Appendix B Procedures to Be Followed to Place Gas Equipment in Operation — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) Appendix B · Effective January 1, 2026 · Official source: Building Standards Commission
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC-CG | SFM | HCD 1 | HCD 2 | HCD 1-AC | DSA AC | DSA SS | DSA SS/CC | OSHPD 1 | OSHPD 1R | OSHPD 2 | OSHPD 3 | OSHPD 4 | OSHPD 5 | OSHPD 6 | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopt Entire Chapter | X | X | X | X | X | X | X | X | ||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) | ||||||||||||||||||||||||
| Adopt only those sections that are listed below | ||||||||||||||||||||||||
| Chapter/ |
||||||||||||||||||||||||
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
APPENDIX B
PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT IN OPERATION
The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.
B 101.0 Adjusting the Burner Input.
B 101.1 Adjusting Input. The input rate of the burner shall be adjusted to the proper value in accordance with the appliance manufacturer’s instructions. Firing at a rate in excess of the nameplate rating shall be prohibited. The input rate can be adjusted by either changing the size of a fixed orifice, changing the adjustment of an adjustable orifice, or readjusting the appliance’s gas pressure regulator outlet pressure (where a regulator is provided in the appliance). [NFPA 54:11.1.1, 11.1.1.1]
B 101.2 High Altitude. Gas input ratings of appliances shall be used for elevations up to 2000 feet (610 m). The input ratings of appliances operating at elevations above 2000 feet (610 m), shall be reduced in accordance with one of the following methods:
(1) At the rate of 4 percent for each 1000 feet (305 m) above sea level before selecting appropriately sized appliances.
(2) As permitted by the Authority Having Jurisdiction.
(3) In accordance with the manufacturer’s installation instructions. [NFPA 54:11.1.2]
B 102.0 Primary Air Adjustment. B 102.1 General. The primary air for injection (Bunsen)type burners shall be adjusted for proper flame characteristics in accordance with the appliance manufacturer’s instructions. After setting the primary air, the adjustment means shall be secured in position. [NFPA 54:11.2]
B 103.0 Safety Shutoff Devices.
B 103.1 General. Where a safety shutoff device is provided, it shall be checked for proper operation and adjustment in accordance with the appliance manufacturer’s instructions. Where the device does not turn off the gas supply in the event of pilot outage or other ignition malfunction, the device shall be serviced or replaced with a new device. [NFPA 54:11.3]
B 104.0 Automatic Ignition.
B 104.1 General. Appliances supplied with means for automatic ignition shall be checked for operation within the parameters provided by the manufacturer. Any adjustments made shall be in accordance with the manufacturer’s instal lation instructions. [NFPA 54:11.4]
B 105.0 Protective Devices.
B 105.1 General. Where required by the manufacturer’s installation instructions, all protective devices furnished with the appliance such as a limit control, fan control to blower,
temperature and pressure relief valve, low-water cutoff device, or manual operating features, shall be checked for operation within the parameters provided by the manufacturer. Any adjustments made shall be in accordance with the manufacturer’s installation instructions. [NFPA 54:11.5]
B 106.0 Checking the Draft.
B 106.1 General. Draft hood-equipped appliances shall be checked to verify that there is no draft hood spillage after 5 minutes of main burner operation. [NFPA 54:11.6]
B 107.0 Operating Instructions.
B 107.1 General. Operating instructions shall be furnished and shall be left in a prominent position near the appliance for use by the consumer. [NFPA 54:11.7]