Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2.
TABLE 1305.2
MINIMUM FLOW RATES (cubic feet per minute)
| MEDICAL SYSTEM | FLOW RATE |
|---|---|
Oxygen |
0.71 CFM per outlet1 |
Nitrous Oxide |
0.71 CFM per outlet1 |
Medical Compressed Air |
0.71 CFM per outlet1 |
Nitrogen |
15 CFM free air per outlet |
Vacuum |
1 SCFM per inlet2 |
Carbon Dioxide |
0.71 CFM per outlet1 |
Helium |
0.71 CFM per outlet |
For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s
Notes: 1 A room designed for a permanently located respiratory ventilator or anesthesia machine shall have an outlet capable of a flow rate of 6.36 CFM (3.0 L/s) at the station outlet. 2 For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM (1.4 L/s), while maintaining a system pressure of not less than 12 inches of mercury (41 kPa) at the nearest adjacent vacuum inlet.