Skip to content

Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL

Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS

2025 California Green Building Standards Code (Title 24, Part 11) · 2025 edition · updated 2026-07-25 · California

A4.204.1 Energy efficiency. Alterations to existing residential buildings shall comply with Sections A4.204.1.1 and A4.204.1.2.

A4.204.1.1 Altered space-conditioning system serving existing single-family dwelling units – mechanical cooling. When a space-conditioning system serving an existing single-family dwelling unit is altered in Climate Zones 1 through 14 and 16 by installation or replacement of an air conditioner, the altered system shall comply with either a or b below in addition to the requirements for installation specified by Title 24, Part 6, Sections 150.2(b)1E and 150.2(b)1F: a. A heat pump shall be the primary heating source and sized according to the system selection requirements specified by Title 24, Part 6 of Section 150.0(h)5. Supplemental heating may be provided by an existing gas furnace or existing electric resistance heating; or b. An air conditioner shall meet the following requirements: i. R-8 duct insulation for ducts located in unconditioned space; and ii. The duct system measured air leakage shall be equal to or less than 5 percent of the system air handler airflow as confirmed through field verification and diagnostic testing, per the requirements in Title 24, Part 6, Reference Residential Appendix Section RA3.1.4.3.1; and iii. Demonstrate, in every control mode, airflow greater than or equal to 400 CFM per ton of nominal cooling capacity through the return grilles, and an air-handling unit fan efficacy less than or equal to 0.35 W/CFM. The airflow rate and fan efficacy requirements in this section shall be confirmed through field verification and diagnostic testing, following the procedures outlined in Title 24, Part 6, Reference Residential Appendix RA3.3; and iv. In all climate zones refrigerant charge verification requirements shall meet the requirements in Title 24, Part 6 Section 150.2(b)1Fiib; and v. Vented attics shall have insulation installed to achieve a U -factor of 0.020 or insulation installed at the ceiling level shall result in an insulated thermal resistance of R-49 or greater for the insulation alone; and vi. Air seal all accessible areas of the ceiling plane between the attic and the conditioned space in accordance with the requirements in Title 24, Part 6 Section 150.2(b)1Jii.

Exception 1 to Section A4.204.1.1: Where the capacity of the existing main electrical service panel is insufficient to supply the electrical capacity of a heat pump and where the existing main electrical service panel is sufficient to supply a new or replacement air conditioner, as calculated according to the requirements of California Electrical Code Article 220.83 or 220.87. Documentation of electrical load calculations in accordance with Article 220 must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.

e the existing main electrical service panel is sufficient to supply a new or replacement air conditioner, as calculated according to the requirements of California Electrical Code Article 220.83 or 220.87. Documentation of electrical load calculations in accordance with Article 220 must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.

Exception 2 to Section A4.204.1.1: Where the required capacity of a heat pump to meet the system selection requirements of Section 150.0(h)5 is greater than or equal to 12,000 Btu/h more than the required capacity of an air conditioner to meet the design cooling load. Documentation of heating and cooling load calculations in accordance with 150.0(h) must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.

A4.204.1.2 Altered pool and/or spa heating for existing multifamily buildings. Alteration of an existing multifamily pool and/or spa heating system shall meet the following:

Heating source sizing. Heating systems or equipment for pools or spas shall meet one of the sizing requirements of Items 1 through 5 below:

  1. A solar pool heating system with a solar collector surface area that is equivalent to 65 percent or greater of the surface areas of the pool or spa or a combination of both respectively; or
  2. A heat pump pool heater as the primary heating system that meets the sizing requirements of Reference Joint Appendix JA16.3. The control for the heat pump pool heater shall meet the requirements specified in Title 24, Part 6, Section 110.4(d). The supplementary heater can be of any energy source; or
  3. A heating system that derives at least 60 percent of the annual heating energy from on-site renewable energy or on-site recovered energy; or
  4. A combination of a solar pool heating system and heat pump pool heater without any additional supplementary heater; or
  5. A pool heating system determined by the Energy Commission Executive Director to use no more energy than the systems specified in Item 1, 2, 3, or 4 above.

Exception 1 to A4.204.1.2: Portable electric spas compliant with 20 CCR, Section 1605.3(g)(7) of the Appliance Efficiency Regulations.

Exception 2 to A4.204.1.2: A pool or spa that is heated solely by a solar pool heating system without any supplementary heater.

Exception 3 to A4.204.1.2: An existing building with inadequate Solar Access Roof Area (SARA) as specified in Title 24, Part 6, Section 170.2(f) for a solar pool heating system to be installed.

Exception 4 to A4.204.1.2: Heating systems which are used exclusively for permanent spa applications in existing buildings with gas availability.

Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25402, 25402.1, 25402.4 and 25402.8, Public Resources Code.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A4-12 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

A4 RESIDENTIAL VOLUNTARY MEASURES

DIVISION A4.3 – WATER EFFICIENCY AND CONSERVATION

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Green Building Standards Code (Title 24, Part 11)
2025 California Green Building Standards Code (Title 24, Part 11)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GREEN BUILDING
  4. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  5. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  6. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  7. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  8. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  9. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  10. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  11. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  12. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  13. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  14. Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
  15. Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
  16. Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
    Overview
    1. Section A4.101 — GENERAL
    2. Section A4.102 — DEFINITIONS
    3. Section A4.103 — SITE SELECTION
    4. Section A4.104 — SITE PRESERVATION
    5. Section A4.105 — DECONSTRUCTION AND REUSE OF EXISTING MATERIALS
    6. Section A4.106 — SITE DEVELOPMENT
    7. Section A4.107
    8. Section A4.108 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    9. Section A4.201 — GENERAL
    10. Section A4.202 — DEFINITIONS
    11. Section A4.203 — PERFORMANCE APPROACH FOR NEWLY CONSTRUCTED BU…
    12. Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUIL…
    13. Section A4.301 — GENERAL
    14. Section A4.302 — DEFINITIONS
    15. Section A4.303 — INDOOR WATER USE
    16. Section A4.304 — OUTDOOR WATER USE
    17. Section A4.305 — WATER REUSE SYSTEMS
    18. Section A4.306 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    19. Section A4.401 — GENERAL
    20. Section A4.402 — DEFINITIONS
    21. Section A4.403 — FOUNDATION SYSTEMS
    22. Section A4.404 — EFFICIENT FRAMING TECHNIQUES
    23. Section A4.405 — MATERIAL SOURCES
    24. Section A4.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    25. Section A4.407 — WATER RESISTANCE AND MOISTURE MANAGEMENT
    26. Section A4.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    27. Section A4.409 — LIFE CYCLE ASSESSMENT
    28. Section A4.410 — BUILDING MAINTENANCE AND OPERATION
    29. Section A4.411 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    30. Section A4.501 — GENERAL
    31. Section A4.502 — DEFINITIONS
    32. Section A4.503 — FIREPLACES
    33. Section A4.504 — POLLUTANT CONTROL
    34. Section A4.505 — INTERIOR MOISTURE CONTROL
    35. Section A4.506 — INDOOR AIR QUALITY AND EXHAUST
    36. Section A4.507 — ENVIRONMENTAL COMFORT
    37. Section A4.508 — OUTDOOR AIR QUALITY
    38. Section A4.509 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    39. Section A4.601 — GENERAL
    40. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST
    41. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    42. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    43. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    44. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    45. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    46. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    47. Section A5.101 — GENERAL
    48. Section A5.102 — DEFINITIONS
    49. Section A5.103 — SITE SELECTION
    50. Section A5.104 — SITE PRESERVATION
    51. Section A5.105 — DECONSTRUCTION AND REUSE OF EXISTING STRUCTURES
    52. Section A5.106 — SITE DEVELOPMENT
    53. Section A5.107 — BIRD-FRIENDLY BUILDING DESIGN
    54. Section A5.201 — GENERAL
    55. Section A5.202 — DEFINITIONS
    56. Section A5.203 — PERFORMANCE APPROACH
    57. Section A5.204 — MANDATORY REQUIREMENTS FOR ALTERATIONS TO EXI…
    58. Section A5.211 — RESERVED
    59. Section A5.212 — ELEVATORS, ESCALATORS AND OTHER EQUIPMENT
    60. Section A5.213 — ENERGY EFFICIENT FRAMING
    61. Section A5.301 — GENERAL
    62. Section A5.302 — DEFINITIONS
    63. Section A5.303 — INDOOR WATER USE
    64. Section A5.304 — OUTDOOR WATER USE
    65. Section A5.305 — WATER REUSE
    66. Section A5.401 — GENERAL
    67. Section A5.402 — DEFINITIONS
    68. Section A5.403 — FOUNDATION SYSTEMS
    69. Section A5.404 — EFFICIENT FRAMING TECHNIQUES
    70. Section A5.405 — MATERIAL SOURCES
    71. Section A5.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    72. Section A5.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    73. Section A5.409 — LIFE CYCLE ASSESSMENT
    74. Section A5.501 — GENERAL
    75. Section A5.502 — DEFINITIONS
    76. Section A5.504 — POLLUTANT CONTROL
    77. Section A5.507 — ENVIRONMENTAL COMFORT
    78. Section A5.508 — OUTDOOR AIR QUALITY
    79. Section A6.106 — SITE DEVELOPMENT
    80. Section A6.202 — DEFINITIONS
    81. Section A6.203 — PERFORMANCE APPROACH
    82. Section A6.204 — PRESCRIPTIVE APPROACH
    83. Section A6.205 — [OSHPD 1 & 4]—BUILDING ENVELOPE
    84. Section A6.207 — [OSHPD 1, 2 & 4]—HVAC DESIGN, EQUIPMENT AND I…
    85. Section A6.210 — [OSHPD 1, 2 & 4]—APPLIANCES
    86. Section A6.401 — GENERAL
    87. Section A6.407 — [OSHPD 1, 2 & 4]—WATER RESISTANCE AND MOISTUR…
    88. Section A6.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    89. Section A6.410 — BUILDING MAINTENANCE AND OPERATION
    90. Section A6.504 — POLLUTANT CONTROL
    91. Section A6.505 — [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.