Section 4.106 — SITE DEVELOPMENT
San Francisco Building Inspection Commission Codes · 2022 edition · updated 2026-07-25 · San Francisco
4.106.4 Revise this section as follows:
4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Section 4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers. Electric vehicle supply equipment (EVSE) shall be installed in accordance with the California Electrical Code, Article 625.
Exceptions:
- On a case-by-case basis, where the local enforcing agency has determined EV charging and infrastructure are not feasible based upon one or more of the following conditions:
1.1 Where there is no local utility power supply or the local utility is unable to supply adequate power.
1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional local utility infrastructure design requirements,
← directly related to the implementation of Section 4.106.4, [ ] increase the utility side cost to the homeowner or the developer by more than $400 per parking space. In such cases, buildings subject to Section 4.106.4 shall maximize the number of EV Charging Spaces, up to a utility side cost of a maximum of $400 per space. Cost shall be determined by dividing the increase in local utility infrastructure cost attributable to compliance with this section by the sum of parking spaces and EV Charging Spaces.
- Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional parking facilities.
4.106.4.1 New one-and-two-family dwellings and townhouses with attached or adjacent private garages. [ ← ] For each parking space, install a 40-Amp 208 or 240-volt branch circuit, including raceway, electrical panel capacity, overprotection devices, wire, and termination point such as a receptacle. The termination point shall be in close proximity to the proposed EV charger location. Raceways are required to be continuous at enclosed, inaccessible, or concealed areas and spaces. Raceway for each circuit shall not be less than trade size 1 (nominal 1-inch inside diameter).
4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging as [ ← ] “EV READY” for full circuits. The raceway termination location shall be permanently and visibly marked as [ ← ] “EV
READY” for full circuits.
4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions. The charging spaces shall be designed to comply with the following:
The minimum length of each EV space shall be 18 feet (5486 mm).
The minimum width of each EV space shall be 9 feet (2743 mm).
One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is 12 feet (3658 mm).
a. Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction.
b. Notwithstanding any other applicable requirements, when an EV charger is installed serving an accessible parking space, the space may be considered a parking space if the duration of stay is not subject to any limitations different from those generally applied to other publicly accessible parking spaces in the same parking area. If the duration of stay in an accessible space equipped with an EV charger is subject to limitations different from those generally applied to other publicly accessible parking spaces in the same parking area, the space is not a parking space.
4.106.4.2.2.1.3 Accessible EV spaces. In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE, when installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A. Accessible spaces must meet the dimensions specified in Section 4.106 .4.2.2.1.2, Planning Code Section 154, or other applicable accessibility requirements, whichever would result in the largest space size.
4.106.4.2.3 EV space requirements.
Single EV space required. [ ← ] Where a single EV space is required, install a full circuit with a minimum of 40-Amp 208 or 240 Volt capacity, including listed raceway, sufficient electrical panel capacity, overcurrent protection devices, wire, and termination point such as a receptacle. The termination point shall be in close proximity to the proposed EV charger location. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter).
Multiple EV spaces required. Construction documents shall indicate the raceway termination point and the location of installed or future EV spaces, receptacles, or EV chargers. Construction documents shall also provide information on amperage of installed or future receptacles or EVSE, raceway method(s), wiring schematics and electrical load calculations. Plan design shall be based upon a 40-ampere minimum branch circuit. Required raceways and related components that are planned to be installed underground, enclosed, inaccessible or in concealed areas and spaces shall be installed at the time of original construction.
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the location or the proposed location of the EV space at the time of original construction in accordance with the California Electrical Code.
a. Multiple Levels of Parking:
i. Branch circuit panelboard(s) shall be installed at each parking level with service capacity dedicated to EV Capable Spaces and EV spaces proportional to the number of vehicle spaces on each level, including panelboard(s) space and capacity. The circuits and overcurrent protective devices shall remain reserved exclusively for EV charging.
Exception: Circuits and overcurrent protective devices in panelboards not located on the same level may contribute to the requirements of 4.106.4.2.4(b), provided the circuits are reserved exclusively for EV charging. For example, the circuit serving an EV Space dedicated to a condominium owner may connect to the electrical panelboard of the corresponding condominium.
ii. Install raceway or sleeves where penetrations to walls, floors, or other partitions will be necessary to install panels, raceways, or related electrical components necessary per site conditions for future installation of branch circuits. All such penetrations must comply with applicable codes, including but not limited to the San Francisco Electrical Code and the San Francisco Fire Code.
NOTES:
Electric vehicle charging infrastructure and housing are critical priorities for the City and County of San Francisco. Automated Load Management Systems, energy efficiency, and selection of low-amperage technologies can help mitigate increases to peak electric load. Where the installation of a utility electrical transformer may be determined to be necessary in the context of compliance with Section 4.106.4.2.4 of this chapter, SF Building Code Section 106A.1.17.1, or other provisions of the San Francisco Electrical Code, and where such transformer cannot be accommodated on the project site due to the combination of project site dimensions, San Francisco Building Code, San Francisco Electrical Code, and applicable utility regulations, the Director of Public Works is encouraged to issue a Sidewalk Vault Encroachment Permit, provided that the fronting property owner complies with all requirements governing street occupancy, including but not limited to the San Francisco Public Works Code and Department of Public Works Order 165,553.
4.106.4.2.4 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EVSE READY” for full circuits and otherwise “EVSE CAPABLE” in accordance with the California Electrical Code.
Division 4.2
ENERGY EFFICIENCY
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — San Francisco Building Inspection Commission Codes
- Section 101A — TITLE, SCOPE AND GENERAL
- Section 102A — UNSAFE BUILDINGS, STRUCTURES OR PROPERTY
- Section 103A — VIOLATIONS
- Section 104A — ORGANIZATION AND ENFORCEMENT
- Section 105A — BOARDS, COMMISSIONS, AND COMMITTEES
- Section 106A — PERMITS
- Section 107A — FEES
- Section 108A — INSPECTIONS
- Section 109A — CERTIFICATE OF OCCUPANCY; AMENDED CERTIFICATE O…
- Section 110A — SCHEDULE OF FEE TABLES
- Section 111A — ADAPTIVE REUSE
- Section 202 — DEFINITIONS
- Section 406 — MOTOR-VEHICLE-RELATED OCCUPANCIES
- Section 435 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FAC…
- Section 456 — FENCES
- Section 707 — FIRE BARRIERS
- Section 901 — GENERAL
- Section 903 — AUTOMATIC SPRINKLER SYSTEMS
- Section 905 — STANDPIPE SYSTEMS
- Section 907 — FIRE ALARM AND DETECTION SYSTEMS
- Section 912 — FIRE DEPARTMENT CONNECTIONS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1001A — SCOPE
- Section 1002A — DEFINITIONS
- Section 1003A — GENERAL REQUIREMENTS FOR SECURITY
- Section 1004A — SPECIAL HOTEL AND MOTEL SECURITY REQUIREMENTS
- Section 1005A — SPECIAL APARTMENT HOUSE AND CONDOMINIUM SECURITY
- Section 1101D — SCOPE
- Section 1102D — DEFINITIONS
- Section 1103D — DEPARTMENT COORDINATION
- Section 1104D — DISABILITY ACCESS COMPLIANCE UNIT
- Section 1105D — REPORTS TO THE MAYOR’S OFFICE ON DISABILITY AN…
- Section 1106D — NOTICE
- Section 1107D — [REPEALED]
- Section 1108D — [REPEALED]
- Section 1109D — [REPEALED]
- Section 1110D — [REPEALED]
- Section 1111D — [REPEALED]
- Section 1112D — [REPEALED]
- Section 1113D — [REPEALED]
- Section 1114D — [REPEALED]
- Section 1202 — VENTILATION
- Section 1204 — LIGHTING
- Section 1206 — SOUND TRANSMISSION
- 1208.4 Revise paragraph 1 of this section and add paragraphs 5…
- Section 1210 — [ ← ] TOILET, BATHROOM AND LACTATION ROOM REQUI…
- Section 1301A — TITLE
- Section 1302A — INTENT
- Section 1303A — DEFINITIONS
- Section 1304A — RULES AND GUIDELINES
- Section 1305A — CIVIL REMEDIES
- Section 1306A — REQUIREMENTS
- Section 1307A — INFORMATIONAL BROCHURE
- Section 1308A — POSTPONEMENTS OF REQUIREMENTS
- Section 1309A — EARLY COMPLIANCE WITH WATER CONSERVATION MEASU…
- Section 1310A — WATER CONSERVATION INSPECTIONS
- Section 1311A — PROOF OF COMPLIANCE WITH WATER CONSERVATION ME…
- Section 1312A — APPEALS FROM RESULTS OF A WATER CONSERVATION I…
- Section 1313A — REQUIRED WATER CONSERVATION MEASURES
- Section 1314A — WATER CONSERVATION INSPECTIONS
- Section 1301B — TITLE
- Section 1302B — RECOVERY OF CONSTRUCTION AND DEMOLITION DEBRIS
- Section 1303B — DEFINITIONS
- Section 1304B — PERMIT CONDITION
- Section 1305B — PERMIT NOTIFICATION
- Section 1301D — TITLE
- Section 1302D — PURPOSE
- Section 1303D — SCOPE
- Section 1304D — DEFINITIONS
- Section 1305D — COMPLIANCE REQUIREMENTS
- Section 1306D — LIGHTING EFFICIENCY MEASURES
- Section 1307D — ENFORCEMENT
- Section 1308D — RULES
- Section 1309D — UNDERTAKING FOR THE GENERAL WELFARE
- Section 1310D — PREEMPTION
- Section 1311D — SEVERABILITY
- Section 1402 — PERFORMANCE REQUIREMENTS
- Section 1501 — GENERAL
- Section 1502 — ROOF DRAINAGE
- Section 1505 — FIRE CLASSIFICATION
- Section 1511 — ROOF TOP STRUCTURES
- Section 1604 — GENERAL DESIGN REQUIREMENTS
- Section 1607 — LIVE LOADS
- Section 1704 — SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPO…
- Section 1705 — REQUIRED SPECIAL INSPECTIONS AND TESTS
- Section 2304 — GENERAL CONSTRUCTION REQUIREMENTS
- Section 2405 — SLOPED GLAZING AND SKYLIGHTS
- Section 2603 — FOAM PLASTIC INSULATION
- Section 3010 — PRIVATE RESIDENCE ELEVATORS
- Section 3103 — TEMPORARY STRUCTURES
- Section 3107 — SIGNS
- Section 3116 — WOODBURNING APPLIANCES
- Section 3201 — GENERAL
- Section 3202 — ENCROACHMENTS
- Section 3203 — SIDEWALK CONSTRUCTION
- Section 3302 — CONSTRUCTION SAFEGUARDS
- Section 3303 — DEMOLITION
- Section 3304 — SITE WORK
- Section 3306 — PROTECTION OF PEDESTRIANS
- Section 3307 — PROTECTION OF ADJOINING PROPERTY
- Section 3311 — STANDPIPES
- Section J103 — PERMITS REQUIRED
- Section J104 — PERMIT APPLICATION AND SUBMITTALS
- Section J106 — EXCAVATIONS
- Section J109 — DRAINAGE AND TERRACING
- Section J112G — RADING FEES
- Section P101 — GENERAL
- Section P103 — EMERGENCY HOUSING
- Section P110 — EMERGENCY HOUSING FACILITIES SANITATION REQUIRE…
- Section P111 — EMERGENCY HOUSING FIRE AND LIFE SAFETY REQUIREM…
- Section P112 — ALTERNATIVES AND MODIFICATIONS
- 1604.4 Analysis. Any system or method of construction to be us…
- A401.1 Purpose
- A401.2 Scope. Omit.
- A403.1 General. All modifications required ... the building co…
- A403.2 Scope of analysis. This chapter requires the alteration…
- A403.3 Design base shear and design parameters. ... Despite an…
- A403.8 Horizontal diaphragms. The diaphragm immediately above …
- A405.1 New materials. New materials shall meet the requirement…
- 329.1 General.
- 329.2 Scope and Criteria
- 329.5 Voluntary Minimum Life-Safety Retrofit
- 10.1 Code-Based Site Classification
- 10.2 Ground Motion and Seismic Ground Deformation Characteriza…
- 10.3 Settlement Analysis
- 10.4 Sea Level Rise
- 10.5 Static and Seismic Design of Basement Walls
- 11.1 Driven Concrete and Steel Piles
- 11.2 Augered Cast-in-Place Piles
- 11.3 Drilled Shafts
- 13.1 Selection of Instrumentation and Monitoring Requirements
- 13.2 Pre-Construction Monitoring
- 13.3 Reporting
- 89.115 Add the following section:
- 89.115 Suppression. This code shall supersede all previous Ele…
- 89.116 Add the following section:
- 89.116 Maintenance. All electrical equipment, wiring and syste…
- 89.117 Add the following section:
- 89.117 Alternate Materials, Design and Methods of Construction.
- 89.118 Add the following section:
- 89.118 Change in Occupancy. Electrical equipment, wiring and s…
- 89.119 Add the following section:
- 89.119 Modifications. When there are practical difficulties in…
- 89.120 Add the following section:
- 89.120 Permits Required.
- 89.121 Add the following section:
- 89.121 Work Exempt from Permits. Electrical permits and fees s…
- 89.122 Add the following section:
- 89.122 Permit Issuance.
- 89.123 Add the following section:
- 89.123 Fees.
- 89.124 Add the following new section:
- 89.124 Powers and Duties of the Building Official.
- 89.125 Add the following section:
- 89.125 Violation. Any person, the owner or the owner’s authori…
- 89.126 Add the following section:
- 89.126 Unsafe Buildings or Structures. Any buildings, structur…
- 89.127 Add the following section:
- 89.127 Inspection.
- 89.128 Add the following section:
- 89.128 Survey. An electrical survey may be requested when an e…
- 89.129 Add the following section:
- 89.129 Board of Examiners. Application may be made to the Boar…
- 110.15 Revise this section as follows:
- 110.15 High-Leg Marking. On a 4-wire, delta-connected system w…
- 230.43 Revise this section as follows:
- 230.43 Wiring Methods for 1000 Volts, Nominal, or Less.
- 230.56 Revise this section as follows:
- 230.56 Service Conductor with the Higher Voltage to Ground. On…
- 230.71 Maximum Number of Disconnects.
- 250.50 Revise the first paragraph of this section as follows:
- 250.50 Grounding Electrode System. All grounding electrodes as…
- 300.37 Revise this section as follows:
- 300.37 Aboveground Wiring Methods. Aboveground conductors, 12K…
- 320.108 Revise this section as follows:
- 320.108 Equipment Grounding Conductor. Type AC cable shall pro…
- 330.12 Revise item (1) as follows:
- 330.12 Uses Not Permitted. Type MC cable shall not be used und…
- 330.108 Revise this section as follows:
- 330.108 Equipment Grounding Conductor. Where Type MC cable is …
- 334.10 Revise Item (2) as follows:
- 334.10 Uses permitted.
- 334.12 Add Items (11), (12) and (13) as follows:
- 334.12 Uses Not Permitted.
- 340.10 Revise Item (1) as follows:
- 340.10 Uses Permitted. Type UF cable shall be permitted as fol…
- 348.10 Revise this section as follows:
- 348.10 Uses Permitted. FMC shall be permitted to be used in [ …
- 350.10 Revise the first sentence as follows:
- 350.10 Uses Permitted. LFMC shall be permitted to be used [ ← …
- 352.10 Revise Item (A) as follows:
- 352.10 Uses Permitted. The use of PVC conduit shall be permitt…
- 355.10 Revise Item (A) as follows:
- 355.10 Uses Permitted. The use of RTRC shall be permitted in a…
- 356.10 Revise the first sentence of this section and item (5) …
- 356.10 Uses Permitted. LFNC shall be permitted to be used in e…
- 358.12 Add Item (3) as follows:
- 358.12 Uses Not Permitted. EMT shall not be used under the fol…
- 362.10 Revise Item 6 and delete Items 1, 2, 4, 5, 7, 8 and 9 a…
- 362.10 Uses Permitted. For the purpose of this article, the fi…
- 378.12 Add Item (6) as follows:
- 378.12 Uses Not Permitted. Nonmetallic wireways shall not be u…
- 411.5 Revise Section 411.5(A) as follows:
- 411.5 Specific Location Requirements.
- 760.46 Revise this section as follows:
- 760.46 NPLFA Circuit Wiring. Installation of non-power-limited…
- 760.180 Add the following new section:
- 760.180 System Requirements.
- Section 304 — STRUCTURAL DESIGN LOADS AND EVALUATION AND DESIGN
- Section 314 — EXISTING HIGH-RISE BUILDINGS [SFM]
- Section 324 — RESERVED
- Section 325 — RESERVED
- Section 326 — EXISTING BUILDINGS OR OTHER STRUCTURES LOCATED O…
- Section 327 — WORK PRACTICES FOR LEAD-BASED PAINT ON PRE-1979 …
- Section 328 — ASBESTOS INFORMATION AND NOTICE
- Section 329 — EARTHQUAKE EVALUATION OF PRIVATE SCHOOL STRUCTURES
- 405.2 Revise this section as follows:
- 405.2 Repairs to damaged buildings. Repairs to damaged buildin…
- Section 501 — GENERAL
- Section 502 — ADDITIONS
- Section 503 — ALTERATIONS
- Section 506 — CHANGE OF OCCUPANCY
- Section 508 — MOVED STRUCTURES
- Section 501B — PURPOSE
- Section 502B — SCOPE
- Section 503B — DEFINITIONS
- Section 504B — COMPLIANCE REQUIREMENTS
- Section 505B — ADMINISTRATION
- Section 506B — EXISTING UTILITY, FIRE PROTECTION, LIFE-SAFETY …
- Section 507B — ENERGY CONSERVATION
- Section 501C — PURPOSE
- Section 502C — SCOPE
- Section 503C — DEFINITIONS
- Section 504C — SYMBOLS AND NOTATIONS
- Section 505C — GENERAL REQUIREMENTS
- Section 506C — MATERIALS REQUIREMENTS
- Section 507C — QUALITY CONTROL
- Section 508C — ALLOWABLE DESIGN VALUES
- Section 509C — SELECTION OF PROCEDURE
- Section 510C — GENERAL PROCEDURE
- Section 511C — SPECIAL PROCEDURE
- Section 512C — ANALYSIS AND DESIGN
- Section 513C — DETAILED SYSTEM DESIGN REQUIREMENTS
- Section 514C — IN-PLACE MASONRY SHEAR TESTS
- Section 515C — TEST OF ANCHORS IN UNREINFORCED MASONRY WALLS
- Section 516C — POINTING OF UNREINFORCED MASONRY WALLS
- Section 501D — GENERAL
- Section 502D — CORRECTION OF HAZARDOUS PARAPETS AND APPENDAGES
- Section 503D — VARIANCE PROCEDURE
- Section 504D — UNREINFORCED MASONRY PARAPETS AND APPENDAGES
- Section 501E — PURPOSE AND INTENT
- Section 502E — SCOPE
- Section 503E — DEFINITIONS
- Section 504E — COMPLIANCE REQUIREMENTS
- Section 505E — PROGRAM IMPLEMENTATION AND ADMINISTRATION; FEE
- Section 506E — ENGINEERING CRITERIA FOR EVALUATION AND RETROFIT.
- Section 501F — GENERAL REQUIREMENTS AND SCOPE
- Section 502F — DEFINITIONS
- Section 503F — INSPECTION SCHEDULE
- Section 504F — FACADE INSPECTION AND MAINTENANCE CRITERIA AND …
- Section 505F — INSPECTION REPORTS.
- Section 506F — FEES
- Section 507F — COMPLIANCE, ENFORCEMENT AND ABATEMENT.
- 501G.1 Intent. This Chapter 5G is intended to advance public s…
- 501G.2 Definitions. In addition to the definitions in San Fran…
- 501G.3 Subject Buildings. The building inventory assessment re…
- 501G.4 Exemptions for Certain Concrete Buildings. Concrete Bui…
- 502G.1 Screening Process. The owner of each subject building s…
- 502G.2 Screening Form. Within six months of the effective date…
- 502G.3 Concrete Building Website. The Department shall maintai…
- Section 101 — GENERAL
- Section 202 — DEFINITIONS
- Section 301 — GENERAL
- Section 302 — MIXED OCCUPANCY BUILDINGS
- Section 303 — PHASED PROJECTS
- Section 304 — VOLUNTARY TIERS
- Section 305 — [OSHPD 1] – CALGREEN TIER 1 AND CALGREEN TIER 2
- Section 306 — [ ← ] – VOLUNTARY MEASURES
- Section 4.101 — GENERAL
- 4101.1 Revise the section as follows:
- Section 4.104 — [ ← ] HISTORIC PRESERVATION
- Section 4.105 — [ ← ] DEMOLITION OF EXISTING STRUCTURES
- Section 4.106 — SITE DEVELOPMENT
- Section 4.201 — GENERAL
- Section 5.101 — GENERAL
- Section 5.103 — [ ← ] – REQUIREMENTS FOR GROUP A, B, I, E and …
- Section 5.104 — [ ← ] – HISTORIC PRESERVATION
- Section 5.105 — [ ← ] DEMOLITION OF EXISTING STRUCTURES
- Section 5.106 — SITE DEVELOPMENT
- Section 5.201 — GENERAL
- Section 701 — GENERAL
- Section 702 — QUALIFICATIONS
- 703.1 Modify the section as follows:
- 703.1 Documentation. Documentation used to show compliance wit…
- Section 101.0 — TITLE
- 101.1 Revise this section as follows:
- 101.1 Title. This document shall be known as the [ ← ] 2022 Sa…
- Section 103.0 — DUTIES AND POWERS OF THE AUTHORITY HAVING JURI…
- 103.1 Revise the first paragraph as follows:
- 103.1 General. The Authority Having Jurisdiction shall be the …
- 103.4 Revise the first paragraph as follows:
- 103.4 Right of Entry. [ ← ] When it is necessary to make an in…
- 103.5 Add the following section:
- 103.5 Authority Having Jurisdiction May Adopt Rules and Regula…
- 103.6 Add the following section:
- 103.6 Code Revisions. The Authority Having Jurisdiction shall …
- Section 104.0 — PERMITS
- 104.2 Add item (6) as follows:
- 104.3 Replace this section as follows:
- 104.3 Application for Permit. [ ← ] Applications for permits t…
- 104.4 Replace this section as follows:
- 104.4 Permit Issuance. [ ← ] Permit processing and issuance fo…
- 104.5 Replace this entire section including subsections with t…
- Section 106.0 — VIOLATIONS AND PENALTIES
- 106.0 Add the following three sections:
- 106.7 Violations. Any person, the owner or the owner’s authori…
- 106.8 Any person, the owner or the owner’s authorized agent, w…
- 106.9 It shall be unlawful for any person to interfere with th…
- Section 107.0 — BOARD OF APPEALS
- 107.0 Replace this title and entire section as follows:
- 107.0 [ ← ] Board of Examiners. Applicants may appeal decision…
- Section 302.2 — ALTERNATE MATERIALS AND METHODS OF CONSTRUCTION
- Section 504.3 — DOMESTIC RANGE
- 504.3 Add a second paragraph as follows:
- Section 802.2 — CONNECTION TO VENTING SYSTEMS
- Section 802.6 — GAS VENTS
- Section 802.8 — THROUGH-THE-WALL VENT TERMINATIONS
- 802.8 Revise the first sentence of this section and add an exc…
- 802.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- Section 925.0 — INCINERATORS AND CREMATORIES
- 925.1 Add the following sentence as a second paragraph:
- Section 1013.0 — INSPECTIONS AND TESTS
- 1013.1 Revise this section as follows:
- 1013.1 General. An installation for which a permit is required…
- 1013.2 Revise this section as follows:
- 1013.2 Operating Permit.
- 1013.3 Revise this section as follows:
- 1013.3 Maintenance Inspection. The Authority Having Jurisdicti…
- 1013.7 Revise the second paragraph as follows:
- Section 101.0 — GENERAL
- 101.1 Revise this section as follows:
- 101.1 Title. This document shall be known as the “ [ ← ] 2022 …
- Section 103.0 — DUTIES AND POWERS OF THE AUTHORITY HAVING JURI…
- 103.1 Replace the third paragraph with the following:
- 103.4 Revise the first paragraph of this section as follows:
- 103.4 Right of Entry. Where it is necessary to make an inspect…
- 103.5 Add the following section:
- 103.5 Rules and Regulations. The Authority Having Jurisdiction…
- 103.6 Add the following section:
- 103.6 Code Revisions. The Authority Having Jurisdiction shall …
- 103.7 Add the following section:
- 103.7 Modifications. When there are practical difficulties inv…
- Section 104.0 — PERMITS
- 104.1 Add the following as the second paragraph of this section:
- 104.2 Replace Section 104.2(1) and the first paragraph of Sect…
- 104.2 Exempt Work. A permit shall not be required for the foll…
- 104.3 Replace this section as follows:
- 104.3 Application for Permit. [ ← ] Permit applicants shall fi…
- 104.4 Add a new second paragraph to this section as follows:
- 104.5 Replace this section as follows:
- 104.5 Permit Fees. [ ← ] Before any permit is issued, the appl…
- Section 105.0 — INSPECTIONS AND TESTING
- Section 106.0 — VIOLATIONS AND PENALTIES
- 106.3 Replace this section as follows:
- 106.3 Penalties. [ ← ] Any person, the owner or the owner’s au…
- 106.5 Revise this section as follows:
- 106.5 Authority to Disconnect Utilities in Emergencies. The Au…
- Section 107.0 — BOARD OF APPEALS
- 107.0 Replace this title and the entire section as follows:
- Section 108.0 — ABATEMENT OF PUBLIC NUISANCE
- 108.0 Abatement of Public Nuisance. In order to abate a nuisan…
- Section 109.0 — REPAIRS TO DEFECTIVE BUILDING SEWERS
- 109.0 Repairs to Defective Building Sewers
- 109.1 General. Any defective building sewer found to be a nuis…
- 109.2 Cost of Repairs by City and County of San Francisco. Whe…
- 109.3 Plumbing Building Sewer Revolving Fund. A special revolv…
- 109.4 Assessment for Costs. The Authority Having Jurisdiction …
- Section 201.0 — GENERAL
- 201.1 Add the following to the end of the first sentence:
- Section 204.0 — B
- 204.0 Add the following definition:
- Section 208.0 — F
- 208.0 Add the following definition:
- Section 216.0 — N
- Section 218.0 — P
- 218.0 Revise this definition as follows:
- Section 221.0 — S
- 221.0 Add the following definition:
- Section 313.0 — HANGERS AND SUPPORTS
- 313.9 Add the following section:
- 313.9 Materials.
- Section 405 — PROHIBITED FIXTURES
- Section 415.0 — DRINKING FOUNTAINS
- 415.2 Add the following section:
- Section 504.0 — WATER HEATER REQUIREMENTS
- 504.1 Add the following as the first paragraph of this section:
- 504.1 Location. Water Heaters mounted on the exterior of a bui…
- Section 603.0 — CROSS-CONNECTION CONTROL
- 603.1 Add a third paragraph to this section as follows:
- 603.2 Revise Table 603.2 as follows:
- Section 604.0 — MATERIALS
- 604.1 Add the following sentence to the end of the second para…
- Section 606.0 — VALVES
- 606.2 Revise this section as follows:
- 606.2 Fullway Valve. A fullway valve controlling outlets shall…
- 606.3 Revise this section as follows:
- 606.3 Multidwelling Units. In multidwelling units, one or more…
- 606.5 Revise this section as follows:
- 606.5 Control Valve. A control valve shall be installed immedi…
- 606.11 Add the following section:
- 606.11 Backflow Assembly. All buildings four stories or more i…
- Section 609.0 — INSTALLATION, TESTING, UNIONS AND LOCATION
- Section 701.0 — GENERAL
- Section 706.0 — CHANGES IN DIRECTION OF DRAINAGE FLOW
- 706.4 Revise this section as follows:
- 706.4 Vertical to Horizontal. Vertical drainage lines connecti…
- Section 710.0 — DRAINAGE OF FIXTURES LOCATED BELOW THE NEXT UP…
- Section 901.0 — GENERAL
- 901.1 Add the following second paragraph to this section:
- Section 907.0 — VENT STACKS AND RELIEF VENTS
- 907.1 Revise the first sentence of this section as follows:
- 907.1 Drainage Stack. Each drainage stack that extends [ ← ] s…
- 907.3 Add the following section:
- 907.3 Vent Stacks and Relief Vents. Every building in which pl…
- Section 911.0 — CIRCUIT VENTING
- 911.0 Revise this section as follows:
- 911.0 Circuit Venting. Circuit venting is not permitted unless…
- 1001.3 Add the following section:
- 1001.3 Placement and Minimum Size of Building Traps. The build…
- Section 1008.0 — BUILDING TRAPS
- 1008.1 Revise this section as follows:
- 1008.1 General. Building traps shall not be installed except w…
- Section 1016.0 — SAND INTERCEPTORS
- 1016.3 Add the following section:
- Section 1101.0 — GENERAL
- Section 1208.0 — GAS PIPING SYSTEM DESIGN, MATERIALS, AND COMP…