504.1 General — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 504.1 · Effective January 1, 2026 · Official source: Building Standards Commission
Where not specified in this chapter, exhaust ducts shall be constructed and installed in accordance with
Chapter 6 and shall be airtight as approved by the Authority Having Jurisdiction. Environmental air ducts that have an alternate function as a part of an approved smoke control sys
«
»
tem in accordance with Section 505.7.3 do not require design as Class 1 product-conveying ducts.
Exceptions:
(1) Ductless range hoods where installed in accordance with the manufacturer’s installation instructions.
(2) Condensing clothes dryers where installed in accordance with the manufacturer’s installation instructions.
504.1.1 Backdraft Protection. Exhaust ducts shall terminate outside the building and shall be equipped with backdraft dampers or with motorized dampers that automatically shut where the systems or spaces served are not in use. [OSHPD 1, 1R, 2, 4 & 5] Exception: Back- draft dampers are not required when the exhaust fan must operate continuously.
Exception: Where the exhaust duct does not discharge into a common exhaust plenum and one of the following:
(1) The exhaust fan runs continuously.
(2) The exhaust duct serves space(s) that are not mechanically heated or cooled.
(3) The space served is maintained at positive pressure.