1142A.1 Receptacle heights.

Electrical receptacle outlets on branch circuits of 30 amperes or less and communication system recep- tacles shall be located no more than 48 inches (1219 mm) measured from the top of the receptacle outlet box nor less than 15 inches (381 mm) measured from the bottom of the receptacle outlet box to the level of the finished floor or working platform. If the reach is over a physical barrier or an obstruction (for example, a kitchen base cabinet), receptacles shall be located within the reach ranges specified in Section 1138A.3. Physical barriers and obstructions shall not extend more than 25 inches (635 mm) from the wall beneath the receptacle.

Receptacle outlets that do not satisfy these specifications are acceptable provided that comparable receptacle outlets, that perform the same functions, are provided within the same area and are accessible.

Exceptions:

1. Receptacle outlets installed as part of permanently installed baseboard heaters are exempt. 2. Required receptacle outlets shall be permitted in floors when adjacent to sliding panels or walls. 3. Baseboard electrical outlets used in relocatable partitions, window walls or other electrical convenience floor outlets are not subject to the minimum height requirements. 4. This section shall not apply to existing buildings when the enforcing agency determines that compliance with these stan- dards would create an unreasonable hardship.

1142A.2 Switch and control heights.

Controls or switches intended to be used by the occupant of the room or area to control lighting and receptacle outlets, appliances, alarms or cooling, heating and ventilating equipment shall be located no more than 48 inches (1219 mm) measured from the top of the outlet box nor less than 15 inches (381 mm) measured from the bottom of the outlet box to the level of the finished floor or working platform. If the reach is over a physical barrier or an obstruction (for example, a kitchen base cabinet), switches and controls shall be located within the reach ranges specified in Section 1138A.3. Physical barriers or obstructions shall not extend more than 25 inches (635 mm) from the wall beneath a switch or control.

Switches and controls that do not satisfy these specifications are acceptable provided that comparable controls or outlets, that perform the same functions, are provided within the same area and are accessible.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Building Code (Title 24, Part 2)
2025 California Building Code (Title 24, Part 2)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  4. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
  5. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  6. Chapter 6 — TYPES OF CONSTRUCTION
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
  9. Chapter 8 — INTERIOR FINISHES
  10. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  11. Chapter 10 — MEANS OF EGRESS
  12. Chapter 11 — RESERVED
  13. Chapter 11A — HOUSING ACCESSIBILITY
    Overview
    1. Section 1101A — APPLICATION
    2. Section 1102A — BUILDING ACCESSIBILITY
    3. Section 1103A — DESIGN AND CONSTRUCTION
    4. Section 1104A — COVERED MULTIFAMILY DWELLINGS
    5. Section 1105A — GARAGES, CARPORTS AND PARKING FACILITIES
    6. Section 1106A — SITE AND BUILDING CHARACTERISTICS
    7. Section 1107A — DEFINITIONS
    8. Section 1108A — GENERAL REQUIREMENTS FOR ACCESSIBLE PARKING AN…
    9. Section 1109A — PARKING FACILITIES
    10. Section 1110A — EXTERIOR ACCESSIBLE ROUTES
    11. Section 1111A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
    12. Section 1112A — CURB RAMPS ON ACCESSIBLE ROUTES
    13. Section 1113A — WALKS AND SIDEWALKS ON ACCESSIBLE ROUTES
    14. Section 1114A — EXTERIOR RAMPS AND LANDINGS ON ACCESSIBLE ROUTES
    15. Section 1115A — EXTERIOR STAIRWAYS
    16. Section 1116A — HAZARDS ON ACCESSIBLE ROUTES
    17. Section 1117A — GENERAL REQUIREMENTS FOR ACCESSIBLE ENTRANCES,…
    18. Section 1118A — EGRESS AND AREAS OF REFUGE
    19. Section 1119A — INTERIOR ACCESSIBLE ROUTES
    20. Section 1120A — RESERVED
    21. Section 1121A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
    22. Section 1122A — INTERIOR RAMPS AND LANDINGS ON ACCESSIBLE ROUTES
    23. Section 1123A — INTERIOR STAIRWAYS
    24. Section 1124A — ELEVATORS AND PLATFORM (WHEELCHAIR) LIFTS
    25. Section 1125A — HAZARDS ON ACCESSIBLE ROUTES
    26. Section 1126A — DOORS, GATES AND WINDOWS
    27. Section 1127A — COMMON USE FACILITIES
    28. Section 1128A — COVERED DWELLING UNITS
    29. Section 1129A — RESERVED
    30. Section 1130A — ACCESSIBLE ROUTE WITHIN COVERED MULTIFAMILY DW…
    31. Section 1131A — CHANGES IN LEVEL ON ACCESSIBLE ROUTES
    32. Section 1132A — DOORS
    33. Section 1133A — KITCHENS
    34. Section 1134A — BATHING AND TOILET FACILITIES
    35. Section 1135A — LAUNDRY ROOMS
    36. Section 1136A — ELECTRICAL RECEPTACLE, SWITCH AND CONTROL HEIG…
    37. Section 1137A — OTHER FEATURES AND FACILITIES
    38. Section 1138A — SPACE ALLOWANCES AND REACH RANGES
    39. Section 1139A — ACCESSIBLE DRINKING FOUNTAINS
    40. Section 1140A — ACCESSIBLE TELEPHONES
    41. Section 1141A — ACCESSIBLE SWIMMING POOLS
    42. Section 1142A — ELECTRICAL RECEPTACLE, SWITCH AND CONTROL HEIG…
    43. Section 1143A — SIGNAGE
    44. Section 1144A — RESERVED
    45. Section 1145A — RESERVED
    46. Section 1146A — RESERVED
    47. Section 1147A — RESERVED
    48. Section 1148A — RESERVED
    49. Section 1149A — RESERVED
    50. Section 1150A — SITE IMPRACTICALITY TESTS
  14. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  15. Chapter 12 — INTERIOR ENVIRONMENT
  16. Chapter 13 — ENERGY EFFICIENCY
  17. Chapter 14 — EXTERIOR WALLS
  18. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  19. Chapter 16 — STRUCTURAL DESIGN
  20. Chapter 16A — STRUCTURAL DESIGN
  21. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  22. Chapter 17A — SPECIAL INSPECTIONS AND TESTS
  23. Chapter 18 — SOILS AND FOUNDATIONS
  24. Chapter 18A — SOILS AND FOUNDATIONS
  25. Chapter 19 — CONCRETE
  26. Chapter 19A — CONCRETE
  27. Chapter 20 — ALUMINUM
  28. Chapter 21 — MASONRY
  29. Chapter 21A — MASONRY
  30. Chapter 22 — STEEL
  31. Chapter 22A — STEEL
  32. Chapter 23 — WOOD
  33. Chapter 24 — GLASS AND GLAZING
  34. Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
  35. Chapter 26 — PLASTIC
  36. Chapter 27 — ELECTRICAL
  37. Chapter 28 — MECHANICAL SYSTEMS
  38. Chapter 29 — PLUMBING SYSTEMS
  39. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  40. Chapter 31 — SPECIAL CONSTRUCTION
  41. Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
  42. Chapter 31B — PUBLIC POOLS
  43. Chapter 31C — RADIATION
  44. Chapter 31D — FOOD ESTABLISHMENTS
  45. Chapter 31F — MARINE OIL TERMINALS
  46. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  47. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  48. Chapter 34 — RESERVED
  49. Chapter 35 — REFERENCED STANDARDS
  50. Appendix A — EMPLOYEE QUALIFICATIONS
  51. Appendix B — BOARD OF APPEALS
  52. Appendix C — GROUP U—AGRICULTURAL BUILDINGS
  53. Appendix D — FIRE DISTRICTS
  54. Appendix E — RESERVED
  55. Appendix F — RODENTPROOFING
  56. Appendix G — FLOOD-RESISTANT CONSTRUCTION
  57. Appendix H — SIGNS
  58. Appendix I — PATIO COVERS
  59. Appendix J — GRADING
  60. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
  61. Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
  62. Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
  63. Appendix N — REPLICABLE BUILDINGS
  64. Appendix O — PERFORMANCE-BASED APPLICATION
  65. Appendix P — SLEEPING LOFTS
  66. Appendix Q — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.