Chapter 11A — HOUSING ACCESSIBILITY
Section 1139A — ACCESSIBLE DRINKING FOUNTAINS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1139A.1 General. ¶
Drinking fountains and water coolers in common use areas and/or sites shall comply with this section. A side approach drinking fountain is not acceptable. (See Figure 11A-11A.)
1139A.2 Accessible route. ¶
Drinking fountains and water coolers shall be on an accessible route.
1139A.3 Depth. ¶
Drinking fountains shall be a minimum of 18 inches (457 mm) and a maximum of 19 inches (483 mm) in depth.
1139A.4 Clear floor space. ¶
Drinking fountains shall be provided with 30 inches by 48 inches (762 mm by 1219 mm) clear floor space, centered on the unit. The clear floor space shall be positioned for a forward approach.
1139A.4.1 Knee and toe space. Drinking fountains shall be provided with a clear and unobstructed knee and toe space. Knee and toe space shall comply with Section 1138A.2.
1139A.5 Spout location. ¶
The spout shall be located 15 inches (381 mm) minimum from the vertical support and 5 inches (127 mm) maxi- mum from the front edge of the drinking fountain, including bumpers. Spout outlets shall be 36 inches (914 mm) maximum above the finish floor.
1139A.6 Water flow. ¶
The spout shall provide a flow of water at least 4 inches (101.6 mm) high to allow the insertion of a cup or glass under the flow of water. The angle of the water stream shall be measured horizontally relative to the front face of the unit. When spouts are located less than 3 inches (76 mm) from the front of the unit, the angle of the water stream shall be 30 degrees maximum. When spouts are located between 3 inches (76 mm) and 5 inches (127 mm) maximum from the front of the unit, the angle of the water stream shall be 15 degrees maximum.
1139A.7 Controls and operating mechanisms. ¶
The flow of water shall be activated by manually or electronically operated controls. The manually operated controls shall be front mounted or side mounted, located within 6 inches (152 mm) of the front edge of the foun- tain. The force required to activate controls shall be no greater than 5 pounds (22.2 N).
1139A.8 Location. ¶
Drinking fountains shall be located completely within alcoves, between wing walls or otherwise positioned so as not to encroach into pedestrian ways. The alcove or otherwise protected area in which the drinking fountain is located shall not be less than 32 inches (813 mm) in width and 18 inches (457 mm) in depth. When the depth of the protected area where the drinking fountain is located exceeds 24 inches (610 mm), additional maneuvering clearance shall be provided in accordance with Section 1138A.1.4.2 and Figure 11A-1H.
11A-40 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
HOUSING ACCESSIBILITY
When provided, wing walls shall project out from the supporting wall at least as far as the drinking fountain to within 6 inches (152.4 mm) vertically from the finish floor.
Protruding objects located in alcoves or otherwise positioned so as to limit encroachment into pedestrian ways are permitted to proj- ect 4 inches (101.6 mm) into walks, halls, corridors, passageways or aisles. (See Figure 11A-11A.)
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
-
▸ Chapter 11A — HOUSING ACCESSIBILITY
Overview- Section 1101A — APPLICATION
- Section 1102A — BUILDING ACCESSIBILITY
- Section 1103A — DESIGN AND CONSTRUCTION
- Section 1104A — COVERED MULTIFAMILY DWELLINGS
- Section 1105A — GARAGES, CARPORTS AND PARKING FACILITIES
- Section 1106A — SITE AND BUILDING CHARACTERISTICS
- Section 1107A — DEFINITIONS
- Section 1108A — GENERAL REQUIREMENTS FOR ACCESSIBLE PARKING AN…
- Section 1109A — PARKING FACILITIES
- Section 1110A — EXTERIOR ACCESSIBLE ROUTES
- Section 1111A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
- Section 1112A — CURB RAMPS ON ACCESSIBLE ROUTES
- Section 1113A — WALKS AND SIDEWALKS ON ACCESSIBLE ROUTES
- Section 1114A — EXTERIOR RAMPS AND LANDINGS ON ACCESSIBLE ROUTES
- Section 1115A — EXTERIOR STAIRWAYS
- Section 1116A — HAZARDS ON ACCESSIBLE ROUTES
- Section 1117A — GENERAL REQUIREMENTS FOR ACCESSIBLE ENTRANCES,…
- Section 1118A — EGRESS AND AREAS OF REFUGE
- Section 1119A — INTERIOR ACCESSIBLE ROUTES
- Section 1120A — RESERVED
- Section 1121A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
- Section 1122A — INTERIOR RAMPS AND LANDINGS ON ACCESSIBLE ROUTES
- Section 1123A — INTERIOR STAIRWAYS
- Section 1124A — ELEVATORS AND PLATFORM (WHEELCHAIR) LIFTS
- Section 1125A — HAZARDS ON ACCESSIBLE ROUTES
- Section 1126A — DOORS, GATES AND WINDOWS
- Section 1127A — COMMON USE FACILITIES
- Section 1128A — COVERED DWELLING UNITS
- Section 1129A — RESERVED
- Section 1130A — ACCESSIBLE ROUTE WITHIN COVERED MULTIFAMILY DW…
- Section 1131A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
- Section 1132A — DOORS
- Section 1133A — KITCHENS
- Section 1134A — BATHING AND TOILET FACILITIES
- Section 1135A — LAUNDRY ROOMS
- Section 1136A — ELECTRICAL RECEPTACLE, SWITCH AND CONTROL HEIG…
- Section 1137A — OTHER FEATURES AND FACILITIES
- Section 1138A — SPACE ALLOWANCES AND REACH RANGES
- Section 1139A — ACCESSIBLE DRINKING FOUNTAINS
- Section 1140A — ACCESSIBLE TELEPHONES
- Section 1141A — ACCESSIBLE SWIMMING POOLS
- Section 1142A — ELECTRICAL RECEPTACLE, SWITCH AND CONTROL HEIG…
- Section 1143A — SIGNAGE
- Section 1144A — RESERVED
- Section 1145A — RESERVED
- Section 1146A — RESERVED
- Section 1147A — RESERVED
- Section 1148A — RESERVED
- Section 1149A — RESERVED
- Section 1150A — SITE IMPRACTICALITY TESTS
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING