Chapter 6 — WATER SUPPLY AND DISTRIBUTION
613.6 Hot-water distribution system serving patient care areas — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-10-23 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 613.6 · Effective January 1, 2026 · Official source: Building Standards Commission
shall be under constant mechanical recirculation to provide continuous hot water at each hot water outlet. Hot water recir- culation piping shall return the recirculation loop back through the hot water source. Non-recirculated fixture branch piping shall not exceed 10 feet (3.05 meters) in length. Dead-end pip- ing (risers with no flow, branches with no fixture) shall not be installed. In renovation projects, dead-end piping shall be removed in the area of renovation. Empty risers, mains, and branches installed for future use shall be permitted.