Central heating furnaces and boilers shall be listed in accordance with the following:
(1) Central heating furnaces and boilers having input ratings up to and including 400 000 Btu/hr (117 kW) shall be listed in accordance with the following as applicable:
(a) Furnaces listed in accordance with CSA/ANSI Z21.47/CSA 2.3.
»
»
(b) Low-pressure boilers listed in accordance with ANSI Z21.13/CSA 4.9. [NFPA 54:10.3.1.1]
(2) Furnaces and boilers having input ratings greater than 400 000 Btu/hr (117 kW) shall be listed or in accordance with Section 904.1(2)(a) and Section 904.1(2)(b). [NFPA 54:10.3.1.2]
(a) Acceptance of unlisted appliances, equipment, and accessories shall be on the basis of engineering methods. [NFPA 54:9.1.1.2]
(b) The unlisted appliance, equipment, or accessory shall be safe and suitable for the proposed service and shall be recommended for the service by the manufacturer. [NFPA 54:9.1.1.3]