Section 506C — MATERIALS REQUIREMENTS
506C.3 Existing Unreinforced Masonry Walls.
San Francisco Building Inspection Commission Codes · 2022 edition · updated 2026-07-25 · San Francisco
506C.3.1 General. All unreinforced masonry walls utilized to carry vertical loads or seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this section. All masonry that does not meet the minimum standards established by this chapter shall be removed and replaced with new materials, repaired or alternatively shall have its structural functions replaced with new materials and shall be anchored to supporting elements.
506C.3.2 Construction (lay-up) of walls.
506C.3.2.1 Multi-wythe solid brick. The facing and backing shall be bonded so that not less than 10 percent of the exposed face area is composed of solid headers extending not less than 4 inches (101.6 mm) into the backing. The clear distance between adjacent full-length headers shall not exceed 24 inches (609.6 mm) vertically or horizontally. Where the backing consists of two or more wythes, the headers shall extend not less than 4 inches (101.6 mm) into the most distant wythe or the backing wythes shall be bonded together with separate headers whose area and spacing conform to the foregoing. Wythes of walls not bonded as described above shall be considered as veneer. Veneer wythes shall not be included in the effective thickness used in calculating the height to thickness and the shear capacity of the wall.
506C.3.2.2 Grouted or ungrouted hollow concrete or clay block and structural hollow clay tile. These materials shall be laid in a running bond pattern.
Other lay-up patterns may be acceptable if their performance can be justified as being at least equal to those specified above.
506C.3.3 Mortar.
506C.3.3.1 Tests. The quality of mortar in all masonry walls shall be determined by performing in-place shear tests in accordance with Section 514C. Alternative methods of testing may be approved by the Building Official for masonry walls other than brick.
506C.3.3.2 Location of tests. The shear tests shall be taken at locations representative of the mortar conditions throughout the entire building, taking into account variations in workmanship at different building height levels, variations in weathering of the exterior surfaces, and variations in the condition of the interior surfaces due to deterioration caused by leaks and condensation of water and/or by the deleterious effects of other substances
contained within the building. The exact test locations shall be determined at the building site by the engineer or architect in responsible charge of the structural design work. An accurate record of all such tests and their location in the building shall be recorded, and these results shall be submitted to the Department for approval as part of the structural analysis.
506C.3.3.3 Number of tests. The minimum number of tests per class shall be as follows:
At each of both the first and top stories, not less than two tests per wall or line of wall elements providing a common line of resistance to lateral forces.
At each of all other stories, not less than one test per wall or line of wall elements providing a common line of resistance to lateral forces.
In any case, not less than one test per 1,500 square feet (139.355 m [2] ) of wall surface nor less than a total of eight tests.
506C.3.3.4 Minimum quality of mortar.
- Mortar shear test values, vto, in psi shall be obtained for each in-place shear test in accordance with the following equation:
vto = (Vtest/Ab) - PD+L (5C-1)
The mortar shear strength, vt, is the value in psi that, after discarding the lowest 20 percent of the mortar shear test values, vto, is the lowest of the remaining 80 percent of the mortar shear test values.
Any unreinforced masonry bearing wall with vto, or with mortar shear strength, vt, less than 30 psi (206.84 kPa) shall be either removed, entirely pointed and retested or have its structural function replaced and shall be anchored to supporting elements in accordance with Section 506C.3.1 and Section 513C.8. When existing mortar in any wythe is pointed to increase its shear strength and retested, the condition of the mortar in the adjacent bed joints of the inner wythe or wythes and the opposite outer wythe shall be examined for extent of deterioration. The shear strength of any wall class shall be no greater than that of the weakest wythe of that class.
506C.3.3.5 Collar joints. The collar joints shall be inspected at the test locations during each in-place shear test, and estimates of the percentage of the surfaces of adjacent wythes which are covered with mortar shall be reported along with the results of the in-place shear tests.
506C.3.3.6 Unreinforced masonry classes. All existing unreinforced masonry shall be categorized into one or more classes based on quality of construction, state of repair, deterioration and weathering. A class shall be characterized by the allowable masonry shear stress determined in accordance with Section 508C.2. Classes shall be defined for whole walls, not for small areas of masonry within a wall.
506C.3.3.7 Pointing. All deteriorated mortar joints in unreinforced masonry bearing walls shall be pointed according to Section 516C. Nothing shall
p re vent pointing of any deteriorated masonry wall joints before the tests are made, except as required in Section 507C.1.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — San Francisco Building Inspection Commission Codes
- Section 101A — TITLE, SCOPE AND GENERAL
- Section 102A — UNSAFE BUILDINGS, STRUCTURES OR PROPERTY
- Section 103A — VIOLATIONS
- Section 104A — ORGANIZATION AND ENFORCEMENT
- Section 105A — BOARDS, COMMISSIONS, AND COMMITTEES
- Section 106A — PERMITS
- Section 107A — FEES
- Section 108A — INSPECTIONS
- Section 109A — CERTIFICATE OF OCCUPANCY; AMENDED CERTIFICATE O…
- Section 110A — SCHEDULE OF FEE TABLES
- Section 111A — ADAPTIVE REUSE
- Section 202 — DEFINITIONS
- Section 406 — MOTOR-VEHICLE-RELATED OCCUPANCIES
- Section 435 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FAC…
- Section 456 — FENCES
- Section 707 — FIRE BARRIERS
- Section 901 — GENERAL
- Section 903 — AUTOMATIC SPRINKLER SYSTEMS
- Section 905 — STANDPIPE SYSTEMS
- Section 907 — FIRE ALARM AND DETECTION SYSTEMS
- Section 912 — FIRE DEPARTMENT CONNECTIONS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1001A — SCOPE
- Section 1002A — DEFINITIONS
- Section 1003A — GENERAL REQUIREMENTS FOR SECURITY
- Section 1004A — SPECIAL HOTEL AND MOTEL SECURITY REQUIREMENTS
- Section 1005A — SPECIAL APARTMENT HOUSE AND CONDOMINIUM SECURITY
- Section 1101D — SCOPE
- Section 1102D — DEFINITIONS
- Section 1103D — DEPARTMENT COORDINATION
- Section 1104D — DISABILITY ACCESS COMPLIANCE UNIT
- Section 1105D — REPORTS TO THE MAYOR’S OFFICE ON DISABILITY AN…
- Section 1106D — NOTICE
- Section 1107D — [REPEALED]
- Section 1108D — [REPEALED]
- Section 1109D — [REPEALED]
- Section 1110D — [REPEALED]
- Section 1111D — [REPEALED]
- Section 1112D — [REPEALED]
- Section 1113D — [REPEALED]
- Section 1114D — [REPEALED]
- Section 1202 — VENTILATION
- Section 1204 — LIGHTING
- Section 1206 — SOUND TRANSMISSION
- 1208.4 Revise paragraph 1 of this section and add paragraphs 5…
- Section 1210 — [ ← ] TOILET, BATHROOM AND LACTATION ROOM REQUI…
- Section 1301A — TITLE
- Section 1302A — INTENT
- Section 1303A — DEFINITIONS
- Section 1304A — RULES AND GUIDELINES
- Section 1305A — CIVIL REMEDIES
- Section 1306A — REQUIREMENTS
- Section 1307A — INFORMATIONAL BROCHURE
- Section 1308A — POSTPONEMENTS OF REQUIREMENTS
- Section 1309A — EARLY COMPLIANCE WITH WATER CONSERVATION MEASU…
- Section 1310A — WATER CONSERVATION INSPECTIONS
- Section 1311A — PROOF OF COMPLIANCE WITH WATER CONSERVATION ME…
- Section 1312A — APPEALS FROM RESULTS OF A WATER CONSERVATION I…
- Section 1313A — REQUIRED WATER CONSERVATION MEASURES
- Section 1314A — WATER CONSERVATION INSPECTIONS
- Section 1301B — TITLE
- Section 1302B — RECOVERY OF CONSTRUCTION AND DEMOLITION DEBRIS
- Section 1303B — DEFINITIONS
- Section 1304B — PERMIT CONDITION
- Section 1305B — PERMIT NOTIFICATION
- Section 1301D — TITLE
- Section 1302D — PURPOSE
- Section 1303D — SCOPE
- Section 1304D — DEFINITIONS
- Section 1305D — COMPLIANCE REQUIREMENTS
- Section 1306D — LIGHTING EFFICIENCY MEASURES
- Section 1307D — ENFORCEMENT
- Section 1308D — RULES
- Section 1309D — UNDERTAKING FOR THE GENERAL WELFARE
- Section 1310D — PREEMPTION
- Section 1311D — SEVERABILITY
- Section 1402 — PERFORMANCE REQUIREMENTS
- Section 1501 — GENERAL
- Section 1502 — ROOF DRAINAGE
- Section 1505 — FIRE CLASSIFICATION
- Section 1511 — ROOF TOP STRUCTURES
- Section 1604 — GENERAL DESIGN REQUIREMENTS
- Section 1607 — LIVE LOADS
- Section 1704 — SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPO…
- Section 1705 — REQUIRED SPECIAL INSPECTIONS AND TESTS
- Section 2304 — GENERAL CONSTRUCTION REQUIREMENTS
- Section 2405 — SLOPED GLAZING AND SKYLIGHTS
- Section 2603 — FOAM PLASTIC INSULATION
- Section 3010 — PRIVATE RESIDENCE ELEVATORS
- Section 3103 — TEMPORARY STRUCTURES
- Section 3107 — SIGNS
- Section 3116 — WOODBURNING APPLIANCES
- Section 3201 — GENERAL
- Section 3202 — ENCROACHMENTS
- Section 3203 — SIDEWALK CONSTRUCTION
- Section 3302 — CONSTRUCTION SAFEGUARDS
- Section 3303 — DEMOLITION
- Section 3304 — SITE WORK
- Section 3306 — PROTECTION OF PEDESTRIANS
- Section 3307 — PROTECTION OF ADJOINING PROPERTY
- Section 3311 — STANDPIPES
- Section J103 — PERMITS REQUIRED
- Section J104 — PERMIT APPLICATION AND SUBMITTALS
- Section J106 — EXCAVATIONS
- Section J109 — DRAINAGE AND TERRACING
- Section J112G — RADING FEES
- Section P101 — GENERAL
- Section P103 — EMERGENCY HOUSING
- Section P110 — EMERGENCY HOUSING FACILITIES SANITATION REQUIRE…
- Section P111 — EMERGENCY HOUSING FIRE AND LIFE SAFETY REQUIREM…
- Section P112 — ALTERNATIVES AND MODIFICATIONS
- 1604.4 Analysis. Any system or method of construction to be us…
- A401.1 Purpose
- A401.2 Scope. Omit.
- A403.1 General. All modifications required ... the building co…
- A403.2 Scope of analysis. This chapter requires the alteration…
- A403.3 Design base shear and design parameters. ... Despite an…
- A403.8 Horizontal diaphragms. The diaphragm immediately above …
- A405.1 New materials. New materials shall meet the requirement…
- 329.1 General.
- 329.2 Scope and Criteria
- 329.5 Voluntary Minimum Life-Safety Retrofit
- 10.1 Code-Based Site Classification
- 10.2 Ground Motion and Seismic Ground Deformation Characteriza…
- 10.3 Settlement Analysis
- 10.4 Sea Level Rise
- 10.5 Static and Seismic Design of Basement Walls
- 11.1 Driven Concrete and Steel Piles
- 11.2 Augered Cast-in-Place Piles
- 11.3 Drilled Shafts
- 13.1 Selection of Instrumentation and Monitoring Requirements
- 13.2 Pre-Construction Monitoring
- 13.3 Reporting
- 89.115 Add the following section:
- 89.115 Suppression. This code shall supersede all previous Ele…
- 89.116 Add the following section:
- 89.116 Maintenance. All electrical equipment, wiring and syste…
- 89.117 Add the following section:
- 89.117 Alternate Materials, Design and Methods of Construction.
- 89.118 Add the following section:
- 89.118 Change in Occupancy. Electrical equipment, wiring and s…
- 89.119 Add the following section:
- 89.119 Modifications. When there are practical difficulties in…
- 89.120 Add the following section:
- 89.120 Permits Required.
- 89.121 Add the following section:
- 89.121 Work Exempt from Permits. Electrical permits and fees s…
- 89.122 Add the following section:
- 89.122 Permit Issuance.
- 89.123 Add the following section:
- 89.123 Fees.
- 89.124 Add the following new section:
- 89.124 Powers and Duties of the Building Official.
- 89.125 Add the following section:
- 89.125 Violation. Any person, the owner or the owner’s authori…
- 89.126 Add the following section:
- 89.126 Unsafe Buildings or Structures. Any buildings, structur…
- 89.127 Add the following section:
- 89.127 Inspection.
- 89.128 Add the following section:
- 89.128 Survey. An electrical survey may be requested when an e…
- 89.129 Add the following section:
- 89.129 Board of Examiners. Application may be made to the Boar…
- 110.15 Revise this section as follows:
- 110.15 High-Leg Marking. On a 4-wire, delta-connected system w…
- 230.43 Revise this section as follows:
- 230.43 Wiring Methods for 1000 Volts, Nominal, or Less.
- 230.56 Revise this section as follows:
- 230.56 Service Conductor with the Higher Voltage to Ground. On…
- 230.71 Maximum Number of Disconnects.
- 250.50 Revise the first paragraph of this section as follows:
- 250.50 Grounding Electrode System. All grounding electrodes as…
- 300.37 Revise this section as follows:
- 300.37 Aboveground Wiring Methods. Aboveground conductors, 12K…
- 320.108 Revise this section as follows:
- 320.108 Equipment Grounding Conductor. Type AC cable shall pro…
- 330.12 Revise item (1) as follows:
- 330.12 Uses Not Permitted. Type MC cable shall not be used und…
- 330.108 Revise this section as follows:
- 330.108 Equipment Grounding Conductor. Where Type MC cable is …
- 334.10 Revise Item (2) as follows:
- 334.10 Uses permitted.
- 334.12 Add Items (11), (12) and (13) as follows:
- 334.12 Uses Not Permitted.
- 340.10 Revise Item (1) as follows:
- 340.10 Uses Permitted. Type UF cable shall be permitted as fol…
- 348.10 Revise this section as follows:
- 348.10 Uses Permitted. FMC shall be permitted to be used in [ …
- 350.10 Revise the first sentence as follows:
- 350.10 Uses Permitted. LFMC shall be permitted to be used [ ← …
- 352.10 Revise Item (A) as follows:
- 352.10 Uses Permitted. The use of PVC conduit shall be permitt…
- 355.10 Revise Item (A) as follows:
- 355.10 Uses Permitted. The use of RTRC shall be permitted in a…
- 356.10 Revise the first sentence of this section and item (5) …
- 356.10 Uses Permitted. LFNC shall be permitted to be used in e…
- 358.12 Add Item (3) as follows:
- 358.12 Uses Not Permitted. EMT shall not be used under the fol…
- 362.10 Revise Item 6 and delete Items 1, 2, 4, 5, 7, 8 and 9 a…
- 362.10 Uses Permitted. For the purpose of this article, the fi…
- 378.12 Add Item (6) as follows:
- 378.12 Uses Not Permitted. Nonmetallic wireways shall not be u…
- 411.5 Revise Section 411.5(A) as follows:
- 411.5 Specific Location Requirements.
- 760.46 Revise this section as follows:
- 760.46 NPLFA Circuit Wiring. Installation of non-power-limited…
- 760.180 Add the following new section:
- 760.180 System Requirements.
- Section 304 — STRUCTURAL DESIGN LOADS AND EVALUATION AND DESIGN
- Section 314 — EXISTING HIGH-RISE BUILDINGS [SFM]
- Section 324 — RESERVED
- Section 325 — RESERVED
- Section 326 — EXISTING BUILDINGS OR OTHER STRUCTURES LOCATED O…
- Section 327 — WORK PRACTICES FOR LEAD-BASED PAINT ON PRE-1979 …
- Section 328 — ASBESTOS INFORMATION AND NOTICE
- Section 329 — EARTHQUAKE EVALUATION OF PRIVATE SCHOOL STRUCTURES
- 405.2 Revise this section as follows:
- 405.2 Repairs to damaged buildings. Repairs to damaged buildin…
- Section 501 — GENERAL
- Section 502 — ADDITIONS
- Section 503 — ALTERATIONS
- Section 506 — CHANGE OF OCCUPANCY
- Section 508 — MOVED STRUCTURES
- Section 501B — PURPOSE
- Section 502B — SCOPE
- Section 503B — DEFINITIONS
- Section 504B — COMPLIANCE REQUIREMENTS
- Section 505B — ADMINISTRATION
- Section 506B — EXISTING UTILITY, FIRE PROTECTION, LIFE-SAFETY …
- Section 507B — ENERGY CONSERVATION
- Section 501C — PURPOSE
- Section 502C — SCOPE
- Section 503C — DEFINITIONS
- Section 504C — SYMBOLS AND NOTATIONS
- Section 505C — GENERAL REQUIREMENTS
- Section 507C — QUALITY CONTROL
- Section 508C — ALLOWABLE DESIGN VALUES
- Section 509C — SELECTION OF PROCEDURE
- Section 510C — GENERAL PROCEDURE
- Section 511C — SPECIAL PROCEDURE
- Section 512C — ANALYSIS AND DESIGN
- Section 513C — DETAILED SYSTEM DESIGN REQUIREMENTS
- Section 514C — IN-PLACE MASONRY SHEAR TESTS
- Section 515C — TEST OF ANCHORS IN UNREINFORCED MASONRY WALLS
- Section 516C — POINTING OF UNREINFORCED MASONRY WALLS
- Section 501D — GENERAL
- Section 502D — CORRECTION OF HAZARDOUS PARAPETS AND APPENDAGES
- Section 503D — VARIANCE PROCEDURE
- Section 504D — UNREINFORCED MASONRY PARAPETS AND APPENDAGES
- Section 501E — PURPOSE AND INTENT
- Section 502E — SCOPE
- Section 503E — DEFINITIONS
- Section 504E — COMPLIANCE REQUIREMENTS
- Section 505E — PROGRAM IMPLEMENTATION AND ADMINISTRATION; FEE
- Section 506E — ENGINEERING CRITERIA FOR EVALUATION AND RETROFIT.
- Section 501F — GENERAL REQUIREMENTS AND SCOPE
- Section 502F — DEFINITIONS
- Section 503F — INSPECTION SCHEDULE
- Section 504F — FACADE INSPECTION AND MAINTENANCE CRITERIA AND …
- Section 505F — INSPECTION REPORTS.
- Section 506F — FEES
- Section 507F — COMPLIANCE, ENFORCEMENT AND ABATEMENT.
- 501G.1 Intent. This Chapter 5G is intended to advance public s…
- 501G.2 Definitions. In addition to the definitions in San Fran…
- 501G.3 Subject Buildings. The building inventory assessment re…
- 501G.4 Exemptions for Certain Concrete Buildings. Concrete Bui…
- 502G.1 Screening Process. The owner of each subject building s…
- 502G.2 Screening Form. Within six months of the effective date…
- 502G.3 Concrete Building Website. The Department shall maintai…
- Section 101 — GENERAL
- Section 202 — DEFINITIONS
- Section 301 — GENERAL
- Section 302 — MIXED OCCUPANCY BUILDINGS
- Section 303 — PHASED PROJECTS
- Section 304 — VOLUNTARY TIERS
- Section 305 — [OSHPD 1] – CALGREEN TIER 1 AND CALGREEN TIER 2
- Section 306 — [ ← ] – VOLUNTARY MEASURES
- Section 4.101 — GENERAL
- 4101.1 Revise the section as follows:
- Section 4.104 — [ ← ] HISTORIC PRESERVATION
- Section 4.105 — [ ← ] DEMOLITION OF EXISTING STRUCTURES
- Section 4.106 — SITE DEVELOPMENT
- Section 4.201 — GENERAL
- Section 5.101 — GENERAL
- Section 5.103 — [ ← ] – REQUIREMENTS FOR GROUP A, B, I, E and …
- Section 5.104 — [ ← ] – HISTORIC PRESERVATION
- Section 5.105 — [ ← ] DEMOLITION OF EXISTING STRUCTURES
- Section 5.106 — SITE DEVELOPMENT
- Section 5.201 — GENERAL
- Section 701 — GENERAL
- Section 702 — QUALIFICATIONS
- 703.1 Modify the section as follows:
- 703.1 Documentation. Documentation used to show compliance wit…
- Section 101.0 — TITLE
- 101.1 Revise this section as follows:
- 101.1 Title. This document shall be known as the [ ← ] 2022 Sa…
- Section 103.0 — DUTIES AND POWERS OF THE AUTHORITY HAVING JURI…
- 103.1 Revise the first paragraph as follows:
- 103.1 General. The Authority Having Jurisdiction shall be the …
- 103.4 Revise the first paragraph as follows:
- 103.4 Right of Entry. [ ← ] When it is necessary to make an in…
- 103.5 Add the following section:
- 103.5 Authority Having Jurisdiction May Adopt Rules and Regula…
- 103.6 Add the following section:
- 103.6 Code Revisions. The Authority Having Jurisdiction shall …
- Section 104.0 — PERMITS
- 104.2 Add item (6) as follows:
- 104.3 Replace this section as follows:
- 104.3 Application for Permit. [ ← ] Applications for permits t…
- 104.4 Replace this section as follows:
- 104.4 Permit Issuance. [ ← ] Permit processing and issuance fo…
- 104.5 Replace this entire section including subsections with t…
- Section 106.0 — VIOLATIONS AND PENALTIES
- 106.0 Add the following three sections:
- 106.7 Violations. Any person, the owner or the owner’s authori…
- 106.8 Any person, the owner or the owner’s authorized agent, w…
- 106.9 It shall be unlawful for any person to interfere with th…
- Section 107.0 — BOARD OF APPEALS
- 107.0 Replace this title and entire section as follows:
- 107.0 [ ← ] Board of Examiners. Applicants may appeal decision…
- Section 302.2 — ALTERNATE MATERIALS AND METHODS OF CONSTRUCTION
- Section 504.3 — DOMESTIC RANGE
- 504.3 Add a second paragraph as follows:
- Section 802.2 — CONNECTION TO VENTING SYSTEMS
- Section 802.6 — GAS VENTS
- Section 802.8 — THROUGH-THE-WALL VENT TERMINATIONS
- 802.8 Revise the first sentence of this section and add an exc…
- 802.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- Section 925.0 — INCINERATORS AND CREMATORIES
- 925.1 Add the following sentence as a second paragraph:
- Section 1013.0 — INSPECTIONS AND TESTS
- 1013.1 Revise this section as follows:
- 1013.1 General. An installation for which a permit is required…
- 1013.2 Revise this section as follows:
- 1013.2 Operating Permit.
- 1013.3 Revise this section as follows:
- 1013.3 Maintenance Inspection. The Authority Having Jurisdicti…
- 1013.7 Revise the second paragraph as follows:
- Section 101.0 — GENERAL
- 101.1 Revise this section as follows:
- 101.1 Title. This document shall be known as the “ [ ← ] 2022 …
- Section 103.0 — DUTIES AND POWERS OF THE AUTHORITY HAVING JURI…
- 103.1 Replace the third paragraph with the following:
- 103.4 Revise the first paragraph of this section as follows:
- 103.4 Right of Entry. Where it is necessary to make an inspect…
- 103.5 Add the following section:
- 103.5 Rules and Regulations. The Authority Having Jurisdiction…
- 103.6 Add the following section:
- 103.6 Code Revisions. The Authority Having Jurisdiction shall …
- 103.7 Add the following section:
- 103.7 Modifications. When there are practical difficulties inv…
- Section 104.0 — PERMITS
- 104.1 Add the following as the second paragraph of this section:
- 104.2 Replace Section 104.2(1) and the first paragraph of Sect…
- 104.2 Exempt Work. A permit shall not be required for the foll…
- 104.3 Replace this section as follows:
- 104.3 Application for Permit. [ ← ] Permit applicants shall fi…
- 104.4 Add a new second paragraph to this section as follows:
- 104.5 Replace this section as follows:
- 104.5 Permit Fees. [ ← ] Before any permit is issued, the appl…
- Section 105.0 — INSPECTIONS AND TESTING
- Section 106.0 — VIOLATIONS AND PENALTIES
- 106.3 Replace this section as follows:
- 106.3 Penalties. [ ← ] Any person, the owner or the owner’s au…
- 106.5 Revise this section as follows:
- 106.5 Authority to Disconnect Utilities in Emergencies. The Au…
- Section 107.0 — BOARD OF APPEALS
- 107.0 Replace this title and the entire section as follows:
- Section 108.0 — ABATEMENT OF PUBLIC NUISANCE
- 108.0 Abatement of Public Nuisance. In order to abate a nuisan…
- Section 109.0 — REPAIRS TO DEFECTIVE BUILDING SEWERS
- 109.0 Repairs to Defective Building Sewers
- 109.1 General. Any defective building sewer found to be a nuis…
- 109.2 Cost of Repairs by City and County of San Francisco. Whe…
- 109.3 Plumbing Building Sewer Revolving Fund. A special revolv…
- 109.4 Assessment for Costs. The Authority Having Jurisdiction …
- Section 201.0 — GENERAL
- 201.1 Add the following to the end of the first sentence:
- Section 204.0 — B
- 204.0 Add the following definition:
- Section 208.0 — F
- 208.0 Add the following definition:
- Section 216.0 — N
- Section 218.0 — P
- 218.0 Revise this definition as follows:
- Section 221.0 — S
- 221.0 Add the following definition:
- Section 313.0 — HANGERS AND SUPPORTS
- 313.9 Add the following section:
- 313.9 Materials.
- Section 405 — PROHIBITED FIXTURES
- Section 415.0 — DRINKING FOUNTAINS
- 415.2 Add the following section:
- Section 504.0 — WATER HEATER REQUIREMENTS
- 504.1 Add the following as the first paragraph of this section:
- 504.1 Location. Water Heaters mounted on the exterior of a bui…
- Section 603.0 — CROSS-CONNECTION CONTROL
- 603.1 Add a third paragraph to this section as follows:
- 603.2 Revise Table 603.2 as follows:
- Section 604.0 — MATERIALS
- 604.1 Add the following sentence to the end of the second para…
- Section 606.0 — VALVES
- 606.2 Revise this section as follows:
- 606.2 Fullway Valve. A fullway valve controlling outlets shall…
- 606.3 Revise this section as follows:
- 606.3 Multidwelling Units. In multidwelling units, one or more…
- 606.5 Revise this section as follows:
- 606.5 Control Valve. A control valve shall be installed immedi…
- 606.11 Add the following section:
- 606.11 Backflow Assembly. All buildings four stories or more i…
- Section 609.0 — INSTALLATION, TESTING, UNIONS AND LOCATION
- Section 701.0 — GENERAL
- Section 706.0 — CHANGES IN DIRECTION OF DRAINAGE FLOW
- 706.4 Revise this section as follows:
- 706.4 Vertical to Horizontal. Vertical drainage lines connecti…
- Section 710.0 — DRAINAGE OF FIXTURES LOCATED BELOW THE NEXT UP…
- Section 901.0 — GENERAL
- 901.1 Add the following second paragraph to this section:
- Section 907.0 — VENT STACKS AND RELIEF VENTS
- 907.1 Revise the first sentence of this section as follows:
- 907.1 Drainage Stack. Each drainage stack that extends [ ← ] s…
- 907.3 Add the following section:
- 907.3 Vent Stacks and Relief Vents. Every building in which pl…
- Section 911.0 — CIRCUIT VENTING
- 911.0 Revise this section as follows:
- 911.0 Circuit Venting. Circuit venting is not permitted unless…
- 1001.3 Add the following section:
- 1001.3 Placement and Minimum Size of Building Traps. The build…
- Section 1008.0 — BUILDING TRAPS
- 1008.1 Revise this section as follows:
- 1008.1 General. Building traps shall not be installed except w…
- Section 1016.0 — SAND INTERCEPTORS
- 1016.3 Add the following section:
- Section 1101.0 — GENERAL
- Section 1208.0 — GAS PIPING SYSTEM DESIGN, MATERIALS, AND COMP…