Section A5.507 — ENVIRONMENTAL COMFORT

2025 California Green Building Standards Code (Title 24, Part 11) · 2025 edition · updated 2026-07-25 · California

A5.507.1 Lighting and thermal comfort controls. Provide controls in the workplace as described in Sections A5.507.1.1 and A5.507.1.2.

A5.507.1.1 Single-occupant spaces. Provide individual controls that meet energy use requirements in the California Energy Code in accordance with Sections A5.507.1.1.1 and A5.507.1.1.2.

A5.507.1.1.1 Lighting. Provide individual task lighting and/or daylighting controls for at least 90 percent of the building occupants.

A5.507.1.1.2 Thermal comfort. Provide individual thermal comfort controls for at least 50 percent of the building occupants.

  1. Occupants shall have control over at least one of the factors of air temperature, radiant temperature, air speed and humidity as described in ASHRAE 55-2004.
  2. Occupants inside 20 feet of the plane of and within 10 feet either side of operable windows can substitute windows to control thermal comfort. The areas of operable window must meet the requirements of Section 120.1 (Requirement for Ventilation) of the California Energy Code.

A5.507.1.2 Multi-occupant spaces. Provide lighting and thermal comfort system controls for all shared multi-occupant spaces, such as classrooms and conference rooms.

A5.507.2 Daylight. Provide daylit spaces as required for toplighting and sidelighting in the California Energy Code. In constructing a design, consider the following:

  1. Use of light shelves and reflective room surfaces to maximize daylight penetrating the rooms
  2. Means to eliminate glare and direct sun light, including through skylights
  3. Use of photosensors to turn off electric lighting when daylight is sufficient
  4. Not using diffuse daylighting glazing where views are desired

A5.507.3 Views. Achieve direct line of sight to the outdoor environment via vision glazing between 2 feet 6 inches and 7 feet 6 inches above finish floor for building occupants in 90 percent of all regularly occupied areas as demonstrated by plan view and section cut diagrams.

A5.507.3.1 Interior office spaces. Entire areas of interior office spaces may be included in the calculation if at least 75 percent of each area has direct line of sight to perimeter vision glazing.

A5.507.3.2 Multi-occupant spaces. Include in the calculation the square footage with direct line of sight to perimeter vision glazing.

Exceptions to Sections A5.507.2 and A5.507.3. Copy/ printing rooms, storage areas, mechanical spaces, rest- rooms, auditoria and other intermittently or infrequently occupied spaces or spaces where daylight would interfere with use of the space.

A5.507.5 Acoustical control [DSA-SS]. Public Schools and Community Colleges: Unoccupied, furnished classrooms must have a maximum background noise level of no more than 45 dBA LAeq and a maximum (unoccupied, furnished) reverberation of 0.6-second time for classrooms with less than 10,000 cubic feet and a maximum (unoccupied, furnished) reverberation of 0.7-second time for classroom volumes with between 10,000 cubic feet and 20,000 cubic feet.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Green Building Standards Code (Title 24, Part 11)
2025 California Green Building Standards Code (Title 24, Part 11)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GREEN BUILDING
  4. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  5. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  6. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  7. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  8. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  9. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  10. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  11. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  12. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  13. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  14. Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
  15. Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
  16. Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
    Overview
    1. Section A4.101 — GENERAL
    2. Section A4.102 — DEFINITIONS
    3. Section A4.103 — SITE SELECTION
    4. Section A4.104 — SITE PRESERVATION
    5. Section A4.105 — DECONSTRUCTION AND REUSE OF EXISTING MATERIALS
    6. Section A4.106 — SITE DEVELOPMENT
    7. Section A4.107
    8. Section A4.108 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    9. Section A4.201 — GENERAL
    10. Section A4.202 — DEFINITIONS
    11. Section A4.203 — PERFORMANCE APPROACH FOR NEWLY CONSTRUCTED BU…
    12. Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUIL…
    13. Section A4.301 — GENERAL
    14. Section A4.302 — DEFINITIONS
    15. Section A4.303 — INDOOR WATER USE
    16. Section A4.304 — OUTDOOR WATER USE
    17. Section A4.305 — WATER REUSE SYSTEMS
    18. Section A4.306 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    19. Section A4.401 — GENERAL
    20. Section A4.402 — DEFINITIONS
    21. Section A4.403 — FOUNDATION SYSTEMS
    22. Section A4.404 — EFFICIENT FRAMING TECHNIQUES
    23. Section A4.405 — MATERIAL SOURCES
    24. Section A4.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    25. Section A4.407 — WATER RESISTANCE AND MOISTURE MANAGEMENT
    26. Section A4.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    27. Section A4.409 — LIFE CYCLE ASSESSMENT
    28. Section A4.410 — BUILDING MAINTENANCE AND OPERATION
    29. Section A4.411 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    30. Section A4.501 — GENERAL
    31. Section A4.502 — DEFINITIONS
    32. Section A4.503 — FIREPLACES
    33. Section A4.504 — POLLUTANT CONTROL
    34. Section A4.505 — INTERIOR MOISTURE CONTROL
    35. Section A4.506 — INDOOR AIR QUALITY AND EXHAUST
    36. Section A4.507 — ENVIRONMENTAL COMFORT
    37. Section A4.508 — OUTDOOR AIR QUALITY
    38. Section A4.509 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    39. Section A4.601 — GENERAL
    40. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST
    41. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    42. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    43. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    44. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    45. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    46. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    47. Section A5.101 — GENERAL
    48. Section A5.102 — DEFINITIONS
    49. Section A5.103 — SITE SELECTION
    50. Section A5.104 — SITE PRESERVATION
    51. Section A5.105 — DECONSTRUCTION AND REUSE OF EXISTING STRUCTURES
    52. Section A5.106 — SITE DEVELOPMENT
    53. Section A5.107 — BIRD-FRIENDLY BUILDING DESIGN
    54. Section A5.201 — GENERAL
    55. Section A5.202 — DEFINITIONS
    56. Section A5.203 — PERFORMANCE APPROACH
    57. Section A5.204 — MANDATORY REQUIREMENTS FOR ALTERATIONS TO EXI…
    58. Section A5.211 — RESERVED
    59. Section A5.212 — ELEVATORS, ESCALATORS AND OTHER EQUIPMENT
    60. Section A5.213 — ENERGY EFFICIENT FRAMING
    61. Section A5.301 — GENERAL
    62. Section A5.302 — DEFINITIONS
    63. Section A5.303 — INDOOR WATER USE
    64. Section A5.304 — OUTDOOR WATER USE
    65. Section A5.305 — WATER REUSE
    66. Section A5.401 — GENERAL
    67. Section A5.402 — DEFINITIONS
    68. Section A5.403 — FOUNDATION SYSTEMS
    69. Section A5.404 — EFFICIENT FRAMING TECHNIQUES
    70. Section A5.405 — MATERIAL SOURCES
    71. Section A5.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    72. Section A5.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    73. Section A5.409 — LIFE CYCLE ASSESSMENT
    74. Section A5.501 — GENERAL
    75. Section A5.502 — DEFINITIONS
    76. Section A5.504 — POLLUTANT CONTROL
    77. Section A5.507 — ENVIRONMENTAL COMFORT
    78. Section A5.508 — OUTDOOR AIR QUALITY
    79. Section A6.106 — SITE DEVELOPMENT
    80. Section A6.202 — DEFINITIONS
    81. Section A6.203 — PERFORMANCE APPROACH
    82. Section A6.204 — PRESCRIPTIVE APPROACH
    83. Section A6.205 — [OSHPD 1 & 4]—BUILDING ENVELOPE
    84. Section A6.207 — [OSHPD 1, 2 & 4]—HVAC DESIGN, EQUIPMENT AND I…
    85. Section A6.210 — [OSHPD 1, 2 & 4]—APPLIANCES
    86. Section A6.401 — GENERAL
    87. Section A6.407 — [OSHPD 1, 2 & 4]—WATER RESISTANCE AND MOISTUR…
    88. Section A6.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    89. Section A6.410 — BUILDING MAINTENANCE AND OPERATION
    90. Section A6.504 — POLLUTANT CONTROL
    91. Section A6.505 — [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.