1308.2 Interconnections Supplying Separate Users — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1308.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Where two or more meters, or two or more service regulators where meters are not provided, are located on the same premises and supply separate users, the gas piping systems shall not be interconnected on the outlet side of the meters or service regulators. [NFPA 54:5.2.1] 1308.2.1 Interconnections for Standby Fuels. Where a supplementary gas for standby use is connected downstream from a meter or a service regulator where a meter is not provided, equipment to prevent backflow shall be installed. A three-way valve installed to admit the standby supply and at the same time shut off the reg
«
| APPLIANCE | INPUT (Btu/ |
|---|---|
| Space Heating Units Warm air furnace Single family Multifamily, per unit Hydronic boiler Single family Multifamily, per unit |
100 000 60 000 100 000 60 000 |
| Space and Water Heating Units Hydronic boiler Single family Multifamily, per unit |
120 000 75 000 |
| Water Heating Appliances Water heater, automatic storage 30 to 40 gallon tank Water heater, automatic storage 50 gallon tank Water heater, automatic instantaneous Capacity at 2 gallons per minute Capacity at 4 gallons per minute Capacity at 6 gallons per minute Water heater, domestic, circulating or side-arm |
35 000 50 000 142 800 285 000 428 400 35 000 |
| Cooking Appliances Range, freestanding, domestic Built-in oven or broiler unit, domestic Built-in top unit, domestic |
65 000 25 000 40 000 |
| Other Appliances Refrigerator Clothes dryer, Type 1 (domestic) Gas fireplace direct vent Gas log Barbecue Gaslight |
3000 35 000 40 000 80 000 40 000 2500 |
For SI units: 1000 British thermal units per hour = 0.293 kW
ular supply shall be permitted to be used for this purpose.
[NFPA 54:5.2.2.1 – 5.2.2.2]