Skip to content

Earlier editions: 20222019

Chapter 6 — WATER SUPPLY AND DISTRIBUTION

609.2 Trenches — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 609.2 · Effective January 1, 2026 · Official source: Building Standards Commission

Water pipes shall not be run or laid in the same trench as building sewer or drainage piping con structed of clay or materials that are not approved for use within a building unless both of the following conditions are met: (1) The bottom of the water pipe shall be not less than 12 inches (305 mm) above the top of the sewer or drain line. (2) The water pipe shall be placed on a solid shelf excavated at one side of the common trench with a clear horizontal distance of not less than 12 inches (305 mm) from the sewer or drain line.

Water pipes crossing sewer or drainage piping constructed of clay or materials that are not approved for use within a building shall be laid not less than 12 inches (305 mm) above the sewer or drainpipe.

Explained in plain English

Guides that cite this section.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Plumbing Code (Title 24, Part 5)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.