Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2.

TABLE 1305.2

MINIMUM FLOW RATES (cubic feet per minute)

MEDICAL SYSTEM FLOW RATE

Oxygen
0.71 CFM per outlet1

Nitrous Oxide
0.71 CFM per outlet1

Medical Compressed Air
0.71 CFM per outlet1

Nitrogen
15 CFM free air per outlet

Vacuum
1 SCFM per inlet2

Carbon Dioxide
0.71 CFM per outlet1

Helium
0.71 CFM per outlet

For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s

Notes: 1 A room designed for a permanently located respiratory ventilator or anesthesia machine shall have an outlet capable of a flow rate of 6.36 CFM (3.0 L/s) at the station outlet. 2 For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM (1.4 L/s), while maintaining a system pressure of not less than 12 inches of mercury (41 kPa) at the nearest adjacent vacuum inlet.