are stored, handled or used shall be constructed in accordance with the California Building Code .

5003.8.2 Required detached buildings. Group H occupancies containing quantities of hazardous materials in excess of those set forth in Table 5003.8.2 shall be in detached buildings.

TABLE 5003.8.2—DETACHED BUILDING REQUIRED
A DETACHED BUILDING IS REQUIRED WHERE THE QUANTITY OF MATERIAL EXCEEDS THAT LISTED HEREIN
Material Class Solids and liquids
(tons)a, b
Gases
(cubic feet)a, b
Explosives Division 1.1
Division 1.2
Division 1.3
Division 1.4e
Division 1.4c, e
Division 1.5
Division 1.6
Maximum Allowable Quantity
Maximum Allowable Quantity
Maximum Allowable Quantity
Maximum Allowable Quantity
1
Maximum Allowable Quantity
Maximum Allowable Quantity
Not Applicable
Oxidizers Class 4 Maximum Allowable Quantity Maximum Allowable Quantity
Unstable (reactives) detonable Class 3 or 4 Maximum Allowable Quantity Maximum Allowable Quantity
Oxidizer, liquids and solids Class 3
Class 2
1,200
2,000
Not Applicable
Organic peroxides Detonable
Class I
Class II
Class III
Maximum Allowable Quantity
Maximum Allowable Quantity
25
50
Not Applicable
Unstable (reactives) nondetonable Class 3
Class 2
1
25
2,000
10,000
Water reactives Class 3
Class 2
1
25
Not Applicable
Pyrophoric gasesd Not Applicable Not Applicable 2,000

For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.02832 m3, 1 ton = 2000 lb = 907.2 kg.
a. For materials that are detonable, the distance to other buildings or lot lines shall be in accordance with Section 415.6 of the_California Building Code_ or Chapter 56 based on
the trinitrotoluene (TNT) equivalence of the material, whichever is greater.
b. “Maximum Allowable Quantity” means the maximum allowable quantity per control area set forth in Table 5003.1.1(1).
c. Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and
Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing the net explosive
weight of individual articles does not exceed 1 pound.
d. Detached buildings are not required for gases in gas rooms that support H-5 fabrication facilities where the gas room is separated from other areas by a fire barrier with a fire-
resistance rating of not less than 2 hours and the gas is located in a gas cabinet that is internally sprinklered, equipped with continuous leak detection, automatic shutdown,
and is not manifolded upstream of pressure controls. The gas supply is limited to cylinders that do not exceed 125 pounds water capacity in accordance with DOTn 49 CFR
173.192 for Hazard Zone A toxic gases.
e. Does not apply to consumer fireworks, Division 1.4G.

5003.8.3 Control areas. Control areas shall comply with Sections 5003.8.3.1 through 5003.8.3.5.3.

5003.8.3.1 Construction requirements. Control areas shall be separated from each other by fire barriers constructed in accordance with Section 707 of the California Building Code or horizontal assemblies constructed in accordance with Section 711 of the California Building Code, or both.

5003.8.3.2 Percentage of maximum allowable quantities. The percentage of maximum allowable quantities of hazardous materials per control area allowed at each story within a building shall be in accordance with Table 5003.8.3.2.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.8.3.2—DESIGN AND NUMBER OF CONTROL AREAS

STORY STORY PERCENTAGE OF THE
MAXIMUM ALLOWABLE
QUANTITY PER CONTROL AREAa
NUMBER OF CONTROL
AREAS PER STORY
FIRE-RESISTANCE
RATING FOR FIRE
BARRIERS IN HOURSb
Above grade plane Higher than 9
7–9
6
5
4
3
2
1
5
5
12.5
12.5
12.5
50
75
100
1
2
2
2
2
2
3
4
2
2
2
2
2
1
1
1
Below grade plane 1
2
Lower than 2
75
50
Not Allowed
3
2
Not Allowed
1
1
Not Allowed
a. Percentages shall be of the maximum allowable quantity per control area shown in Tables 5003.1.1(1) and 5003.1.1(2), with all increases allowed in the footnotes to those tables.
b. Separation shall include fire barriers and horizontal assemblies as necessary to provide separation from other portions of the building.

5003.8.3.3 Number. The maximum number of control areas per floor within a building shall be in accordance with Table 5003.8.3.2. For the purposes of determining the number of control areas within a building, each portion of a building separated by one or more fire walls complying with Section 706 of the California Building Code shall be considered a separate building.

5003.8.3.4 Fire-resistance-rating requirements. The required fire-resistance rating for fire barriers shall be in accordance with Table 5003.8.3.2. The floor assembly of the control area and the construction supporting the floor of the control area shall have a fire-resistance rating of not less than 2 hours.

Exception: The floor assembly of the control area and the construction supporting the floor of the control area is allowed to be 1hour fire-resistance rated in buildings of Types IIA, IIIA, IV and VA construction, provided that both of the following conditions exist:

  1. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. The building is three stories or less above grade plane.

5003.8.3.5 Hazardous materials in Group M display and storage areas and in Group S storage areas. Hazardous materials located in Group M and Group S occupancies shall be in accordance with Sections 5003.8.3.5.1 through 5003.8.3.5.4.

5003.8.3.5.1 Nonflammable solids and nonflammable and noncombustible liquids. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed within a single control area of a Group M display and storage area or a Group S storage area is allowed to exceed the maximum allowable quantities per control area specified in Tables 5003.1.1(1) and 5003.1.1(2) without classifying the building or use as a Group H occupancy, provided that the materials are displayed and stored in accordance with Section 5003.11.

5003.8.3.5.2 Flammable and combustible liquids. In Group M occupancy wholesale and retail sales uses, indoor storage of flammable and combustible liquids shall not exceed the maximum allowable quantities per control area as indicated in Table 5704.3.4.1, provided that the materials are displayed and stored in accordance with Chapter 57.

5003.8.3.5.3 Aerosols. The maximum quantity of aerosol products in Group M occupancy retail display areas, storage areas adjacent to retail display areas and retail storage areas shall be in accordance with Chapter 51.

5003.8.3.5.4 Flammable gas. The aggregate quantity of Category 1B flammable gas having a burning velocity of 3.9 in/s (10 cm/s) or less stored and displayed within a single control area of a Group M occupancy, in an outdoor control area or stored in a single control area of a Group S occupancy is allowed to exceed the maximum allowable quantities per control area specified in Table 5003.1.1(1) without classifying the building or use as a Group H occupancy, provided that the materials are stored and displayed in accordance with Section 5003.11.2.

5003.8.4 Gas rooms. Where a gas room is used to increase the maximum allowable quantity per control area or provided to comply with the provisions of Chapter 60, the gas room shall be in accordance with Sections 5003.8.4.1 and 5003.8.4.2.

5003.8.4.1 Construction. Gas rooms shall be protected with an automatic sprinkler system. Gas rooms shall be separated from the remainder of the building in accordance with the requirements of the California Building Code based on the occupancy group into which it has been classified.

5003.8.4.2 Ventilation system. The ventilation system for gas rooms shall be designed to operate at a negative pressure in relation to the surrounding area. Highly toxic and toxic gases shall also comply with Section 6004.2.2.6. The ventilation system shall be installed in accordance with the California Mechanical Code .

5003.8.5 Exhausted enclosures. Where an exhausted enclosure is used to increase maximum allowable quantity per control area or where the location of hazardous materials in exhausted enclosures is provided to comply with the provisions of Chapter 60, the exhausted enclosure shall be in accordance with Sections 5003.8.5.1 through 5003.8.5.3.

5003.8.5.1 Construction. Exhausted enclosures shall be of noncombustible construction.

50-16 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

5003.8.5.2 Ventilation. Exhausted enclosures shall be provided with an exhaust ventilation system. The ventilation system for exhausted enclosures shall be designed to operate at a negative pressure in relation to the surrounding area. Ventilation systems used for highly toxic and toxic gases shall also comply with Items 1, 2 and 3 of Section 6004.1.3. The ventilation system shall be installed in accordance with the California Mechanical Code .

5003.8.5.3 Fire-extinguishing system. Exhausted enclosures where flammable materials are used shall be protected by an approved automatic fire-extinguishing system in accordance with Chapter 9.

5003.8.6 Gas cabinets. Where a gas cabinet is used to increase the maximum allowable quantity per control area or where the location of compressed gases in gas cabinets is provided to comply with the provisions of Chapter 60, the gas cabinet shall be in accordance with Sections 5003.8.6.1 through 5003.8.6.3.

5003.8.6.1 Construction. Gas cabinets shall be constructed with the following:

  1. Not less than 0.097-inch (2.5 mm) (No. 12 gage) steel.
  2. Self-closing limited access ports or noncombustible windows to give access to equipment controls.
  3. Self-closing doors.
  4. Interiors treated, coated or constructed of materials that are compatible with the hazardous materials stored. Such treatment, coating or construction shall include the entire interior of the cabinet.

5003.8.6.2 Ventilation. Gas cabinets shall be provided with an exhaust ventilation system. The ventilation system for gas cabinets shall be designed to operate at a negative pressure in relation to the surrounding area. Ventilation systems used for highly toxic and toxic gases shall also comply with Items 1, 2 and 3 of Section 6004.1.2. The ventilation system shall be installed in accordance with the California Mechanical Code .

5003.8.6.3 Maximum number of cylinders per gas cabinet. The number of cylinders contained in a single gas cabinet shall not exceed three.

5003.8.7 Hazardous materials storage cabinets. Where storage cabinets are used to increase maximum allowable quantity per control area or to comply with this chapter, such cabinets shall be in accordance with Sections 5003.8.7.1 through 5003.8.7.4.

5003.8.7.1 Construction. The interior of cabinets shall be treated, coated or constructed of materials that are nonreactive with the hazardous material stored. Such treatment, coating or construction shall include the entire interior of the cabinet. Cabinets shall either be listed in accordance with UL 1275 as suitable for the intended storage or constructed in accordance with the following:

  1. Cabinets shall be of steel having a thickness of not less than 0.0478 inch (1.2 mm) (No. 18 gage). The cabinet, including the door, shall be double walled with a 1 [1] / 2 -inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting.
  2. The bottoms of cabinets utilized for the storage of liquids shall be liquid tight to a minimum height of 2 inches (51 mm).

5003.8.7.2 Doors. Doors shall be well fitted, self-closing and equipped with a self-latching device.

5003.8.7.3 Electrical. Electrical equipment and devices within cabinets used for the storage of hazardous gases or liquids shall be in accordance with the California Electrical Code.

5003.8.7.4 Warning markings. Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background to read:

HAZARDOUS—KEEP FIRE AWAY

5003.9 General safety precautions.

General precautions for the safe storage, handling or care of hazardous materials shall be in accordance with Sections 5003.9.1 through 5003.9.10.

5003.9.1 Personnel training and written procedures. Persons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of fire, leak or spill.

5003.9.1.1 Fire department liaison. Responsible persons shall be designated and trained to be liaison personnel to the fire department. These persons shall aid the fire department in preplanning emergency responses and identifying the locations where hazardous materials are located, and shall have access to Safety Data Sheets and be knowledgeable in the site’s emergency response procedures.

5003.9.2 Security. Storage, dispensing, use and handling areas shall be secured against unauthorized entry and safeguarded in a manner approved by the fire code official.

5003.9.3 Protection from vehicles. Guard posts or other approved means shall be provided to protect storage tanks and connected piping, valves and fittings; dispensing areas; and use areas subject to vehicular damage in accordance with Section 312.

5003.9.4 Electrical wiring and equipment. Electrical wiring and equipment shall be installed and maintained in accordance with the California Electrical Code.

5003.9.5 Static accumulation. Where processes or conditions exist where a flammable mixture could be ignited by static electricity, means shall be provided to prevent the accumulation of a static charge.

5003.9.6 Protection from light. Materials that are sensitive to light shall be stored in containers designed to protect them from such exposure.

5003.9.7 Shock padding. Materials that are shock sensitive shall be padded, suspended or otherwise protected against accidental dislodgement and dislodgement during seismic activity.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

5003.9.8 Separation of incompatible materials. Incompatible materials in storage and storage of materials that are incompatible with materials in use shall be separated where the stored materials are in containers having a capacity of more than 5 pounds (2 kg), 0.5 gallon (2 L) or any amount of compressed gases. Separation shall be accomplished by:

  1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm).

  2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material.

  3. Storing liquid and solid materials in hazardous material storage cabinets.

  4. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with Sections 5003.8.5 and 5003.8.6.

Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure.

5003.9.9 Shelf storage. Shelving shall be of substantial construction, and shall be braced and anchored in accordance with the seismic design requirements of the California Building Code for the seismic design category in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard where used for the storage of individual containers.

Shelf storage of hazardous materials shall be maintained in an orderly manner.

Exceptions:

  1. Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use.
  2. Storage of hazardous materials in amounts not requiring a permit in accordance with Section 5001.5.

5003.9.10 Safety cans. Safety cans shall be listed in accordance with UL 30 where used to increase the maximum allowable quantities per control area of flammable or combustible liquids in accordance with Table 5003.1.1(1). Safety cans listed in accordance with UL 1313 are allowed for flammable and combustible liquids where not used to increase the maximum allowable quantities per control area and for other hazardous material liquids in accordance with the listing.

5003.10 Handling and transportation.

In addition to the requirements of Section 5003.2, the handling and transportation of hazardous materials in corridors or enclosures for stairways and ramps shall be in accordance with Sections 5003.10.1 through 5003.10.3.6.

5003.10.1 Valve protection. Hazardous material gas containers, cylinders and tanks in transit shall have their protective caps in place. Containers, cylinders and tanks of highly toxic or toxic compressed gases shall have their valve outlets capped or plugged with an approved closure device in accordance with Chapter 53.

5003.10.2 Carts and trucks required. Liquids in containers exceeding 5.28 gallons (20 L) in an elevator, a corridor or enclosure for a stairway or ramp shall be transported on a cart or truck. Containers of hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 and transported within an elevator, corridors or interior exit stairways and ramps, shall be on a cart or truck. Where carts and trucks are required for transporting hazardous materials, they shall be in accordance with Section 5003.10.3. Exceptions 1 through 4 shall not apply where elevators are utilized.

Exceptions:

  1. Two hazardous material liquid containers that are hand carried in acceptable safety carriers.
  2. Not more than four drums not exceeding 55 gallons (208 L) each that are transported by suitable drum trucks.
  3. Containers and cylinders of compressed gases that are transported by approved hand trucks, and containers and cylinders not exceeding 25 pounds (11 kg) that are hand carried.
  4. Solid hazardous materials not exceeding 100 pounds (45 kg) that are transported by approved hand trucks, and a single container not exceeding 50 pounds (23 kg) that is hand carried.

5003.10.2.1 On the 11th story and above. On the 11th story and above of any occupancy, all vertical handling and transporta- tion of hazardous materials in the building shall be in approved carts.

5003.10.2.2 Transportation of hazardous materials on the 11th story and above. The handling and transportation of hazard- ous materials on the 11th story and above shall be limited to 5 percent of the maximum allowable quantities of Tables 5003.1(1) and (2). Quantities are permitted to be increased by 100 percent in buildings with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Materials where footnote g applies shall not be increased.

5003.10.3 Carts and trucks. Carts and trucks required by Section 5003.10.2 to be used to transport hazardous materials shall be in accordance with Sections 5003.10.3.1 through 5003.10.3.6.

5003.10.3.1 Design. Carts and trucks used to transport hazardous materials shall be designed to provide a stable base for the commodities to be transported and shall have a means of restraining containers to prevent accidental dislodgement. Compressed gas cylinders placed on carts and trucks shall be individually restrained.

5003.10.3.2 Speed-control devices. Carts and trucks shall be provided with a device that will enable the operator to control safely movement by providing stops or speed-reduction devices.

5003.10.3.3 Construction. Construction materials for hazardous material carts or trucks shall be compatible with the material transported. The cart or truck shall be of substantial construction.

5003.10.3.4 Spill control. Carts and trucks transporting liquids shall be capable of containing a spill from the largest single container transported.

5003.10.3.5 Attendance. Carts and trucks used to transport materials shall not obstruct or be left unattended within any part of a means of egress.

50-18 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

5003.10.3.6 Incompatible materials. Incompatible materials shall not be transported on the same cart or truck.

5003.10.4 Elevators utilized to transport hazardous materials.

5003.10.4.1 When transporting hazardous materials, elevators shall have no other passengers other than the individual(s) handling the chemical transport cart.

5003.10.4.1.1 When transporting cryogenic or liquefied compressed gases, there shall be no occupants in the elevator.

5003.10.4.2 Hazardous materials liquid containers shall have a maximum capacity of 20 liters (5.28 gal).

5003.10.4.3 Toxic and highly-toxic gases shall be limited to a container of a maximum water capacity of 1 pound.

5003.10.4.4 When transporting cryogenic or liquefied compressed gases, means shall be provided to prevent the elevator from being summoned to other floors.

5003.10.5 Elevators or conveyance systems utilized to transport hazardous materials in excess of the quantities listed in Section 5003.10.4 shall comply with Sections 5003.10.5.1 through 5003.10.5.6.

5003.10.5.1 Elevators or conveyance hoist-way enclosures shall be located in a shaft constructed in accordance with Section 713 of the California Building Code.

5003.10.5.2 Elevators shall have no passengers other than the individual handling the chemical transport and shall comply with the requirements of Section 5003.10.4.

5003.10.5.2.1 When transporting cryogenic or liquefied compressed gases, there shall be no occupants in the elevator.

5003.10.5.3 Spill containment shall be provided for all transported liquids.

5003.10.5.4 Ventilation shall be provided in the elevator shaft in accordance with Section 5004.3.1.

5003.10.5.5 Signage shall be provided on all floors adjacent to each elevator call station to indicate the elevator is designated for hazardous materials transportation.

5003.10.5.6 Use of an elevator or conveyance system described in this section shall be restricted to personnel that have been properly trained.

5003.10.5.7 Means shall be provided to prevent the elevator from being summoned to other floors.

5003.10.6 Posted sequence of operation. A documented sequence of operation shall be submitted to the authority having jurisdic- tion for review and approval prior to the transportation of hazardous materials in elevators or conveyance systems described in Section 5003.10.5.

5003.10.6.1 The approved sequence of operations shall be posted in the elevator car or conveyance system.

5003.10.6.2 The approved sequence of operation shall be maintained and tested upon the request of the authority having jurisdiction.

5003.11 Maximum allowable quantity for Group M storage and display and Group S storage.

The aggregate quantity of hazardous materials stored and displayed within a single control area of a Group M occupancy, or an outdoor control area, or stored in a single control area of a Group S occupancy, is allowed to exceed the maximum allowable quantity per control area indicated in Section 5003.1 where in accordance with Sections 5003.11.1 and 5003.11.2.

5003.11.1 Nonflammable solid and nonflammable or noncombustible liquid hazardous materials. The aggregate amount of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single control area of a Group M occupancy, in an outdoor control area or stored in a single control area of a Group S occupancy shall not exceed the amounts set forth in Table 5003.11.1.

TABLE 5003.11.1—MAXIMUM ALLOWABLE QUANTITY PER INDOOR AND OUTDOOR CONTROL AREA IN
GROUP M AND S OCCUPANCIES—NONFLAMMABLE SOLIDS, NONFLAMMABLE AND NONCOMBUSTIBLE LIQUIDSd, e, f

CONDITION CONDITION MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA
Materiala Class Solids (pounds) Liquids (gallons)
A. Health-Hazard Materials—Nonflammable and Noncombustible Solids and Liquids
1. Corrosivesb, c Not Applicable 9,750 975
2. Highly toxics Not Applicable 20b, c 2b, c
3. Toxicsb, c Not Applicable 1,000k 100
B. Physical-Hazard Materials—Nonflammable and Noncombustible Solids and Liquids
1. Oxidizersb, c 4 Not Allowed Not Allowed
1. Oxidizersb, c 3 1,350g 135
1. Oxidizersb, c 2 2,250h 225
1. Oxidizersb, c 1 18,000i, j 1,800i, j
2. Unstable (reactives)b, c 4 Not Allowed Not Allowed
2. Unstable (reactives)b, c 3 550 55
2. Unstable (reactives)b, c 2 1,150 115
2. Unstable (reactives)b, c 1 Not Limited Not Limited

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

TABLE 5003.11.1—MAXIMUM ALLOWABLE QUANTITY PER INDOOR AND OUTDOOR CONTROL AREA IN
GROUP M AND S OCCUPANCIES—NONFLAMMABLE SOLIDS, NONFLAMMABLE AND NONCOMBUSTIBLE LIQUIDSd, e, f—continued

CONDITION CONDITION MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA
Materiala Class Solids (pounds) Liquids (gallons)
3. Water reactives 3b, c 550 55
3. Water reactives 2b, c 1,150 115
3. Water reactives 1 Not Limited Not Limited

For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
a. Hazard categories are as specified in Section 5001.2.2.
b. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section
903.3.1.1. Where Note c applies, the increase for both notes shall be applied accumulatively.
c. Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets in accordance with Section 5003.8. Where Note b applies, the
increase for both notes shall be applied accumulatively.
d. See Table 5003.8.3.2 for design and number of control areas.
e. Maximum allowable quantities for other hazardous material categories shall be in accordance with Section 5003.1.
f. Maximum allowable quantities shall be increased 100 percent in outdoor control areas.
g. Maximum allowable quantities shall be increased to 2,250 pounds where individual packages are in the original sealed containers from the manufacturer or packager and do
not exceed 10 pounds each.
h. Maximum allowable quantities shall be increased to 4,500 pounds where individual packages are in the original sealed containers from the manufacturer or packager and do
not exceed 10 pounds each.
i. Quantities are unlimited where protected by an automatic sprinkler system.
j. Quantities are unlimited in an outdoor control area.
k. Maximum allowable quantity of consumer products shall be increased to 10,000 pounds where individual packages are in the original sealed containers from the manufac-
turer and the toxic classification is exclusively based on the LC50 threshold and no other hazardous materials classifications apply.

5003.11.1.1 Storage and display. Storage and display shall be in accordance with Sections 5003.11.1.1.1 through 5003.11.1.1.11. 5003.11.1.1.1 Density. Storage and display of solids shall not exceed 200 pounds per square foot (976 kg/m [2] ) of floor area actually occupied by solid merchandise. Storage and display of liquids shall not exceed 20 gallons per square foot (0.50 L/m [2] ) of floor area actually occupied by liquid merchandise.

5003.11.1.1.2 Storage and display height. Display height shall not exceed 6 feet (1829 mm) above the finished floor in display areas of Group M occupancies. Storage height shall not exceed 8 feet (2438 mm) above the finished floor in storage areas of Group M and Group S occupancies.

5003.11.1.1.3 Container location. Individual containers less than 5 gallons (19 L) or less than 25 pounds (11 kg) shall be stored or displayed on pallets, racks or shelves.

5003.11.1.1.4 Racks and shelves. Racks and shelves used for storage or display shall be in accordance with Section 5003.9.9.

5003.11.1.1.5 Container type. Containers shall be approved for the intended use and identified as to their content.

5003.11.1.1.6 Container size. Individual containers shall not exceed 100 pounds (45 kg) for solids or 10 gallons (38 L) for liquids in storage and display areas.

5003.11.1.1.7 Incompatible materials. Incompatible materials shall be separated in accordance with Section 5003.9.8.

5003.11.1.1.8 Floors. Floors shall be in accordance with Section 5004.12.

5003.11.1.1.9 Aisles. Aisles 4 feet (1219 mm) in width shall be maintained on three sides of the storage or display area.

5003.11.1.1.10 Signs. Hazard identification signs shall be provided in accordance with Section 5003.5.

5003.11.1.1.11 Storage plan. A storage plan illustrating the intended storage arrangement, including the location and dimensions of aisles, and storage racks shall be provided.

5003.11.2 Category 1B flammable gas with low burning velocity. The aggregate quantity of Category 1B flammable gas having a burning velocity of 3.9 in/s (10 cm/s) or less stored and displayed within a single control area of a Group M occupancy, in an outdoor control area or stored in a single control area of a Group S occupancy shall not exceed the amounts set forth in Table 5003.11.2.

TABLE 5003.11.2—MAXIMUM ALLOWABLE QUANTITY OF LOW BURNING VELOCITY
CATEGORY 1B FLAMMABLE GAS IN GROUP M AND S OCCUPANCIES PER CONTROL AREAa

CATEGORY 1B
(Low BV)d
SPRINKLERED IN ACCORDANCE WITH NOTE B NONSPRINKLERED
Gaseous 39,000 ft3 195,000 ft3
Liquified 40,000 lbc 20,000 lb
For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.028 m3.
a. Control areas shall be separated from each other by not less than a 1-hour fire barrier.
b. The building shall be equipped throughout with an approved automatic sprinkler system with a minimum sprinkler design density of Ordinary Hazard Group 2 in the area
where flammable gases are stored or displayed.
c. Where storage areas exceed 50,000 square feet in area, the maximum allowable quantities area is allowed to be increased by 2 percent for each 1,000 square feet of area in excess
of 50,000 square feet, up to not more than 100 percent of the table amounts. Separation of control areas is not required. The aggregate amount shall not exceed 80,000 pounds.
d. “Low BV” Category 1B flammable gas has a burning velocity of 3.9 in/s (10 cm/s) or less.

50-20 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HAZARDOUS MATERIALS—GENERAL PROVISIONS

5003.11.2.1 Fire protection and storage arrangements. Fire protection and container storage arrangements for quantities of Category 1B flammable gases permitted by Table 5003.11.2 shall be in accordance with the all of the following:

  1. Storage of Category 1B flammable gases on shelves shall not exceed 6 feet (1829 mm) in height, and shelving shall be metal.
  2. Rack storage, pallet storage or piles of Category 1B flammable gas greater than 6 feet 6 inches (1981 mm) in height shall be provided with an automatic sprinkler system with a minimum design density of Extra Hazard Group 1.
  3. Combustible commodities shall not be stored above Category 1B flammable gases.
  4. Flammable liquids shall be separated from Category 1B flammable gases by a distance of not less than 20 feet (6096 mm). The separation is permitted to be reduced to 10 feet (3048 mm) where secondary containment or diking is provided to retain a flammable liquid spill at a distance of 10 feet (3048 mm) from the Category 1B flammable gas storage.

5003.12 Outdoor control areas.

Outdoor control areas for hazardous materials shall be in accordance with the following general requirements:

  1. Outdoor control areas shall be kept free from weeds, debris and common combustible materials not necessary to the storage. The area surrounding an outdoor control area shall be kept clear of such materials for not less than 15 feet (4572 mm).
  2. Outdoor control areas shall be located not closer than 20 feet (6096 mm) from a public street, public alley, public way or lot line that can be built on.

Exceptions:

  1. For solid and liquid hazardous materials, a 2-hour fire-resistance-rated wall without openings extending not less than 30 inches (762 mm) above and to the sides of the storage area shall be allowed in lieu of such distance.
  2. For compressed gas hazardous materials, unless otherwise specified, the minimum required distances shall not apply where fire barriers without openings or penetrations having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the storage and the exposure. The configuration of the fire barrier shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.
  3. Where a property exceeds 10,000 square feet (929 m [2] ), a group of two outdoor control areas is allowed where approved and where each control area is separated by a minimum distance of 50 feet (15 240 mm).
  4. Where a property exceeds 35,000 square feet (3252 m [2] ), additional groups of outdoor control areas are allowed where approved and where each group is separated by a minimum distance of 300 feet (91 440 mm).

5003.13 Outdoor rooftop storage, use and handling.

Storage, use and handling and use of hazardous materials on top of roofs or canopies shall be classified as rooftop storage or use and shall comply with Sections 5003.13.1 through 5003.13.5.

5003.13.1 Occupancy classification. Quantities of hazardous materials stored, used or handled on top of roofs or canopies shall be classified as rooftop storage or use and shall not be used to determine the occupancy classification of the building.

5003.13.2 Maximum allowable quantity per rooftop or canopy. The storage, use and handling of hazardous materials on top of a roof or canopy shall not exceed the maximum allowable quantity set forth in Tables 5003.1.1(1) and 5003.1.1(2). LP-gas storage and use shall be in accordance with Chapter 61.

Exceptions:

  1. Pollution control, exhaust treatment and dust collection equipment.
  2. Combustible liquids complying with Chapter 57 and NFPA 30.
  3. Hydrogen storage at motor fuel-dispensing facilities in accordance with Chapter 23.
  4. Hazardous materials in closed piping systems complying with this code.
  5. Hazardous materials on top of a normally unoccupied exterior equipment platform necessary for operation of mechanical systems or industrial process equipment.
  6. Hazardous materials necessary for rooftop swimming pool or hot tub treatment systems, limited to a maximum container size of 50 gallons (189 L) or 500 pounds (227 kg) of toxic or corrosive materials, and 200 pounds (91 kg) or 20 gallons (76 L) of oxidizers.
  7. Other situations where rooftop storage or use of hazardous materials is necessary for the operation of equipment serving the building and is approved.

5003.13.3 Story adjustment. In addition to the quantity limits in Section 5003.13.2, rooftop storage and use shall be limited to the percentage of maximum allowable quantity identified in Table 5003.8.3.2 based on the number of stories above grade of the building on which the roof is located.

5003.13.4 Other requirements. In addition to the quantity limits of this section, rooftop storage and use shall comply with other applicable requirements of this code for outdoor storage. This section applies to the exceptions identified in Section 5003.13.2.

5003.13.5 Weather protection. Weather protection provided for sheltering rooftop storage or use shall comply with Section 414.6.1 of the California Building Code, except that there is no distance required to the building on which it is located.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Fire Code (Title 24, Part 9)
2025 California Fire Code (Title 24, Part 9)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REQUIREMENTS
  4. Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
  5. Chapter 5 — FIRE SERVICE FEATURES
  6. Chapter 6 — BUILDING SERVICES AND SYSTEMS
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
  9. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  10. Chapter 10 — MEANS OF EGRESS
  11. Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
  12. Chapter 12 — ENERGY SYSTEMS
  13. Chapter 20 — AVIATION FACILITIES
  14. Chapter 21 — DRY CLEANING
  15. Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
  16. Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
  17. Chapter 24 — FLAMMABLE FINISHES
  18. Chapter 25 — FRUIT AND CROP RIPENING
  19. Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
  20. Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
  21. Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
  22. Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
  23. Chapter 30 — INDUSTRIAL OVENS
  24. Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
  25. Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
  26. Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
  27. Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
  28. Chapter 35 — WELDING AND OTHER HOT WORK
  29. Chapter 36 — MARINAS
  30. Chapter 37 — COMBUSTIBLE FIBERS
  31. Chapter 38 — RESERVED
  32. Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
  33. Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
  34. Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
  35. Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
  36. Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
  37. Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
  38. Chapter 51 — AEROSOLS
  39. Chapter 52 — RESERVED
  40. Chapter 53 — COMPRESSED GASES
  41. Chapter 54 — CORROSIVE MATERIALS
  42. Chapter 55 — CRYOGENIC FLUIDS
  43. Chapter 56 — EXPLOSIVES AND FIREWORKS
  44. Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
  45. Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
  46. Chapter 59 — FLAMMABLE SOLIDS
  47. Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
  48. Chapter 61 — LIQUEFIED PETROLEUM GASES
  49. Chapter 62 — ORGANIC PEROXIDES
  50. Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
  51. Chapter 64 — PYROPHORIC MATERIALS
  52. Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
  53. Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
  54. Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
  55. Chapter 80 — REFERENCED STANDARDS
  56. Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
  57. Appendix A — BOARD OF APPEALS
  58. Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  59. Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  60. Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  61. Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  62. Appendix D — FIRE APPARATUS ACCESS ROADS
  63. Appendix E — HAZARD CATEGORIES
  64. Appendix F — HAZARD RANKING
  65. Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
  66. Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
  67. Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
  68. Appendix J — BUILDING INFORMATION SIGN
  69. Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
  70. Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
  71. Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
  72. Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
  73. Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
  74. Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
  75. Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.