Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)

BK108 Fire Resistance — 2025 California Residential Code

California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Residential Code (Title 24, Part 2.5) § BK108 · Effective January 1, 2026 · Official source: Building Standards Commission

BK108.1 Fire-resistance rating.

Cob walls that comply with Table BK108.1 have a 2-hour fire-resistance rating.

TABLE BK108.1—TWO-HOUR FIRE-RESISTANCE-RATED COB WALLS

ALLOWABLE SUPER-
IMPOSED LOAD
(plf)
DENSITYa, d
(pcf)
MINIMUM COMPRES-
SIVE STRENGTH PER
SECTION BK106.6.1
(psi)
WALL-TYPE
REINFORCEMENT
PER TABLE
BK105.3
MINIMUM
THICKNESSc, e, f AT
TOP OF WALL
(inches)
MINIMUM
THICKNESSc, e, f AT
BOTTOM OF WALL
(inches)
1,200 100 85 E 9 12
475 ≥ 50 pcf: less than
40 inches from top of wall
40b E or F 8 12
475 ≥ 70 pcf: from 40 inches to 80
inches from top of wall
55b 55b 55b 55b
475 ≥ 90 pcf: more than 80 inches
from top of wall
85 85 85 85
Nonload bearing 50 to 100 ≥ 60 psi
< 60 psib
E or F 9 9
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.45 kg, 1 pound per cubic foot = 16.02 kg/m3.
a.
Density is to be measured at equilibrium moisture content. Average wall density shall be within ±5 pcf of the tabulated value.
b.
Requires an approved engineered design per Section BK106.6.
c.
Cob thickness only. The interior and exterior cob faces shall be permitted to be unfinished or receive any plaster finish allowed by this appendix.
d.
Cob walls with more than one density shall be built with heavier densities below lighter densities.
e.
Minimum cob wall thickness shall be whichever is greater in Tables BK105.3, BK106.11(1) and BK108.1.
f.
Wall thicknesses less than 10 inches require an engineered design.
Exceptions & meaning →

BK108.2 Clearance to fireplaces and chimneys.

Cob walls or other cob surfaces shall not require clearance to fireplaces and chimneys, except where clearance to noncombustibles is required by the manufacturer’s instructions.