313.3 Suspended Piping — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 313.3 · Effective January 1, 2026 · Official source: Building Standards Commission

Suspended piping shall be supported at intervals not to exceed those shown in Table 313.3. TABLE 313.3

HANGERS AND SUPPORTS

MATERIALS TYPES OF JOINTS HORIZONTAL VERTICAL
Cast Lead and Oakum 5 feet, except 10 feet where 10 foot
lengths are installed1, 2, 3
Base and each floor,
not to exceed 15 feet
Cast Compression Gasket Every other joint, unless over 4 feet
then support each joint1, 2, 3
Base and each floor,
not to exceed 15 feet
Cast-Iron Hubless Shielded Coupling Every other joint, unless over 4 feet
then support each joint1,2,3,4
Base and each floor,
not to exceed 15 feet
Copper & Copper
Alloys
Soldered, Brazed, Threaded, or
Mechanical
11⁄2 inches and smaller, 6 feet;
2 inches and larger, 10 feet
Each floor, not to exceed 10 feet5
Steel Pipe for Water or
DWV
Threaded or Welded 3⁄4 inch and smaller, 10 feet;
1 inch and larger, 12 feet
Every other floor,
not to exceed 25 feet5
Steel Pipe for Gas Threaded or Welded 1⁄2 inch, 6 feet;3⁄4 inch and 1 inch,
8 feet; 11⁄4 inches and larger, 10 feet
1⁄2 inch, 6 feet;3⁄4 inch and 1 inch,
8 feet; 11⁄4 inches every floor level
Schedule 40 PVC and
ABS DWV
Solvent Cemented All sizes, 4 feet; allow
for expansion every 30 feet3
Base and each floor; provide
mid-story guides; provide
for expansion every 30 feet
CPVC Solvent Cemented 1 inch and smaller, 3 feet;
11⁄4 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
CPVC-AL-CPVC Solvent Cemented 1⁄2 inch, 5 feet;3⁄4 inch, 65 inches;
1 inch, 6 feet
Base and each floor;
provide mid-story guides
Lead Wiped or Burned Continuous Support Not to exceed 4 feet
Steel Mechanical In accordance with standards acceptable to the Authority Having Jurisdiction In accordance with standards acceptable to the Authority Having Jurisdiction
PEX Cold Expansion, Insert
and Compression
1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
PEX-AL-PEX Metal Insert and Metal
Compression
1⁄2 inch
3⁄4 inch
1 inch } All sizes 98 inches
Base and each floor;
provide mid-story guides
PE-AL-PE Metal Insert and Metal
Compression
1⁄2 inch
3⁄4 inch
1 inch } All sizes 98 inches
Base and each floor;
provide mid-story guides
PE-RT Insert and Compression 1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
Polypropylene (PP) Fusion weld (socket, butt, sad-
dle, electrofusion), threaded
(metal threads only), or
mechanical
1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet
Base and each floor;
provide mid-story guides

For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm

Notes: 1 Support adjacent to joint, not to exceed 18 inches (457 mm). 2 Brace not to exceed 40 foot (12 192 mm) intervals to prevent horizontal movement. 3 Support at each horizontal branch connection. 4 Hangers shall not be placed on the coupling. 5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansion and contraction, where first approved by the Authority Having Jurisdiction.