1605A Load Combinations — 2025 California Building Code

California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Building Code (Title 24, Part 2) § 1605A · Effective January 1, 2026 · Official source: Building Standards Commission

1605 A .1 General. Buildings and other structures and portions thereof shall be designed to resist the strength load combinations specified in ASCE 7, Section 2.3, the allowable stress design load combinations specified in ASCE 7, Section 2.4, or the alternative allowable stress design load combinations of Section 1605 A .2. Exceptions:

  1. The modifications to load combinations of ASCE 7, Section 2.3, ASCE 7, Section 2.4 and Section 1605 A .2 specified in ASCE 7 Chapters 18 and 19 shall apply.

  2. Where the allowable stress design load combinations of ASCE 7, Section 2.4 are used, flat roof snow loads of 45 pounds per square foot (2.15 kN/m [2] ) and roof live loads of 30 pounds per square foot (1.44 kN/m [2] ) or less need not be combined with seismic load. Where flat roof snow loads exceed 45 pounds per square foot (2.15 kN/m [2] ), 15 percent shall be combined with seismic loads.

  3. Where the allowable stress design load combinations of ASCE 7 Section 2.4 are used, crane hook loads need not be combined with roof live loads or with more than three-fourths of the snow load or one-half of the wind loads.

  4. Where design for tornado loads is required, the alternative allowable stress design load combinations of Section 1605 A .2 shall not apply when tornado loads govern the design.

1605 A .1.1 Stability. Regardless of which load combinations are used to design for strength, where overall structure stability (such as stability against overturning, sliding, or buoyancy) is being verified, use of the load combinations specified in Section 2.3 or 2.4 of ASCE 7, and in Section 1605 A .2 shall be permitted. Where the load combinations specified in ASCE 7, Section 2.3 are used, strength reduction factors applicable to soil resistance shall be provided by a registered design professional. The stability of retaining walls shall be verified in accordance with Section 1807 A .2.3. When using allowable stress design, factor of safety for soil bearing values shall not be less than the overstrength factor of the structures supported.

1605A.1.2 Foundation resistance. [OSHPD 1 & 4] Strength design for foundation geotechnical capacity shall be in accordance with ASCE 7, Section 12.13.5 for all strength design load combinations, except that Resistance Factor (Ø) shall be permitted to be 1.0 for load combinations with amplified seismic forces in accordance with Section 1617A.1.15. Allowable stress design for founda- tion geotechnical capacity shall be in accordance with ASCE 7, Section 12.13.6 for all allowable stress design load combinations, and shall be established to be consistent with strength design requirements in ASCE 7, Section 12.13.5.

1605 A .2 Alternative allowable stress design load combinations. In lieu of the load combinations in ASCE 7, Section 2.4, structures and portions thereof shall be permitted to be designed for the most critical effects resulting from the following combinations. Where using these alternative allowable stress load combinations that include wind or seismic loads, allowable stresses are permitted to be increased or load combinations reduced where permitted by the material chapter of this code or the referenced standards. For load combinations that include the counteracting effects of dead and wind loads, only two-thirds of the minimum dead load likely to be in place during a design wind event shall be used. Where using these alternative load combinations to evaluate sliding, overturning and soil bearing at the soil-structure interface, the reduction of foundation overturning from Section 12.13.4 in ASCE 7 shall not be used. Where using these alternative basic load combinations for proportioning foundations for loadings, which include seismic loads, the vertical seismic load effect, E v , in Equation 12.4-4 of ASCE 7 is permitted to be taken equal to zero. Where required by ASCE 7, Chapters 12, 13 and 15, the load combinations including overstrength of ASCE 7, Section 2.4.5 shall be used. Each load combination shall be investigated with one or more of the variable loads set to zero.

Equation 16 A -1 D + L + ( L r or 0.7 S or R )

Equation 16 A -2 D + L + 0.6 W

Equation 16 A -3 D + L + 0.6 W + 0.7 S /2

Equation 16 A -4 D + L + 0.7 S + 0.6 W /2

Equation 16 A -5 D + L + 0.7 S + E /1.4

Equation 16 A -6 0.9 D + E /1.4

Exceptions:

  1. Crane hook loads need not be combined with roof live loads or with more than three-fourths of the snow load or one-half

of the wind load.

  1. Flat roof snow loads of 45 pounds per square foot (2.15 kN/m [2] ) or less and roof live loads of 30 pounds per square foot (1.44 kN/m [2] ) or less need not be combined with seismic loads. Where flat roof snow loads exceed 45 pounds per square foot (2.15 kN/m [2] ), 15 percent shall be combined with seismic loads.

1605A.3 Modifications to load combinations in ICC 300.

Modify the text of ICC 300 as follows:

1605A.3.1 ICC 300, Section 303.5.3. Modify Section 303.5.3 as follows:

The uniform live load L used in Equations 3-4 and 3-9 shall be permitted to be taken as zero when evaluating elements supporting the handrail/guard provided those elements do not also support L.