Chapter 3 — GENERAL REGULATIONS
313.3 Suspended Piping — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 313.3 · Effective January 1, 2026 · Official source: Building Standards Commission
Suspended piping shall be supported at intervals not to exceed those shown in Table 313.3. TABLE 313.3
HANGERS AND SUPPORTS
| MATERIALS | TYPES OF JOINTS | HORIZONTAL | VERTICAL |
|---|---|---|---|
| Cast | Lead and Oakum | 5 feet, except 10 feet where 10 foot lengths are installed1, 2, 3 |
Base and each floor, not to exceed 15 feet |
| Cast | Compression Gasket | Every other joint, unless over 4 feet then support each joint1, 2, 3 |
Base and each floor, not to exceed 15 feet |
| Cast-Iron Hubless | Shielded Coupling | Every other joint, unless over 4 feet then support each joint1,2,3,4 |
Base and each floor, not to exceed 15 feet |
| Copper & Copper Alloys |
Soldered, Brazed, Threaded, or Mechanical |
11⁄2 inches and smaller, 6 feet; 2 inches and larger, 10 feet |
Each floor, not to exceed 10 feet5 |
| Steel Pipe for Water or DWV |
Threaded or Welded | 3⁄4 inch and smaller, 10 feet; 1 inch and larger, 12 feet |
Every other floor, not to exceed 25 feet5 |
| Steel Pipe for Gas | Threaded or Welded | 1⁄2 inch, 6 feet;3⁄4 inch and 1 inch, 8 feet; 11⁄4 inches and larger, 10 feet |
1⁄2 inch, 6 feet;3⁄4 inch and 1 inch, 8 feet; 11⁄4 inches every floor level |
| Schedule 40 PVC and ABS DWV |
Solvent Cemented | All sizes, 4 feet; allow for expansion every 30 feet3 |
Base and each floor; provide mid-story guides; provide for expansion every 30 feet |
| CPVC | Solvent Cemented | 1 inch and smaller, 3 feet; 11⁄4 inches and larger, 4 feet |
Base and each floor; provide mid-story guides |
| CPVC-AL-CPVC | Solvent Cemented | 1⁄2 inch, 5 feet;3⁄4 inch, 65 inches; 1 inch, 6 feet |
Base and each floor; provide mid-story guides |
| Lead | Wiped or Burned | Continuous Support | Not to exceed 4 feet |
| Steel | Mechanical | In accordance with standards acceptable to the Authority Having Jurisdiction | In accordance with standards acceptable to the Authority Having Jurisdiction |
| PEX | Cold Expansion, Insert and Compression |
1 inch and smaller, 32 inches; 11⁄4 inches and larger, 4 feet |
Base and each floor; provide mid-story guides |
| PEX-AL-PEX | Metal Insert and Metal Compression |
1⁄2 inch 3⁄4 inch 1 inch } All sizes 98 inches |
Base and each floor; provide mid-story guides |
| PE-AL-PE | Metal Insert and Metal Compression |
1⁄2 inch 3⁄4 inch 1 inch } All sizes 98 inches |
Base and each floor; provide mid-story guides |
| PE-RT | Insert and Compression | 1 inch and smaller, 32 inches; 11⁄4 inches and larger, 4 feet |
Base and each floor; provide mid-story guides |
| Polypropylene (PP) | Fusion weld (socket, butt, sad- dle, electrofusion), threaded (metal threads only), or mechanical |
1 inch and smaller, 32 inches; 11⁄4 inches and larger, 4 feet |
Base and each floor; provide mid-story guides |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
Notes: 1 Support adjacent to joint, not to exceed 18 inches (457 mm). 2 Brace not to exceed 40 foot (12 192 mm) intervals to prevent horizontal movement. 3 Support at each horizontal branch connection. 4 Hangers shall not be placed on the coupling. 5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansion and contraction, where first approved by the Authority Having Jurisdiction.
Continue researching
Related topics
State and federal sources. Edit the document title or filters, then run your search.
Get a plain-English answer with a citation back to this text.
Ask AI about this code