Chapter 13 — FUEL GAS PIPING

1308.2 Interconnections Supplying Separate Users — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1308.2 · Effective January 1, 2026 · Official source: Building Standards Commission

Where two or more meters, or two or more service regulators where meters are not provided, are located on the same premises and supply separate users, the gas piping systems shall not be interconnected on the outlet side of the meters or service regulators. [NFPA 54:5.2.1] 1308.2.1 Interconnections for Standby Fuels. Where a supplementary gas for standby use is connected downstream from a meter or a service regulator where a meter is not provided, equipment to prevent backflow shall be installed. A three-way valve installed to admit the standby supply and at the same time shut off the reg

«

APPLIANCE INPUT
(Btu/h approx.)
Space Heating Units
Warm air furnace
Single family
Multifamily, per unit
Hydronic boiler
Single family
Multifamily, per unit


100 000
60 000

100 000
60 000
Space and Water Heating Units
Hydronic boiler
Single family
Multifamily, per unit


120 000
75 000
Water Heating Appliances
Water heater, automatic storage
30 to 40 gallon tank
Water heater, automatic storage
50 gallon tank
Water heater, automatic instantaneous
Capacity at 2 gallons per minute
Capacity at 4 gallons per minute
Capacity at 6 gallons per minute
Water heater, domestic, circulating or side-arm


35 000

50 000

142 800
285 000
428 400
35 000
Cooking Appliances
Range, freestanding, domestic
Built-in oven or broiler unit, domestic
Built-in top unit, domestic

65 000
25 000
40 000
Other Appliances
Refrigerator
Clothes dryer, Type 1 (domestic)
Gas fireplace direct vent
Gas log
Barbecue
Gaslight

3000
35 000
40 000
80 000
40 000
2500

For SI units: 1000 British thermal units per hour = 0.293 kW

ular supply shall be permitted to be used for this purpose.

[NFPA 54:5.2.2.1 – 5.2.2.2]