San Francisco Fire Code § 913.2 Fire-Protection Systems

San Francisco Fire Code · 2026-08 edition · updated 2026-10-23 · San Francisco

Cite as: San Francisco Fire Code § 913.2 · Text as of 2026-10-23

913.2.3. Integrity of the fire pump room.

The integrity of the fire pump room shall not be compromised. All non-fire pump related equipment, piping, drains, electrical equipment, and electrical services shall not be routed through or located within the fire pump room. Examples include, but are not limited to:

  1. Non-fire water system piping

  2. Domestic water equipment and piping

  3. Drain piping

  4. HVAC equipment, ducts, fans, and piping

  5. Boilers or furnaces, fuel equipment, and piping (unless feeding a diesel fire pump motor)

  6. Electrical equipment and service (e.g. Transformers and switchgear)

Exceptions & meaning →