508.2 Installation of Appliances on Roofs — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-10-19 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 508.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Appliances shall be installed in accordance with the manufacturer’s installation instructions. [NFPA 54:9.4.2.1] 508.2.1 Edge of Roof Clearance. Appliances shall be installed on a well-drained surface of the roof. At least 6 feet (1829 mm) of clearance shall be available between any part of the appliance and the edge of a roof or similar hazard, or rigidly fixed rails, guards, parapets, or other building structures at least 42 inches (1067 mm) in height shall be provided on the exposed side. [NFPA 54:9.4.2.2]
508.2.1.1 Guards and Rails. Guards or rails shall be required where the following exist:
(1) The clearance between the appliance and a roof edge or open end of an equipment platform is less than 6 feet (1829 mm).
(2) The open end of the equipment platform is located more than 30 inches (762 mm) above the roof, floor, or grade below.
Where guards or rails are installed, they shall be constructed so as to prevent the passage of a 21 inch (533 mm) diameter ball, resist the imposed loading conditions, and shall extend not less than 30 inches (762 mm) beyond each side of the equipment or appliance.
Exception: Guards shall not be required where a permanent fall arrest anchorage connector system in accordance with ASSP Z359.1 is installed.
508.2.2 Electrical Power. Appliances requiring an external source of electrical power shall be installed in accordance with NFPA 70. [NFPA 54:9.4.2.3]
508.2.3 Platform or Walkway. Where water stands on the roof at the appliance or in the passageways to the appliance, or where the roof is of a design having a water seal, a suitable platform, walkway, or both shall be provided above the water line. Such platform(s) or walkway(s) shall be located adjacent to the appliance and control panels so that the appliance can be safely serviced where water stands on the roof. [NFPA 54:9.4.2.4]