Skip to content

Earlier editions: 20222019

Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES

914.6 Atmospheric Vents, Gas Reliefs, or Bleeds — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-10-19 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 914.6 · Effective January 1, 2026 · Official source: Building Standards Commission

Direct gas-fired heating and forced ventilation appliances with valve train components equipped with atmospheric vents, gas reliefs, or bleeds shall have their vent lines, gas reliefs, or bleeds lead to a safe point outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage from insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter.

[NFPA 54:10.8.6]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.