Chapter 12 — INTERIOR ENVIRONMENT
Section 1208 — INTERIOR SPACE DIMENSIONS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1208.1 Minimum room widths. ¶
Habitable spaces, other than a kitchen, shall be not less than 7 feet (2134 mm) in any plan dimension. Kitchens shall have a clear passageway of not less than 3 feet (914 mm) between counter fronts and appliances or counter fronts and walls.
[HCD 1] For limited-density owner-built rural dwellings, there shall be no requirements for room dimensions, provided there is adequate light and ventilation and adequate means of egress.
1208.2 Minimum ceiling heights. ¶
Occupiable spaces, habitable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches (2286 mm) above the finished floor. Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms shall have a ceiling height of not less than 7 feet (2134 mm) above the finished floor.
Exceptions:
- In one- and two-family dwellings, beams or girders spaced not less than 4 feet (1219 mm) on center shall be permitted to project not more than 6 inches (152 mm) below the required ceiling height.
- If any room in a building has a sloped ceiling, the prescribed ceiling height for the room is required in one-half the area thereof. Any portion of the room measuring less than 5 feet (1524 mm) from the finished floor to the ceiling shall not be included in any computation of the minimum area thereof.
- The height of mezzanines and spaces below mezzanines shall be in accordance with Section 505.2.
12-8 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INTERIOR ENVIRONMENT
- Corridors contained within a dwelling unit or sleeping unit in a Group R occupancy shall have a ceiling height of not less than 7 feet (2134 mm) above the finished floor.
5. [OSHPD 1, 2, 3 & 5] Minimum ceiling heights shall comply with Section 1224.4.10. 6. [OSHPD 4] Minimum ceiling heights shall comply with Section 1227.8.
1208.2.1 Furred ceiling. Any room with a furred ceiling shall be required to have the minimum ceiling height in two-thirds of the area thereof, but in no case shall the height of the furred ceiling be less than 7 feet (2134 mm).
1208.3 Dwelling unit size. ¶
Dwelling units shall have a minimum of 190 square feet (17.7 m [2] ) of habitable space.
1208.4 Room area. ¶
Every dwelling unit shall have not less than one room that shall have not less than 120 square feet (11.2 m [2] ) of net floor area. Sleeping units and other habitable rooms of a dwelling unit shall have a net floor area of not less than 70 square feet (6.5 m [2] ).
Exception: Kitchens are not required to be of a minimum floor area.
1208.5 Efficiency dwelling units. ¶
[HCD 1] Unless modified by local ordinance pursuant to Health and Safety Code Section 17958.1, effi- ciency dwelling units shall comply with the following:
- The unit’s habitable space shall comply with Sections 1208.1 through 1208.4.
- The unit shall be provided with a separate closet.
- For other than Accessible, adaptable dwelling units, the unit shall be provided with a kitchen sink, cooking appliance and refrigerator, each having a clear working space of not less than 30 inches (762 mm) in front. Light and ventilation conforming to this code shall be provided.
- The unit shall be provided with a separate bathroom containing a water closet, lavatory and bathtub or shower.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
-
▸ Chapter 12 — INTERIOR ENVIRONMENT
Overview- Section 1201 — GENERAL
- Section 1202 — VENTILATION
- Section 1203 — TEMPERATURE CONTROL
- Section 1204 — LIGHTING
- Section 1205 — YARDS OR COURTS
- Section 1206 — SOUND TRANSMISSION
- Section 1207 — ENHANCED CLASSROOM ACOUSTICS
- Section 1208 — INTERIOR SPACE DIMENSIONS
- Section 1209 — ACCESS TO UNOCCUPIED SPACES
- Section 1210 — TOILET AND BATHROOM REQUIREMENTS
- Section 1211 — UV GERMICIDAL IRRADIATION SYSTEMS
- Section 1212 — [HCD 1 & HCD 2]—GARAGE DOOR SPRINGS
- Section 1213 — [HCD 1]—POLLUTANT CONTROL
- Section 1214 — RESERVED
- Section 1215 — RESERVED
- Section 1216 — RESERVED
- Section 1217 — RESERVED
- Section 1218 — RESERVED
- Section 1219 — RESERVED
- Section 1220 — RESERVED
- Section 1221 — RESERVED
- Section 1222 — RESERVED
- Section 1223 — RESERVED
- Section 1224 — [OSHPD 1]—HOSPITALS
- Section 1225 — [OSHPD 2]-SKILLED NURSING AND INTERMEDIATE-CARE…
- Section 1226 — [OSHPD 3]-CLINICS
- Section 1227 — [OSHPD 4]-CORRECTIONAL TREATMENT CENTERS
- Section 1228 — [OSHPD 5]—ACUTE PSYCHIATRIC HOSPITALS
- Section 1229 — [OSHPD 6] — CHEMICAL DEPENDENCY RECOVERY HOSPIT…
- Section 1230 — [BSCC] — MINIMUM STANDARDS FOR JUVENILE FACILIT…
- Section 1231 — [BSCC] — LOCAL DETENTION
- Section 1232 — RESERVED
- Section 1233 — RESERVED
- Section 1234 — RESERVED
- Section 1235 — [DPH]—SANITARY CONTROL OF SHELLFISH (PLANTS AND…
- Section 1236 — [DPH]—LABORATORY ANIMAL QUARTERS
- Section 1237 — [DPH]—WILD ANIMAL QUARANTINE FACILITIES
- Section 1238 — RESERVED
- Section 1239 — RESERVED
- Section 1240 — [AGR]—MEAT AND POULTRY PROCESSING PLANTS
- Section 1241 — [AGR]—COLLECTION CENTERS AND FACILITIES
- Section 1242 — [AGR]—RENDERERS
- Section 1243 — [AGR]—HORSEMEAT AND PET FOOD ESTABLISHMENTS
- Section 1244 — RESERVED
- Section 1245 — RESERVED
- Section 1246 — RESERVED
- Section 1247 — RESERVED
- Section 1248 — RESERVED
- Section 1249 — RESERVED
- Section 1250 — [CA]—PHARMACIES
- Section 1251 — [CA]—VETERINARY PREMISES
- Section 1252 — [CA]—BARBER COLLEGES AND SHOPS
- Section 1253 — [CA]—SCHOOLS OF COSMETOLOGY, COSMETOLOGICAL EST…
- Section 1254 — [CA]—ACUPUNCTURE OFFICES
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING