418.3 Ventilation Requirements — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 418.3 · Effective January 1, 2026 · Official source: Building Standards Commission
418.3.1 Aeration Units. The aeration units shall be ven- tilated through a nonrecirculating dedicated ventilation exhaust system. 418.3.2 Capture Box. When the drain is not located in the ETO sterilizer equipment room, ventilation is required by a capture box. 418.3.3 Cylinder Change. When not located in the ETO sterilizer equipment room, exhaust during cylinder change is required by installing a hood that is part of a dedicated ventilation exhaust system, positioned no more than 1 foot (305 mm) above or behind the point where the change of cylinders takes place. 418.3.4 Sterilizer Relief Valve. The ventilation of ster- ilizer relief valve is required through a pipe connected to the outlet of the relief valve exhausted directly to the out- doors at a point high enough to be away from passers by, and not near any windows that open, nor near any air- conditioning or ventilation air intakes. 418.3.5 Ventilation of Sterilizer Door Area. The sys- tem shall be designed to capture the ETO when the door is opened following the completion of the sterilization process. A hood or canopy closed on each end should be installed over the sterilization door. A hood or canopy shall be connected to a dedicated exhaust ventilation system.
Continue researching
Related topics
State and federal sources. Edit the document title or filters, then run your search.
Get a plain-English answer with a citation back to this text.
Ask AI about this code