Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE
421 Hydrogen Fuel Gas Rooms — 2025 California Building Code
California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Building Code (Title 24, Part 2) § 421 · Effective January 1, 2026 · Official source: Building Standards Commission
421.1 General.¶
[F] 421.1 General. Where required by the California Fire Code, hydrogen fuel gas rooms shall be designed and constructed in accordance with Sections 421.1 through 421.7.
421.2 Location.¶
[F] 421.2 Location. Hydrogen fuel gas rooms shall not be located below grade.
421.3 Design and construction.¶
[F] 421.3 Design and construction. Hydrogen fuel gas rooms not classified as Group H shall be separated from other areas of the building in accordance with Section 509.1.
[F] 421.3.1 Pressure control. Hydrogen fuel gas rooms shall be provided with a ventilation system designed to maintain the room at a negative pressure in relation to surrounding rooms and spaces.
[F] 421.3.2 Windows. Operable windows in interior walls shall not be permitted. Fixed windows shall be permitted where in accordance with Section 716.
421.4 Exhaust ventilation.¶
[F] 421.4 Exhaust ventilation. Hydrogen fuel gas rooms shall be provided with mechanical exhaust ventilation in accordance with the applicable provisions of the California Mechanical Code .
421.5 Gas detection system.¶
[F] 421.5 Gas detection system. Hydrogen fuel gas rooms shall be provided with a gas detection system that complies with Sections 421.5.1, 421.5.2, and 916.
[F] 421.5.1 System activation. Activation of a gas detection alarm shall result in both of the following:
- Initiation of distinct audible and visible alarm signals both inside and outside of the hydrogen fuel gas room.
- Automatic activation of the mechanical exhaust ventilation system.
[F] 421.5.2 Failure of the gas detection system. Failure of the gas detection system shall automatically activate the mechanical exhaust ventilation system, stop hydrogen generation, and cause a trouble signal to sound at an approved location.
421.6 Explosion control.¶
[F] 421.6 Explosion control. Explosion control shall be provided where required by Section 414.5.1.
421.7 Standby power.¶
[F] 421.7 Standby power. Mechanical ventilation and gas detection systems shall be provided with a standby power system in accordance with Section 2702.
Continue researching
Related topics
State and federal sources. Edit the document title or filters, then run your search.
Get a plain-English answer with a citation back to this text.
Ask AI about this code