913.2.3. Integrity of the fire pump room.¶
The integrity of the fire pump room shall not be compromised. All non-fire pump related equipment, piping, drains, electrical equipment, and electrical services shall not be routed through or located within the fire pump room. Examples include, but are not limited to:
Non-fire water system piping
Domestic water equipment and piping
Drain piping
HVAC equipment, ducts, fans, and piping
Boilers or furnaces, fuel equipment, and piping (unless feeding a diesel fire pump motor)
Electrical equipment and service (e.g. Transformers and switchgear)