Palo Alto Municipal Code § 5.307 Cooling Tower Water Use

Palo Alto Municipal Code · 2026-10 edition · updated 2026-10-19 · Palo Alto

Cite as: Palo Alto Municipal Code § 5.307 · Text as of 2026-10-19

5.307.1. Cooling Tower Water Use in High-rise Residential or Non-Residential Buildings.

Cooling tower water use must meet the conditions as follows and as outlined in Palo Alto Municipal Code Section 16.08.100. Projects are required to perform a potable water analysis at the site to meet the maximum concentration of parameters noted in Table 5.307.1.

Table 5.307.1

Ca (as CaCO3) 600 ppm
Total alkalinity 500 ppm
SiO2 150 ppm
Cr 300 ppm
Conductivity 3300 Us/cm

Calculate maximum number of cycles that can be achieved with these levels of concentration shall be included in the plumbing design plans.

(Ord. 5678 § 2 (part), 2025)