Section R329 — SOLAR ENERGY SYSTEMS

2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

R329.1 General. Solar energy systems shall comply with the provisions of this section.

R329.2 Solar thermal systems.

Solar thermal systems shall be designed and installed in accordance with the California Plumbing Code and the California Fire Code.

R329.3 Photovoltaic systems.

Photovoltaic ( PV ) systems shall be designed and installed in accordance with Sections R329.3.1 through R329.8.1 and the manufacturer’s installation instructions. The electrical portion of solar PV systems shall be designed and installed in accordance with the California Electrical Code.

R329.3.1 Equipment listings. Photovoltaic panels and modules shall be listed and labeled in accordance with UL 1703 or with both UL 61730-1 and UL 61730-2. Inverters shall be listed and labeled in accordance with UL 1741. Systems connected to the utility grid shall use inverters listed for utility interaction. Mounting systems listed and labeled in accordance with UL 2703 shall be installed in accordance with the manufacturer’s installation instructions and their listings. Building-integrated photovoltaic (BIPV) roof coverings and BIPV roof assemblies shall be listed and labeled in accordance with UL 7103.

3-74 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

BUILDING PLANNING

R329.4 Rooftop-mounted photovoltaic systems.

Rooftop-mounted photovoltaic panel systems installed on or above the roof covering shall be designed and installed in accordance with this section.

R329.4.1 Structural requirements. Rooftop-mounted photovoltaic panel systems shall be designed to structurally support the system and withstand applicable gravity loads in accordance with Chapter 3. The roof on which these systems are installed shall be designed and constructed to support the loads imposed by such systems in accordance with Chapter 8.

R329.4.1.1 Roof load. Portions of roof structures not covered with photovoltaic panel systems shall be designed for dead loads and roof loads in accordance with Sections R301.4 and R301.6. Portions of roof structures covered with photovoltaic panel systems shall be designed for the following load cases:

  1. Dead load (including photovoltaic panel weight) plus snow load in accordance with Table R301.2.
  2. Dead load (excluding photovoltaic panel weight) plus roof live load or snow load, whichever is greater, in accordance with Section R301.6.

R329.4.1.2 Wind load. Rooftop-mounted photovoltaic panel or module systems and their supports shall be designed and installed to resist the component and cladding loads specified in Table R301.2.1(1), adjusted for height and exposure in accordance with Table R301.2.1(2).

R329.4.2 Fire classification. Rooftop-mounted photovoltaic panel systems shall have the same fire classification as the roof assembly required in Section R902.

R329.4.3 Roof penetrations. Roof penetrations shall be flashed and sealed in accordance with Chapter 9.

R329.5 Building-integrated photovoltaic systems.

Building-integrated photovoltaic (BIPV) systems shall be designed and installed in accordance with Sections R329.5.1 through R329.5.2.

R329.5.1 BIPV roofing systems. BIPV roofing systems shall comply with Section R905.15. BIPV roof panels shall comply with Section R905.16.

R329.5.1.1 Fire classification. Building-integrated photovoltaic systems shall have a fire classification in accordance with Section R902.3.

R329.5.2 BIPV exterior wall coverings and fenestration. BIPV exterior wall coverings and fenestration shall comply with Section R705.

R329.6 Roof access and pathways.

Roof access, pathways and setback requirements shall be provided in accordance with Sections R329.6.1 through R329.6.2.1. Access and minimum spacing shall be required to provide emergency access to the roof, to provide pathways to specific areas of the roof, provide for smoke ventilation opportunity areas, and to provide emergency egress from the roof.

Exceptions:

  1. Detached, nonhabitable structures, including but not limited to detached garages, parking shade structures, carports, solar trellises and similar structures, shall not be required to provide roof access.
  2. Roof access, pathways and setbacks need not be provided where the enforcing agency has determined that rooftop operations will not be employed.
  3. These requirements shall not apply to roofs with slopes of 2 units vertical in 12 units horizontal (17-percent slope) or less.
  4. BIPV systems listed in accordance with UL 3741, where the removal or cutting away of portions of the BIPV system during firefighting operations has been determined to not expose a firefighter to electrical shock hazards.

R329.6.1 Pathways. Not fewer than two pathways, on separate roof planes from lowest roof edge to ridge and not less than 36 inches (914 mm) wide, shall be provided on all buildings. Not fewer than one pathway shall be provided on the street or driveway side of the roof. For each roof plane with a photovoltaic array, a pathway not less than 36 inches wide (914 mm) shall be provided from the lowest roof edge to ridge on the same roof plane as the photovoltaic array, on an adjacent roof plane, or straddling the same and adjacent roof planes. Pathways shall be over areas capable of supporting firefighters accessing the roof. Pathways shall be located in areas with minimal obstructions such as vent pipes, conduit, or mechanical equipment.

R329.6.2 Setback at ridge. For photovoltaic arrays occupying not more than 33 percent of the plan view total roof area, not less than an 18-inch (457 mm) clear setback is required on both sides of a horizontal ridge. For photovoltaic arrays occupying more than 33 percent of the plan view total roof area, not less than a 36-inch (914 mm) clear setback is required on both sides of a horizontal ridge.

R329.6.2.1 Alternative setback at ridge. Where an automatic sprinkler system is installed within the dwelling or townhouse in accordance with NFPA 13D or Section R309, setbacks at ridges shall comply with one of the following:

  1. For photovoltaic arrays occupying not more than 66 percent of the plan view total roof area, not less than an 18-inch (457 mm) clear setback is required on both sides of a horizontal ridge.
  2. For photovoltaic arrays occupying more than 66 percent of the plan view total roof area, not less than a 36-inch (914 mm) clear setback is required on both sides of a horizontal ridge.

e of the following:

  1. For photovoltaic arrays occupying not more than 66 percent of the plan view total roof area, not less than an 18-inch (457 mm) clear setback is required on both sides of a horizontal ridge.
  2. For photovoltaic arrays occupying more than 66 percent of the plan view total roof area, not less than a 36-inch (914 mm) clear setback is required on both sides of a horizontal ridge.

R329.6.3 Emergency escape and rescue openings. Panels and modules installed on dwellings or townhouses shall not be placed on the portion of a roof that is below an emergency escape and rescue opening. A pathway not less than 36 inches (914 mm) wide shall be provided to the emergency escape and rescue opening.

Exception: BIPV systems listed in accordance with UL 3741, where the removal or cutting away of portions of the BIPV system during firefighting operations has been determined to not expose a firefighter to electrical shock hazards.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

BUILDING PLANNING

R329.6.4 Building-integrated photovoltaic (BIPV) systems. Where building-integrated photovoltaic (BIPV) systems are installed in a manner creating areas with electrical hazards that are hidden from view, markings shall be provided to identify the hazardous areas to avoid for ladder placement. The markings shall be reflective and be visible from grade beneath the eaves or other location approved by the fire code official.

Exception: BIPV systems listed in accordance with UL 3741, where the removal or cutting away of portions of the BIPV system during firefighting operations have been determined to not expose a firefighter to electrical shock hazards.

R329.7 Elevated photovoltaic (PV) support structures.

Elevated PV support structures used as an accessory structure shall comply with either Section R329.7.1 or R329.7.2. Elevated PV support structures shall be considered a roof for the purposes of establishing the number of stories and fire separation distances.

Exception : Elevated PV support structures that are installed over agricultural use.

R329.7.1 PV panels installed over open-grid framing or noncombustible deck. Elevated PV support structures with PV panels installed over open-grid framing or over a noncombustible deck shall have PV panels tested, listed and labeled with a fire type rating in accordance with UL 1703 or with both UL 61730-1 and UL 61730-2. Photovoltaic panels marked “not fire rated” shall not be installed on elevated PV support structures.

R329.7.2 PV panels installed over a roof assembly. Elevated PV support structures with a PV panel system installed over a roof assembly shall have a fire classification in accordance with Section R902.4 and Section R329.4.

R329.8 Ground-mounted photovoltaic (PV) panel systems.

Ground-mounted photovoltaic (PV) panel systems shall be designed and installed in accordance with Section R301.

R329.8.1 Fire separation distances. Ground-mounted photovoltaic systems shall be subject to the fire separation distance requirements determined by the enforcing agency.

R329.8.2 Ground-mounted photovoltaic arrays. Ground mounted photovoltaic arrays shall comply with this section and the Cali- fornia Electrical Code. Setback requirements shall not apply to ground-mounted, free-standing photovoltaic arrays. A clear, brush- free area of 10 feet (3048 mm) shall be required for ground-mounted photovoltaic arrays.

R329.8.3 Locations of DC conductors. Conduit, wiring systems and raceways for photovoltaic circuits shall be located as close as possible to the ridge or hip or valley and from the hip or valley as directly as possible to an outside wall to reduce trip hazards and maximize ventilation opportunities. Conduit runs between sub arrays and to DC combiner boxes shall be installed in a manner that minimizes the total amount of conduit on the roof by taking the shortest path from the array to the DC combiner box. The DC combiner boxes shall be located such that conduit runs are minimized in the pathways between arrays. DC wiring shall be installed in metallic conduit or raceways when located within enclosed spaces in a building. Conduit shall run along the bottom of load bearing members.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Residential Code (Title 24, Part 2.5)
2025 California Residential Code (Title 24, Part 2.5)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — BUILDING PLANNING
    Overview
    1. Section R300 — SITE DRAINAGE
    2. Section R301 — DESIGN CRITERIA
    3. Section R302 — FIRE-RESISTANT CONSTRUCTION
    4. Section R303 — FOAM PLASTIC
    5. Section R304 — PROTECTION OF WOOD AND WOOD-BASED PRODUCTS AGAI…
    6. Section R305 — PROTECTION AGAINST SUBTERRANEAN TERMITES
    7. Section R306 — FLOOD-RESISTANT CONSTRUCTION
    8. Section R307 — STORM SHELTERS
    9. Section R308 — SITE ADDRESS
    10. Section R309 — AUTOMATIC SPRINKLER SYSTEMS
    11. Section R310 — SMOKE ALARMS
    12. Section R311 — CARBON MONOXIDE ALARMS
    13. Section R312 — MINIMUM ROOM AREAS
    14. Section R313 — CEILING HEIGHT
    15. Section R314 — MEZZANINES
    16. Section R315 — SLEEPING LOFTS
    17. Section R316 — HABITABLE ATTICS
    18. Section R317 — GARAGES AND CARPORTS
    19. Section R318 — MEANS OF EGRESS
    20. Section R319 — EMERGENCY ESCAPE AND RESCUE OPENINGS
    21. Section R320 — HANDRAILS
    22. Section R321 — GUARDS AND WINDOW FALL PROTECTION
    23. Section R322 — ACCESSIBILITY
    24. Section R323 — ELEVATORS AND PLATFORM LIFTS
    25. Section R324 — GLAZING
    26. Section R325 — LIGHT, VENTILATION AND HEATING
    27. Section R326 — SANITATION
    28. Section R327 — TOILET, BATH AND SHOWER SPACES
    29. Section R328 — AGING-IN-PLACE DESIGN AND FALL PREVENTION
    30. Section R329 — SOLAR ENERGY SYSTEMS
    31. Section R330 — ENERGY STORAGE SYSTEMS
    32. Section R331 — STATIONARY ENGINE GENERATORS
    33. Section R332 — STATIONARY FUEL CELL POWER SYSTEMS
    34. Section R333 — RESERVED
    35. Section R334 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECY…
    36. Section R335 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FA…
    37. Section R336 — LARGE FAMILY DAY-CARE HOMES
    38. Section R337 — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR…
    39. Section R338 — ELECTRIC VEHICLE
    40. Section 339 — RESERVED
    41. Section R340 — POLLUTANT CONTROL
  4. Chapter 4 — FOUNDATIONS
  5. Chapter 5 — FLOORS
  6. Chapter 6 — WALL CONSTRUCTION
  7. Chapter 7 — WALL COVERING
  8. Chapter 8 — ROOF-CEILING CONSTRUCTION
  9. Chapter 9 — ROOF ASSEMBLIES
  10. Chapter 10 — CHIMNEYS AND FIREPLACES
  11. Chapter 44 — REFERENCED STANDARDS
  12. Appendix AA — BOARD OF APPEALS
  13. Appendix AB — PERMIT FEES
  14. Appendix AC — RESERVED
  15. Appendix BA — RESERVED
  16. Appendix BB — TINY HOUSES
  17. Appendix BC — RESERVED
  18. Appendix BD — RESERVED
  19. Appendix BE — RADON CONTROL METHODS
  20. Appendix BF — PATIO COVERS
  21. Appendix BG — SOUND TRANSMISSION
  22. Appendix BH — AUTOMATIC VEHICULAR GATES
  23. Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
  24. Appendix BJ — STRAWBALE CONSTRUCTION
  25. Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
  26. Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
  27. Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
  28. Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
  29. Appendix BO — EXISTING BUILDINGS AND STRUCTURES
  30. Appendix CA — RESERVED
  31. Appendix CB — RESERVED
  32. Appendix CC — RESERVED
  33. Appendix CD — RESERVED
  34. Appendix CE — RESERVED
  35. Appendix CF — RESERVED
  36. Appendix CG — NONSEWERED SANITATION SYSTEMS
  37. Appendix CH — PRIVATE SEWAGE DISPOSAL
  38. Appendix CI — SWIMMING POOL SAFETY ACT
  39. Appendix CJ — EMERGENCY HOUSING
  40. Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.