Title 17 — BUILDING AND CONSTRUCTION›Chapter 80 — Referenced Standards
Petaluma Municipal Code § 6.2 Referenced Standards
Petaluma Municipal Code · 2026-09 edition · updated 2026-10-04 · Petaluma
Cite as: Petaluma Municipal Code § 6.2 · Text as of 2026-10-04
6.2.1 Where a pump is the source of pressure for the water supply for a Zre sprinkler…¶
portion of the domestic water system, the following shall be met:
(1) A test connection shall be provided downstream of the pump that creates a [ow of water equal to the
smallest sprinkler K-factor on the system.
(2) Pump motors using AC power shall be rated for 240 V and wired in accordance with the NEC (NFPA
70).
(3) Any disconnecting means for the pump shall be approved.
(4) The pump shall be located not less than 1 1/2 inch o] the [oor.
(5) Exterior pumps shall be installed in a well ventilated, weather protected area or shelter.
NFPA 13D 6.2.2
Revise Section 6.2.2 as follows:
6.2.2 Where a well, pump, tank or combination thereof is the source of supply for a Zre…¶
the conZguration for the system shall be one of the following:
(1) The water supply shall serve both domestic and Zre sprinkler systems.
(a) A test connection shall be provided downstream of the pump that creates a [ow of water equal
to the smallest sprinkler on the system. The connection shall return water to the tank.
(b) Any disconnecting means for the pump shall be approved.
(c) A method for reZlling the tank shall be piped to the tank.
(d) A method of seeing the water level in the tank shall be provided without having to open the tank.
(e) The pump shall be located not less than 1 1/2 inch o] the [oor.
(f) Exterior pumps shall be installed in a well ventilated, weather protected area or shelter.
(2) A stand-alone Zre sprinkler system is permitted if the following conditions are met:
(a) The pump shall be connected to a 220-volt circuit breaker shared with a common household
appliance (e.g., range, oven, dryer), or have a power failure alarm installed acceptable to the
Authority Having Jurisdiction that provides an audible and visual signal within the residence at an
approved location. The alarm and components shall be listed by an approved agency.
(b) The pump shall be a stainless steel 240-volt pump,
(c) A valve shall be provided to exercise the pump. The discharge of the exercise valve shall drain to
the tank, and
(d) A sign shall be provided stating: "Valve must be opened monthly for 5 minutes."
(e) A means for automatically reZlling the tank level, so that the tank capacity will meet the required
water supply duration in minutes, shall be provided.
(f) A test connection shall be provided downstream of the pump that creates a [ow of water equal
to the smallest sprinkler on the system. The connection shall return water to the tank.
(g) Any disconnecting means for the pump shall be approved.
(h) A method for reZlling the tank shall be piped to the tank.
(i) A method of seeing the water level in the tank shall be provided without having to open the tank.
(j) The pump shall be located not less than 1 1/2 inch o] the [oor.
(k) Exterior pumps shall be installed in a well ventilated, weather protected area or shelter.
Revise Section 7.6 to read as follows:
NFPA.13D.7.6 A local water [ow alarm shall be provided on all sprinkler systems on the exterior of the
home within 10 feet of the riser location, or as approved by the Fire Code O\cial.
NFPA.72-25—National Fire Alarm and Signaling Code
NFPA 72-7.5.6.1
Revise Section 7.5.6.1 as follows: