Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Section 1511 — ROOFTOP STRUCTURES
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BG] 1511.1 General. The provisions of this section shall govern the construction of rooftop structures.
1511.1.1 Area limitation. The aggregate area of penthouses and other enclosed rooftop structures shall not exceed one-third the area of the supporting roof deck. Such penthouses and other enclosed rooftop structures shall not be required to be included in determining the building height, number of stories or building area as regulated by Section 503.1. The area of such penthouses shall not be included in determining the fire area specified in Section 901.7.
[BG] 1511.2 Penthouses. Penthouses in compliance with Sections 1511.2.1 through 1511.2.4 shall be considered as a portion of the story directly below the roof deck on which such penthouses are located. Other penthouses shall be considered as an additional story of the building.
[BG] 1511.2.1 Height above roof deck. Penthouses constructed on buildings of other than Type I construction shall not exceed 18 feet (5486 mm) in height above the roof deck as measured to the average height of the roof of the penthouse. Penthouses located on the roof of buildings of Type I construction shall not be limited in height.
Exception: Where used to enclose tanks or elevators that travel to the roof level, penthouses shall be permitted to have a maximum height of 28 feet (8534 mm) above the roof deck.
[BG] 1511.2.2 Use limitations. Penthouses shall not be used for purposes other than the shelter of mechanical or electrical equipment, tanks, elevators and related machinery, stairways or vertical shaft openings in the roof assembly, including ancillary spaces used to access elevators and stairways.
[BG] 1511.2.3 Weather protection. Provisions such as louvers, louver blades or flashing shall be made to protect the mechanical and electrical equipment and the building interior from the elements.
[BG] 1511.2.4 Type of construction. Penthouses shall be constructed of building element materials as required for the type of construction of the building. Penthouse exterior walls and roof construction shall have a fire-resistance rating as required for the type of construction of the building. Supporting construction of such exterior walls and roof construction shall have a fire-resistance rating not less than required for the exterior wall or roof supported.
ed of building element materials as required for the type of construction of the building. Penthouse exterior walls and roof construction shall have a fire-resistance rating as required for the type of construction of the building. Supporting construction of such exterior walls and roof construction shall have a fire-resistance rating not less than required for the exterior wall or roof supported.
Exceptions:
- On buildings of Type I construction, the exterior walls and roofs of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating. The exterior walls and roofs of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall not be required to have a fire-resistance rating.
- On buildings of Type I construction two stories or less in height above grade plane or of Type II construction, the exterior walls and roofs of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating or a lesser fire-resistance rating as required by Table 705.5 and be constructed of fire-retardant-treated wood. The exterior walls and roofs of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall be permitted to be constructed of fire
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
retardant-treated wood and shall not be required to have a fire-resistance rating. Interior framing and walls shall be permitted to be constructed of fire-retardant-treated wood. 3. On buildings of Type III, IV or V construction, the exterior walls of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating or a lesser fire-resistance rating as required by Table 705.5. On buildings of Type III, IV or VA construction, the exterior walls of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall be permitted to be of heavy timber construction complying with Sections 602.4 and 2304.11 or noncombustible construction or fire-retardant-treated wood and shall not be required to have a fire-resistance rating.
[BG] 1511.3 Tanks. Tanks having a capacity of more than 500 gallons (1893 L) located on the roof deck of a building shall be supported on masonry, reinforced concrete, steel or heavy timber construction complying with Section 2304.11 provided that, where such supports are located in the building above the lowest story, the support shall be fire-resistance rated as required for Type IA construction.
[BG] 1511.3.1 Valve and drain. In the bottom or on the side near the bottom of the tank, a pipe or outlet, fitted with a suitable quick-opening valve for discharging the contents into a drain in an emergency shall be provided.
[BG] 1511.3.2 Location. Tanks shall not be placed over or near a stairway or an elevator shaft, unless there is a solid roof or floor underneath the tank.
[BG] 1511.3.3 Tank cover. Unenclosed roof tanks shall have covers sloping toward the perimeter of the tanks.
[BG] 1511.4 Cooling towers. Cooling towers located on the roof deck of a building and greater than 250 square feet (23.2 m [2] ) in base area or greater than 15 feet (4572 mm) in height above the roof deck, as measured to the highest point on the cooling tower, where the roof is greater than 50 feet (15 240 mm) in height above grade plane shall be constructed of noncombustible materials. The base area of cooling towers shall not exceed one-third the area of the supporting roof deck.
Exception: Drip boards and the enclosing construction shall be permitted to be of wood not less than 1 inch (25 mm) nominal thickness, provided that the wood is covered on the exterior of the tower with noncombustible material.
[BG] 1511.5 Towers, spires, domes and cupolas. Towers, spires, domes and cupolas shall be of a type of construction having fireresistance ratings not less than required for the building on top of which such tower, spire, dome or cupola is built. Towers, spires, domes and cupolas greater than 85 feet (25 908 mm) in height above grade plane as measured to the highest point on such structures, and either greater than 200 square feet (18.6 m [2] ) in horizontal area or used for any purpose other than a belfry or an architectural embellishment, shall be constructed of and supported on Type I or II construction.
[BG] 1511.5.1 Noncombustible construction required. Towers, spires, domes and cupolas greater than 60 feet (18 288 mm) in height above the highest point at which such structure contacts the roof as measured to the highest point on such structure, or that exceeds 200 square feet (18.6 m [2] ) in area at any horizontal section, or which is intended to be used for any purpose other than a belfry or architectural embellishment, or is located on the top of a building greater than 50 feet (1524 mm) in building height shall be constructed of and supported by noncombustible materials and shall be separated from the building below by construction having a fire-resistance rating of not less than 1.5 hours with openings protected in accordance with Section 711. Such structures located on the top of a building greater than 50 feet (15 240 mm) in building height shall be supported by noncombustible construction.
[BG] 1511.5.2 Towers and spires. Enclosed towers and spires shall have exterior walls constructed as required for the building on top of which such towers and spires are built. The roof covering of spires shall be not less than the same class of roof covering required for the building on top of which the spire is located.
[BG] 1511.6 Mechanical equipment screens. Mechanical equipment screens shall be constructed of the materials specified for the exterior walls in accordance with the type of construction of the building. Where the fire separation distance is greater than 5 feet (1524 mm), mechanical equipment screens shall not be required to comply with the fire-resistance rating requirements.
[BG] 1511.6.1 Height limitations. Mechanical equipment screens shall not exceed 18 feet (5486 mm) in height above the roof deck, as measured to the highest point on the mechanical equipment screen.
Exception: Where located on buildings of Type IA construction, the height of mechanical equipment screens shall not be limited.
[BG] 1511.6.2 Type I, II, III or IV construction. Regardless of the requirements in Section 1511.6, mechanical equipment screens that are located on the roof decks of buildings of Type I, II, III or IV construction shall be permitted to be constructed of combustible materials in accordance with any one of the following limitations:
- The fire separation distance shall be not less than 20 feet (6096 mm) and the height of the mechanical equipment screen above the roof deck shall not exceed 4 feet (1219 mm) as measured to the highest point on the mechanical equipment
screen.
- The fire separation distance shall be not less than 20 feet (6096 mm) and the mechanical equipment screen shall be constructed of fire-retardant-treated wood complying with Section 2303.2 for exterior installation.
- Where exterior wall covering panels are used, the panels shall have a flame spread index of 25 or less when tested in the minimum and maximum thicknesses intended for use, with each face tested independently in accordance with ASTM E84 or UL 723. The panels shall be tested in the minimum and maximum thicknesses intended for use in accordance with, and shall comply with the acceptance criteria of, NFPA 285 and shall be installed as tested. Where the panels are tested as part of an exterior wall assembly in accordance with NFPA 285, the panels shall be installed on the face of the
15-22 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
mechanical equipment screen supporting structure in the same manner as they were installed on the tested exterior wall assembly.
[BG] 1511.6.3 Type V construction. The height of mechanical equipment screens located on the roof decks of buildings of Type V construction, as measured from grade plane to the highest point on the mechanical equipment screen, shall be permitted to exceed the maximum building height allowed for the building by other provisions of this code where complying with any one of the following limitations, provided that the fire separation distance is greater than 5 feet (1524 mm):
- Where the fire separation distance is not less than 20 feet (6096 mm), the height above grade plane of the mechanical equipment screen shall not exceed 4 feet (1219 mm) more than the maximum building height allowed.
- The mechanical equipment screen shall be constructed of noncombustible materials.
- The mechanical equipment screen shall be constructed of fire-retardant-treated wood complying with Section 2303.2 for exterior installation.
ss than 20 feet (6096 mm), the height above grade plane of the mechanical equipment screen shall not exceed 4 feet (1219 mm) more than the maximum building height allowed. 2. The mechanical equipment screen shall be constructed of noncombustible materials. 3. The mechanical equipment screen shall be constructed of fire-retardant-treated wood complying with Section 2303.2 for exterior installation.
- Where the fire separation distance is not less than 20 feet (6096 mm), the mechanical equipment screen shall be constructed of materials having a flame spread index of 25 or less when tested in the minimum and maximum thicknesses intended for use with each face tested independently in accordance with ASTM E84 or UL 723.
[BG] 1511.7 Other rooftop structures. Rooftop structures not regulated by Sections 1511.2 through 1511.6 shall comply with Sections 1511.7.1 through 1511.7.6, as applicable.
[BG] 1511.7.1 Aerial supports. Aerial supports shall be constructed of noncombustible materials.
Exception: Aerial supports not greater than 12 feet (3658 mm) in height as measured from the roof deck to the highest point on the aerial supports shall be permitted to be constructed of combustible materials.
[BG] 1511.7.2 Bulkheads. Bulkheads used for the shelter of mechanical or electrical equipment or vertical shaft openings in the roof assembly shall comply with Section 1511.2 as penthouses. Bulkheads used for any other purpose shall be considered as an additional story of the building.
[BG] 1511.7.3 Dormers. Dormers shall be of the same type of construction as required for the roof in which such dormers are located or the exterior walls of the building.
[BG] 1511.7.4 Fences. Fences and similar structures shall comply with Section 1511.6 as mechanical equipment screens.
[BG] 1511.7.5 Flagpoles. Flagpoles and similar structures shall not be required to be constructed of noncombustible materials and shall not be limited in height or number.
[BG] 1511.7.6 Lightning protection systems. Lightning protection system components shall be installed in accordance with Sections 1511.7.6.1, 1511.7.6.2 and 2703.
[BG] 1511.7.6.1 Installation on metal edge systems or gutters. Lightning protection system components attached to ANSI/SPRI/FM 4435/ES-1 or ANSI/SPRI GT-1 tested metal edge systems or gutters shall be installed with compatible brackets, fasteners or adhesives, in accordance with the metal edge systems or gutter manufacturer’s installation instructions. Where the metal edge system or gutter manufacturer is unknown, installation shall be as directed by a registered design professional.
em components attached to ANSI/SPRI/FM 4435/ES-1 or ANSI/SPRI GT-1 tested metal edge systems or gutters shall be installed with compatible brackets, fasteners or adhesives, in accordance with the metal edge systems or gutter manufacturer’s installation instructions. Where the metal edge system or gutter manufacturer is unknown, installation shall be as directed by a registered design professional.
[BG] 1511.7.6.2 Installation on roof coverings. Lightning protection system components directly attached to or through the roof covering shall be installed in accordance with this chapter and the roof covering manufacturer’s installation instructions. Flashing shall be installed in accordance with the roof assembly manufacturer’s installation instructions and Sections 1503.2 and 1507 where the lightning protection system installation results in a penetration through the roof covering. Where the roof covering manufacturer is unknown, installation shall be as directed by a registered design professional.
[BG] 1511.8 Structural fire resistance. The structural frame and roof construction supporting loads imposed upon the roof by any rooftop structure shall comply with the requirements of Table 601. The fire-resistance reduction permitted by Table 601, Note a, shall not apply to roofs containing rooftop structures.
[BG] 1511.9 Raised-deck systems installed over a roof assembly. Raised-deck systems installed above a roof assembly shall comply with Sections 1511.9.1 through 1511.9.5.
[BG] 1511.9.1 Installation. The installation of a raised-deck system shall comply with all of the following:
The perimeter of the raised-deck system shall be surrounded on all sides by walls or by a noncombustible enclosure approved to prevent fire intrusion below the raised-deck system. The wall or enclosure shall extend at least from the roof assembly to the top surface of the raised-deck system. The enclosure shall not impede roof drainage in accordance with Section 1511.9.5.
A raised-deck system shall be installed above a listed roof assembly.
Exception: Where the roof assembly is not required to have a fire classification in accordance with Section 1505.2. 3. A raised-deck system shall be installed in accordance with the manufacturer’s installation instructions. 4. A raised-deck system shall not impede the operation of plumbing or mechanical vents, exhaust, air inlets or roof drains. Where required, access for inspection, cleaning or maintenance shall be provided.
[BG] 1511.9.2 Fire classification. The raised-deck system shall be listed and identified with a fire classification in accordance with Section 1505 and shall be tested in accordance with either Section 1511.9.2.1 or 1511.9.2.2.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
[BG] 1511.9.2.1 Fire testing of the raised deck system installed over a classified roof assembly. The raised-deck system shall be tested separately from the roof assembly over which it is installed. The fire classification of the raised-deck system shall be not less than the fire classification for the roof assembly over which it is installed.
Exception: Where the decking or pavers of the raised-deck system consists of brick, masonry, concrete or other noncombustible materials, fire testing of the raised-deck system is not required.
[BG] 1511.9.2.2 Fire testing of the raised deck system together with the roof assembly. The roof assembly and the raiseddeck system shall be tested together.
[BG] 1511.9.3 Pedestals or supports. The pedestals or supports for the raised-deck system shall be installed in accordance with manufacturer’s installation instructions.
[BG] 1511.9.4 Structural requirements. The raised-deck system shall be designed for all applicable loads in accordance with Chapter 16 and performance requirements in Section 1504.5.
[ BG] 1511.9.5 Roof drainage. The raised-deck system, including the wall or enclosure between the roof assembly and the raised deck, shall be designed and installed to allow for the operation of the roof drainage system as required by Section 1502 and the California Plumbing Code. The roof structure shall be designed to support any standing water resulting from the installation of the raised-deck system.
[BG] 1511.9.6 Accessibility and egress. The raised-deck system shall be accessible in accordance with Chapters 11A or 11B, as applicable, and means of egress shall be provided in accordance with Chapter 10.
1511.10 Photovoltaic (PV) panel systems. ¶
1511.10 Photovoltaic (PV) panel systems. [BSC, DSA-SS, DSA-SS/CC, HCD 1 & HCD 2, OSHPD 1, 1R, 2, 4 & 5] Rooftop-mounted photo- voltaic panels and modules shall be listed and labeled in accordance with Section 3111.3.1 and installed in accordance with the manufacturer’s printed installation instructions.
1511.10.1 Design. [BSC, DSA-SS, DSA-SS/CC, HCD 1 & HCD 2, OSHPD 1, 1R, 2, 4 & 5] Supports and attachments of photovoltaic panels to the roof structure, the panels, modules and components shall be designed in accordance with this code. 1. Seismic design shall be in accordance with ASCE 7 Section 13.6.12. 2. Wind design pressures shall be determined from ASCE 7 Section 29.4.3 or 29.4.4 using effective wind area in accordance with ASCE 7 Section 26.2.
Construction documents for the supports and attachments shall be submitted to the enforcement agency for approval.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
-
▸ Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Overview- Section 1501 — GENERAL
- Section 1502 — ROOF DRAINAGE
- Section 1503 — WEATHER PROTECTION
- Section 1504 — PERFORMANCE REQUIREMENTS
- Section 1505 — FIRE CLASSIFICATION
- Section 1506 — MATERIALS
- Section 1507 — REQUIREMENTS FOR ROOF COVERINGS
- Section 1508 — ROOF INSULATION
- Section 1509 — ROOF COATINGS
- Section 1510 — RADIANT BARRIERS INSTALLED ABOVE DECK
- Section 1511 — ROOFTOP STRUCTURES
- Section 1512 — REROOFING
- Section 1513 — [DSA-SS & DSA-SS/CC, OSHPD 1, 1R, 2, 4 & 5] SEI…
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING