504.2.1. Breakable Window Marking.

Red reflectors shall be installed to indicate the location of existing breakable, tempered glass windows required under previous codes. Reflectors inside buildings shall be at least 1½ inches (381 mm) 1 in the least dimension. They shall be on the glass and within 6 inches (1524 mm) 1 of a lower corner of the pane. Reflectors outside buildings shall be at least 3 inches (762 mm) 1 in the least dimension. They shall be placed on the wall below the lowest window in each vertical line of windows containing tempered glass. A 24-inch (609 mm) clear space shall be maintained around the reflectors.