Chapter 3 — GENERAL REGULATIONS
303.10 Clearance to Combustible Materials — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 303.10 · Effective January 1, 2026 · Official source: Building Standards Commission
Appliances and their vent connectors shall be installed with clearances from combustible material so their operation does not create a hazard to persons or property. Minimum clearances between combustible walls and the back and sides of various conventional types of appliances and their vent connectors are specified in Chapter 8 and Chapter 9, or NFPA 211.
[NFPA 54:9.2.2] Where not provided in this code, listed and unlisted equipment or appliances shall be installed to maintain the required clearances for servicing and to combustible construction in accordance with the listing and the manufacturer’s installation instructions.
303.10.1 Clearance Reduction. Reduced clearances to combustible construction for listed equipment and appliances shall comply with the listing and Table 303.10.1. Where permitted by the manufacturer, and not provided in this code, reduced clearances to combustible construction for unlisted equipment and appliances shall comply with Table 303.10.1. 303.10.1.1 Type I Hood Exhaust System. Reduced clearances for Type I exhaust systems shall be in accordance with Section 507.4.2 through Section 507.4.2.3. Clearances from the duct or the
exhaust fan to the interior surface of enclosures of
combustible construction shall be in accordance with
Section 510.7.3 and clearances shall not be reduced.
303.10.1.2 Product Conveying Ducts. Reduced clearances to combustibles construction for product conveying ducts shall be in accordance with Section 506.10.3 through Section 506.11.6.3.
»
303.10.1.3 Solid-Fuel-Burning Appliances. For solid-fuel-burning appliances, the clearance shall not be less than 12 inches (305 mm) to combustible walls and not less than 18 inches (457 mm) to combustible ceilings. The clearance, after reduction, shall be permitted to be less than 12 inches (305 mm) to combustible walls and less than 18 inches (457 mm) to combustible ceilings. Solid-fuel-burning appliances listed for lesser clearances shall be permitted to be installed in accordance with the manufacturer’s instructions and their listing. TABLE 303.10.1 REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION [1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11]
| [NFPA 54: TABLE 10.2.4] | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| TYPE OF PROTECTION APPLIED TO AND COVERING ALL SURFACES OF COM- BUSTIBLE MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE REQUIRED CLEARANCE WITH NO PROTECTION |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: |
| TYPE OF PROTECTION APPLIED TO AND COVERING ALL SURFACES OF COM- BUSTIBLE MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE REQUIRED CLEARANCE WITH NO PROTECTION |
36 (INCHES) | 36 (INCHES) | 18 (INCHES) | 18 (INCHES) | 12 (INCHES) | 12 (INCHES) | 9 (INCHES) | 9 (INCHES) | 6 (INCHES) | 6 (INCHES) |
| TYPE OF PROTECTION APPLIED TO AND COVERING ALL SURFACES OF COM- BUSTIBLE MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE REQUIRED CLEARANCE WITH NO PROTECTION |
ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) | ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) |
| TYPE OF PROTECTION APPLIED TO AND COVERING ALL SURFACES OF COM- BUSTIBLE MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE REQUIRED CLEARANCE WITH NO PROTECTION |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE. |
| TYPE OF PROTECTION APPLIED TO AND COVERING ALL SURFACES OF COM- BUSTIBLE MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE REQUIRED CLEARANCE WITH NO PROTECTION |
ABOVE (COLUMN 1) |
SIDES AND REAR (COLUMN 2) |
ABOVE (COLUMN 1) |
SIDES AND REAR (COLUMN 2) |
ABOVE (COLUMN 1) |
SIDES AND REAR (COLUMN 2) |
ABOVE (COLUMN 1) |
SIDES AND REAR (COLUMN 2) |
ABOVE (COLUMN 1) |
SIDES AND REAR (COLUMN 2) |
| (1) 31⁄2 inch thick masonry wall without ventilated air space |
–– | 24 | –– | 12 | –– | 9 | –– | 6 | –– | 5 |
| (2) 1⁄2 of an inch insulation board over 1 inch glass fiber or mineral wool batts |
24 | 18 | 12 | 9 | 9 | 6 | 6 | 5 | 4 | 3 |
| (3) 0.024 inch (nominal 24 gauge) sheet metal over 1 inch glass fiber or min- eral wool batts reinforced with wire on rear face with ventilated air space |
18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 |
| (4) 31⁄2 inch thick masonry wall with ventilated air space |
–– | 12 | –– | 6 | –– | 6 | –– | 6 | –– | 6 |
| (5) 0.024 inch (nominal 24 gauge) sheet metal with ventilated air space |
18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 2 |
| (6) 1⁄2 of an inch thick insula- tion board with ventilated air space |
18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 |
| [NFPA 54: TABLE 10.2.4] | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| (7) 0.024 inch (nominal 24 gauge) sheet metal with ventilated air space over 0.024 inch (nominal 24 gauge) sheet metal with ventilated air space |
18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 |
| (8) 1 inch glass fiber or mineral wool batts sand- wiched between two sheets 0.024 inch (nom- inal 24 gauge) sheet metal with ventilated air space |
18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 |
For SI units: 1 inch = 25.4 mm
Notes:
1 Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 2 All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding any intervening protection applied to the combustible material. 3 Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector. 4 Where all clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. [See Figure 303.10.1(2) and Figure 303.10.1(3)] 5 At least 1 inch (25.4 mm) shall be between clearance reduction systems and combustible walls and ceilings for reduction systems using a ventilated air space. 6 Where a wall protector is installed on a single flat wall away from corners, it shall have a minimum 1 inch (25.4 mm) air gap. To provide adequate air circulation, the bottom and top edges, or only the side and top edges, or all edges shall be left open. 7 Mineral wool batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot (lb/ft 3 ) (128 kg/m 3 ) and a minimum melting point of 1500°F (816°C). 8 Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 British thermal unit inch per hour square foot degree Fahrenheit [Btu•in/(h•ft [2] - °F)] [0.1W/(m•K)] or less. 9 At least 1 inch (25.4 mm) shall be between the appliance and the protector. The clearance between the appliance and the combustible surface shall not be reduced below that allowed in Table 303.10.1. 10 All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable. 11 Listed single-wall connectors shall be installed in accordance with the manufacturer’s installation instructions.
Notes: 1 A – Equals the clearance with no protection specified in Table 802.7.3.3 and Table 904.3.2 and in the sections applying to various types of equipment. 2 B – Equals the reduced clearance permitted in accordance with Table 303.10.1. 3 The protection applied to the construction using combustible material shall extend far enough in each direction to make C equal to A.