Los Angeles Building Code — LAMC Chapter IX § 95.300 Basic Provisions

Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-23 · Los Angeles

Cite as: Los Angeles Building Code — LAMC Chapter IX § 95.300 · Text as of 2026-09-23

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

Chapter 3 of the CMC is hereby adopted by reference with the following amendment:

311.3. Prohibited Source. Outside or return air for heating or cooling air systems shall not be taken from the following locations:

(1) less than 10 feet (3048 mm) in distance from an appliance vent outlet, a vent opening of a plumbing drainage system, or the discharge outlet of an exhaust fan or a medical-surgical vacuum outlet, unless the outlet is 3 feet (914 mm) above the outside-air inlet.

DIVISION 4

VENTILATION AIR

(Title Amended by Ord. No. 184,692, Eff. 12/30/16.)

Section 95.400 Basic Provisions.

SEC. 95.400. BASIC PROVISIONS.

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

Chapter 4 of the CMC is hereby adopted by reference.

DIVISION 5

EXHAUST SYSTEMS

(Amended by Ord. No. 179,327, Eff. 12/10/07, Oper. 1/1/08.)

Section 95.500 Basic Provisions.